# 255.821 Leaks: nonreportable reading.

- **operation:** document
- **citation:** 16 NYCRR 255.821
- **title:** 255.821 Leaks: nonreportable reading.
- **source type:** regulation
- **agency:** New York State Public Service Commission
- **status:** current
- **official:** true
- **published on:** Not available
- **effective on:** Not available
- **summary:** Transmission and Distribution of Gas. Whenever an operator conducts an annual leakage survey of all mains, or a portion of the mains, in its distribution system, any sustained reading of four percent or less gas-in-air on a CGI at an isolated test point outside the curbline or shoulder of the road can be considered a nonreportable reading except where found in manholes, vaults or catch basins.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/ny-nycrr-255-821.json
- **markdown:** https://regulus.evalyn.ai/document/ny-nycrr-255-821.md
- **app url:** https://regulus.evalyn.ai/document/ny-nycrr-255-821
- **source url:** https://govt.westlaw.com/nycrr/Document/I505da85dcd1711dda432a117e6e0f345?viewType=FullText&originationContext=documenttoc&transitionType=CategoryPageItem&contextData=(sc.Default)
**body:**

Whenever an operator conducts an annual leakage survey of all mains, or a portion of the mains, in its distribution system, any sustained reading of four percent or less gas-in-air on a CGI at an isolated test point outside the curbline or shoulder of the road can be considered a nonreportable reading except where found in manholes, vaults or catch basins.
- **truncated:** false
- **body characters:** 358