# CENTRAL NEW YORK OIL AND GAS CO LLC — Warning Letter

- **operation:** document
- **citation:** CPF 120131012W
- **title:** CENTRAL NEW YORK OIL AND GAS CO LLC — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2013-08-08
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.491(c), 192.709(c).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-120131012w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-120131012w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-120131012w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/120131012W
**body:**

Warning Letter involving CENTRAL NEW YORK OIL AND GAS CO LLC. PHMSA's enforcement data identifies the cited regulations as 192.491(c),  192.709(c). The case was opened on 2013-08-08 and is reported as closed as of 2013-08-08. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120131012W_Warning Letter_08082013.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120131012W/120131012W_Warning%20Letter_08082013.pdf

120131012W_Warning Letter_08082013_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120131012W/120131012W_Warning%20Letter_08082013_text.pdf

120131012W_Warning Letter_08082013_text.pdf

U.S. Department Of Transportation Pipeline and 609.989.2171
Hazardous Materials
Safety Administration
820 Bear Tavern Road, Suite 103
West Trenton, NJ 08628
WARNING LETTER
EXPRESS OVERNIGHT DELIVERY
August 8, 2013
Mr. Barry Cigich, VP Ops & Engineering
Inergy Midstream.
Two Brush Creek Boulevard, Suite 200
Kansas City, MO 64112
CPF 1-2013-1012W
Dear Mr. Cigich:
From March 26-30, 2012, a representative of the Pipeline and Hazardous Materials Safety Administration
(PHMSA) pursuant to Chapter 601 of 49 United States Code inspected the Central New York Oil and Gas
(CNYOG) pipeline facilities’ (a subsidiary of Inergy Midstream), procedures and records in Bradford
County, PA, and Owego, NY.
As a result of the inspection, it appears that you have committed probable violations of the Pipeline Safety
Regulations, Title 49, Code of Federal Regulations. The items inspected and the probable violations are:
1. §192.709 Transmission lines; record keeping.
Each Operator shall maintain the following records for transmission lines for the period specified:
(c) A record of each patrol, survey, inspection, and test required by subparts l and M of this part
for at least 5 years or until the next patrol, survey, inspection or test is completed, whichever is
longer.
CNYOG failed to maintain a record of leak surveys conducted on the pipeline for 2009 and 2010 as
required by §192.706. Pursuant to §192.706, leakage surveys of a transmission line must be conducted at
intervals not exceeding 15 months, but at least once each calendar year.
The PHMSA inspector requested leakage survey inspection records for the period 2008-2011. CNYOG
produced records for 2007 and 2011, but not for 2009 and 2010. This finding was discussed with the
operator during the exit interview on 3/29/2012.
CNYOG remarked that they were sure that the survey was done, but the employee who conducted the
inspection has since been seriously ill and incapacitated; and the records could not be retrieved.
2. §192.491 Corrosion control records.
(c) Each operator shall maintain a record of each test, survey, or inspection required by this
subpart in sufficient detail to demonstrate the adequacy of corrosion control measures or that a
corrosive condition does not exist. These records must be retained for at least 5 years, except that
records related to §192.465 (a) and (e) and 192.475(b) must be retained for as long as the pipeline
remains in service.



1-2013-1012W
CNYOG failed to maintain records of annual cathodic protection surveys as required by §192.491(c) for
2009, for each test, or inspection required by §192.465(a).
The PHMSA inspector asked CNYOG to provide annual cathodic protection (CP) survey records, but
CNYOG could only provide records for 2010 and 2011. This finding was discussed with CNYOG in the
exit interview on 3/29/2012.
3. §192.709 Transmission lines; record keeping.
Each Operator shall maintain the following records for transmission lines for the period specified:
(c) A record of each patrol, survey, inspection, and test required by subparts I and M of this part
for at least 5 years or until the next patrol, survey, inspection or test is completed, whichever is
longer
CNYOG failed to maintain valve inspection records for 2009 and 2010 as required by §192.709(c), for
each test, and inspection required by §192.745(a).
The PHMSA inspector asked CNYOG to provide the annual valve inspection records, but CNYOG could
only provide records for 2011. This finding was discussed with CNYOG in the exit interview on
3/29/2012.
Under 49 United States Code, § 60122, you are subject to a civil penalty not to exceed $200,000 per
violation per day the violation persists up to a maximum of $2,000,000 for a related series of violations.
For violations occurring prior to January 4, 2012, the maximum penalty may not exceed $100,000 per
violation per day, with a maximum penalty not to exceed $1,000,000 for a related series of violations. We
have reviewed the circumstances and supporting documents involved in this case, and have decided not to
conduct additional enforcement action or penalty assessment proceedings at this time. We advise you to
correct the items identified in this letter. Failure to do so will result in CNYOG being subject to
additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence on this matter, please
refer to CPF 1-2013-1012W and for each document you submit, please provide a copy in electronic
format whenever possible. Smaller files may be emailed to Byron.Coy@dot.gov. Larger files should be
sent on a CD accompanied by the original paper copy to the Eastern Region Office.
Be advised that all material you submit in response to this enforcement action is subject to being made
publicly available. If you believe that any portion of your responsive material qualifies for confidential
treatment under 5 U.S.C. 552(b), along with the complete original document you must provide a second
copy of the document with the portions you believe qualify for confidential treatment redacted and an
explanation of why you believe the redacted information qualifies for confidential treatment under 5
U.S.C. 552(b).
Sincerely,
Byron Coy, PE
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration
120131012W WL 08082013 Page 2 of 2
- **truncated:** false
- **body characters:** 6022