# RICHMOND, CITY OF — Warning Letter

- **operation:** document
- **citation:** CPF 120150012W
- **title:** RICHMOND, CITY OF — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2015-09-03
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.619(a)(1).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-120150012w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-120150012w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-120150012w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/120150012W
**body:**

Warning Letter involving RICHMOND, CITY OF. PHMSA's enforcement data identifies the cited regulation as 192.619(a)(1). The case was opened on 2015-09-03 and is reported as closed as of 2015-09-03. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120150012W_Warning Letter_09032015.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120150012W/120150012W_Warning%20Letter_09032015.pdf

120150012W_Warning Letter_09032015_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120150012W/120150012W_Warning%20Letter_09032015_text.pdf

120150012W_Warning Letter_09032015_text.pdf

U.S. Department Of Transportation Pipeline and 609.989.2171
Hazardous Materials
Safety Administration
820 Bear Tavern Road, Suite 103
West Trenton, NJ 08628
WARNING LETTER
OVERNIGHT EXPRESS DELIVERY
September 03, 2015
Mr. Robert Steidel
Director, City of Richmond
Department of Public Utilities
730 East Broad Street
Richmond, VA 23219
CPF 1-2015-0012W
Dear Mr. Steidel:
On April 22, 2015, an inspector from the Virginia State Corporation Commission (VA SCC) acting as
Agent for the Pipeline and Hazardous Materials Safety Administration (PHMSA), Office of Pipeline
Safety (OPS), pursuant to Chapter 601 of 49 United States Code inspected the City of Richmond’s (City)
pipeline facilities in Richmond, Virginia.
As a result of the inspection, it appears that you have committed probable violations of the Pipeline Safety
Regulations, Title 49, Code of Federal Regulations. The item inspected and the probable violation is:
1. §192.619 Maximum allowable operating pressure: Steel or plastic pipelines.
(a) No person may operate a segment of steel or plastic pipeline at a pressure that exceeds a
maximum allowable operating pressure determined under paragraph (c) or (d) of this section, or
the lowest of the following:
(1) The design pressure of the weakest element in the segment, determined in accordance with
subparts C and D of this part. However, for steel pipe in pipelines being converted under §192.14 or
uprated under subpart K of this part, if any variable necessary to determine the design pressure
under the design formula (§192.105) is unknown, one of the following pressures is to be used as
design pressure. . .
The City operated a segment of pipeline at a pressure that exceeded the maximum allowable operating
pressure determined under §192.619(a)(1).
While preparing to blow down approximately 500 feet of high pressure City main, the City over-
pressured a low pressure (LP) cast iron system when a City employee opened a regulator station tap valve
on an intermediate pressure (IP) line that was connected to a City 12 inch LP main. The pressure of the
LP piping reached approximately 21 inches of water column. The MAOP of the LP system is 12 inches
of water column.
During the inspection, the VA SCC interviewed City personnel and took photos of the City computer
screens. Based on the data shown on the computer screens, discussions with City personnel, and system



1-2015-0012W
telemetry, the LP system was over-pressured for approximately 25 minutes. A City employee opened the
regulator station block valve to purge the 500 feet of intermediate pressure (IP) City main without
verifying that a station bypass valve was closed. The bypass valve was actually in the open position,
which connected the IP blow down gas (at 22 psig) to a City 12 inch LP main. This action caused a
momentary over-pressurization of the LP distribution system.
Evidence is based on the VA SCC Notice of Investigation (NOI) to the City, and the City response to the
VA SCC NOI, City procedures, VA SCC photographs, and interviews with City personnel.
Under 49 United States Code, § 60122, you are subject to a civil penalty not to exceed $200,000 per
violation per day the violation persists up to a maximum of $2,000,000 for a related series of violations.
For violations occurring prior to January 4, 2012, the maximum penalty may not exceed $100,000 per
violation per day, with a maximum penalty not to exceed $1,000,000 for a related series of violations.
We have reviewed the circumstances and supporting documents involved in this case, and have decided
not to conduct additional enforcement action or penalty assessment proceedings at this time. We advise
you to correct the item(s) identified in this letter. Failure to do so will result in the City being subject to
additional enforcement action.
No reply to this letter is required. If you choose to reply, please address your correspondence to: Byron
Coy, PE, Director, PHMSA Eastern Region, 820 Bear Tavern Road, Suite 103, W. Trenton, NJ 08628
and please refer to CPF 1-2015-0012W. Be advised that all material you submit in response to this
enforcement action is subject to being made publicly available. If you believe that any portion of your
responsive material qualifies for confidential treatment under 5 U.S.C. 552(b), along with the complete
original document you must provide a second copy of the document with the portions you believe qualify
for confidential treatment redacted and an explanation of why you believe the redacted information
qualifies for confidential treatment under 5 U.S.C. 552(b).
Additionally, if you choose to respond to this (or any other case), please ensure that any response letter
pertains solely to one CPF case number.
Sincerely,
Byron Coy, PE
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration
Cc: Mr. Massoud Tahamtani, VA SCC
Mr. Jim Fisher, VA SCC
120150012W_Warning Letter_09032015 Page 2 of 2
- **truncated:** false
- **body characters:** 5586