# EQUITRANS MIDSTREAM CORPORATION — Warning Letter

- **operation:** document
- **citation:** CPF 12020019WL
- **title:** EQUITRANS MIDSTREAM CORPORATION — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2020-11-24
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.731(a).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-12020019wl.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-12020019wl.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-12020019wl
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/12020019WL
**body:**

Warning Letter involving EQUITRANS MIDSTREAM CORPORATION. PHMSA's enforcement data identifies the cited regulation as 192.731(a). The case was opened on 2020-11-24 and is reported as closed as of 2020-11-24. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

12020019WL_Operator Response to Notice_02172021_(20-171845).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12020019WL/12020019WL_Operator%20Response%20to%20Notice_02172021_(20-171845).pdf

12020019WL_Warning Letter_11242020_(20-171845).pdf: https://primis.phmsa.dot.gov/enforcement-documents/12020019WL/12020019WL_Warning%20Letter_11242020_(20-171845).pdf

12020019WL_Warning Letter_11242020_(20-171845)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/12020019WL/12020019WL_Warning%20Letter_11242020_(20-171845)_text.pdf

12020019WL_Warning Letter_11242020_(20-171845)_text.pdf

WARNING LETTER
OVERNIGHT EXPRESS DELIVERY
November 24, 2020
Mr. Gregg West
Vice President, Midstream Operations
Equitrans Midstream Corporation
2200 Energy Drive
Canonsburg, PA 15317
CPF 1-2020-019-WL
Dear Mr. West:
From July 27-31, 2020, a representative of the Pipeline and Hazardous Materials Safety
Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code (U.S.C.) inspected
Equitrans Midstream Corporation’s (Equitrans) procedures and records.
As a result of the inspection, it is alleged that you have committed a probable violation of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations (CFR). The item(s) inspected
and the probable violation(s) are:
1. § 192.731 Compressor stations: Inspection and testing of relief devices.
(a) Except for rupture discs, each pressure relieving device in a
compressor station must be inspected and tested in accordance with
§§192.739 and 192.743, and must be operated periodically to determine
that it opens at the correct set pressure.
Equitrans failed to inspect and test each pressure relieving device in a compressor station in
accordance with § 192.743. Specifically, Equitrans failed to determine if three relief devices
located in compressor stations were adequate from the standpoint of capacity by not considering
relief valve inlet and outlet piping in capacity calculations required under § 192.743.
Section 192.743 states in part:



CPF 1-2020-019-WL
(a) Pressure relief devices at pressure limiting stations and pressure regulating
stations must have sufficient capacity to protect the facilities to which they are
connected. Except as provided in §192.739(b), the capacity must be consistent
with the pressure limits of §192.201(a). This capacity must be determined at
intervals not exceeding 15 months, but at least once each calendar year, by
testing the devices in place or by review and calculations.
(b) If review and calculations are used to determine if a device has sufficient
capacity, the calculated capacity must be compared with the rated or
experimentally determined relieving capacity of the device for the conditions
under which it operates. After the initial calculations, subsequent calculations
need not be made if the annual review documents that parameters have not
changed to cause the rated or experimentally determined relieving capacity to
be insufficient.
Equitrans’ Design and Construction Manual, Design Standard, Pressure Control, 7.2 Relief
Device Design and Installation, Section 6.1 Relief Valve Capacity Calculation, Revision Date
8/27/20, required a Relief Valve Calculation form to be created for each new relief device. The
named procedure required the Relief Valve Calculation form to be reviewed if changes occur that
affect the required capacity or releieving capacity.
With regard to inlet piping losses, Equitrans’ Design and Construction Manual, Design Standard,
Pressure Control, 7.2 Relief Device Design and Installation, Section 4. Installation Requirements,
Revision Date 8/27/20, required that the total of all inlet pressure losses not exceed 3% of the relief
device set pressure. The named procedure required that Crane Technical Paper No. 410, Eqn 3-5,
or another approved method be utilized to calculate Inlet Losses at the rated device capacity for
the relieving medium.
With regard to outlet piping losses, Equitrans’ Design and Construction Manual, Design Standard,
Pressure Control, 7.2 Relief Device Design and Installation, Section 4. Installation Requirements,
Revision Date 8/27/20, required that Crane Technical Paper No. 410, Eqn. 3-5, or another
approved method be utilized to calculate pressure losses in vent piping, and that Company
approved software be used to calculate vent piping backpressure.
During the inspection, the PHMSA inspector requested records for capacity calculations of certain
relief valves at compressor stations. The PHMSA inspector reviewed the Required Capacity and
the Calculated Capacity documented within the Equitable Resources Annual Relief Valve/Auto
Shut-off Device Inspection and Capacity Verification Reports for 3 relief valves located at Comet
Compressor Station, Hartson Compressor Station, and Jefferson Compressor Station. The PHMSA
inspector requested the supporting data for the calculations of both required capacity of the source
of overpressure, and calculated capacity of the relief valve. Calculated capacity of the relief valve
referenced the orifice area; however, the calculations were for the relieving device only and did
not include consideration of inlet and outlet piping pressure losses which can limit relieving
capacity.
12020019WL_Warning Letter_11242020_(20-171845)_text Page 2 of 3



CPF 1-2020-019-WL
Therefore, Equitrans failed to determine the adequacy of the capacity of three relief devices located
at compressor stations by failing to consider inlet and outlet piping pressure losses in its
calculations performed pursuant to § 192.743.
Under 49 U.S.C. § 60122 and 49 CFR § 190.223, you are subject to a civil penalty not to exceed
$218,647 per violation per day the violation persists, up to a maximum of $2,186,465 for a related
series of violations. For violation occurring on or after November 27, 2018 and before July 31,
2019, the maximum penalty may not exceed $213,268 per violation per day, with a maximum
penalty not to exceed $2,132,679. For violation occurring on or after November 2, 2015 and before
November 27, 2018, the maximum penalty may not exceed $209,002 per violation per day, with a
maximum penalty not to exceed $2,090,022. For violations occurring prior to November 2, 2015,
the maximum penalty may not exceed $200,000 per violation per day, with a maximum penalty
not to exceed $2,000,000 for a related series of violations. We have reviewed the circumstances
and supporting documents involved in this case, and have decided not to conduct additional
enforcement action or penalty assessment proceedings at this time. We advise you to correct the
item(s) identified in this letter. Failure to do so will result in Equitrans Midstream Corporation
being subject to additional enforcement action.
Be advised that all material you submit in response to this enforcement action is subject to being
made publicly available. If you believe that any portion of your responsive material qualifies for
confidential treatment under 5 U.S.C. 552(b), along with the complete original document you must
provide a second copy of the document with the portions you believe qualify for confidential
treatment redacted and an explanation of why you believe the redacted information qualifies for
confidential treatment under 5 U.S.C. 552(b).
No reply to this letter is required. If you choose to reply, please submit all correspondence in this
matter to Robert Burrough, Director, PHMSA Eastern Region, 840 Bear Tavern Road, Suite 300,
West Trenton, NJ 08628. Please refer to CPF 1-2020-019-WL on each document you submit, and
whenever possible provide a signed PDF copy in electronic format. Smaller files may be emailed
to robert.burrough@dot.gov. Larger files should be sent on USB flash drive accompanied by the
original paper copy to the Eastern Region Office.
Sincerely,
Robert Burrough
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration
12020019WL_Warning Letter_11242020_(20-171845)_text Page 3 of 3
- **truncated:** false
- **body characters:** 8286
