- **summary:** Transmission and Distribution of Gas. (a) A miter joint on steel pipe to be operated at a pressure that produces a hoop stress of 30 percent or more of SMYS may not deflect the pipe more than three degrees.

(b) A miter joint on steel pipe to be operated at a pressure that produces a hoop stress of less than 30 percent, but more than 10 percent, of SMYS may not deflect the pipe more than 12½ deg
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/ny-nycrr-255-233.json
- **markdown:** https://regulus.evalyn.ai/document/ny-nycrr-255-233.md
- **app url:** https://regulus.evalyn.ai/document/ny-nycrr-255-233
- **source url:** https://govt.westlaw.com/nycrr/Document/I505cbdf7cd1711dda432a117e6e0f345?viewType=FullText&originationContext=documenttoc&transitionType=CategoryPageItem&contextData=(sc.Default)
**body:**

(a) A miter joint on steel pipe to be operated at a pressure that produces a hoop stress of 30 percent or more of SMYS may not deflect the pipe more than three degrees.

(b) A miter joint on steel pipe to be operated at a pressure that produces a hoop stress of less than 30 percent, but more than 10 percent, of SMYS may not deflect the pipe more than 12½ degrees and must be a distance equal to one pipe diameter or more away from any other miter joint, as measured from the crotch of each joint.

(c) A miter joint on steel pipe to be operated at a pressure that produces a hoop stress of 10 percent or less of SMYS may not deflect the pipe more than 90 degrees.