# RICHMOND, CITY OF — Warning Letter

- **operation:** document
- **citation:** CPF 120150002W
- **title:** RICHMOND, CITY OF — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2015-02-12
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.285(c)(1), 192.605(b)(3).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-120150002w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-120150002w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-120150002w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/120150002W
**body:**

Warning Letter involving RICHMOND, CITY OF. PHMSA's enforcement data identifies the cited regulations as 192.285(c)(1),  192.605(b)(3). The case was opened on 2015-02-12 and is reported as closed as of 2015-02-12. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120150002W_Warning Letter_02122015.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120150002W/120150002W_Warning%20Letter_02122015.pdf

120150002W_Warning Letter_02122015_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120150002W/120150002W_Warning%20Letter_02122015_text.pdf

120150002W_Warning Letter_02122015_text.pdf

U.S. Department Of Transportation Pipeline and 609.989.2171
Hazardous Materials
Safety Administration
820 Bear Tavern Road, Suite 103
West Trenton, NJ 08628
WARNING LETTER
OVERNIGHT EXPRESS MAIL
February 12, 2015
Mr. Robert Steidel
Director, City of Richmond
Department of Public Utilities
730 East Broad Street
Richmond, VA 23219
CPF 1-2015-0002W
Dear Mr. Steidal:
Between February 24 and August 7, 2014, an inspector from the Virginia State Corporation Commission
(VA SCC) acting as Agent for the Pipeline and Hazardous Materials Safety Administration (PHMSA),
Office of Pipeline Safety (OPS), pursuant to Chapter 601 of 49 United States Code inspected the City of
Richmond’s (City) pipeline facilities in Richmond, Virginia.
As a result of the inspection, it appears that you have committed probable violations of the Pipeline Safety
Regulations, Title 49, Code of Federal Regulations. The items inspected and the probable violation(s)
are:
1. §192.605 Procedural manual for operations, maintenance, and emergencies.
(b) Maintenance and normal operations. The manual required by paragraph (a) of this section must
include procedures for the following, if applicable, to provide safety during maintenance and
operations.
(3) Making construction records, maps, and operating history available to appropriate operating
personnel.
The City failed to make accurate construction records, maps, and operating history available to
appropriate operating personnel.
The City’s GIS mapping system had an incorrect valve (retired valve on an old system that was indicated
as an active valve on a live system) that the City attempted to utilize to stop a gas leak.
Evidence is based on VA SCC Notice of Investigation (NOI) to the City, and City responses to the VA
SCC NOI. We understand that the City has corrected the map in question.



1-2015-0002W
2. §192.285 Plastic pipe: Qualifying persons to make joints.
c) A person must be requalified under an applicable procedure, if during any 12-month period that
person:
(1) Does not make any joints under that procedure; or
The City failed to re-qualify an individual to perform mechanical joints during any 12-month period in
which that individual does not make any joints under that procedure.
During this inspection on August 7, 2014, VA SCC staff witnessed a Willbros T & D Services crew
installing mechanical joints on a 4 inch plastic main line. The crew foreman performing the joining did
not have a current plastic joining task certification card. The foreman’s qualification had expired on July
17, 2014, 20 days prior to the date of that the joining work was being done. After this discovery, joints
previously completed by the foreman were removed and re- installed by an individual on the crew that
had current qualifications.
Evidence is based on VA SCC Notice of Investigation (NOI) to the City, and City responses to the VA
SCC NOI.
Under 49 United States Code, § 60122, you are subject to a civil penalty not to exceed $200,000 per
violation per day the violation persists up to a maximum of $2,000,000 for a related series of violations.
For violations occurring prior to January 4, 2012, the maximum penalty may not exceed $100,000 per
violation per day, with a maximum penalty not to exceed $1,000,000 for a related series of violations.
We have reviewed the circumstances and supporting documents involved in this case, and have decided
not to conduct additional enforcement action or penalty assessment proceedings at this time. We advise
you to correct the item(s) identified in this letter. Failure to do so will result in the City being subject to
additional enforcement action.
No reply to this letter is required. If you choose to reply, please address your correspondence to: Byron
Coy, PE, Director, PHMSA Eastern Region, 820 Bear Tavern Road, Suite 103, W. Trenton, NJ 08628
and please refer to CPF 1-2015-0002W. Be advised that all material you submit in response to this
enforcement action is subject to being made publicly available. If you believe that any portion of your
responsive material qualifies for confidential treatment under 5 U.S.C. 552(b), along with the complete
original document you must provide a second copy of the document with the portions you believe qualify
for confidential treatment redacted and an explanation of why you believe the redacted information
qualifies for confidential treatment under 5 U.S.C. 552(b).
Additionally, if you choose to respond to this (or any other case), please ensure that any response letter
pertains solely to one CPF case number.
Sincerely,
Byron Coy, PE
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration
Cc: Mr. James Hotinger, VA SCC
120150002W_WL_02122015 Page 2 of 2