# EASTERN GAS TRANSMISSION AND STORAGE, INC. — Warning Letter

- **operation:** document
- **citation:** CPF 120205006W
- **title:** EASTERN GAS TRANSMISSION AND STORAGE, INC. — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2020-04-07
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 195.420(a).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-120205006w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-120205006w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-120205006w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/120205006W
**body:**

Warning Letter involving EASTERN GAS TRANSMISSION AND STORAGE, INC.. PHMSA's enforcement data identifies the cited regulation as 195.420(a). The case was opened on 2020-04-07 and is reported as closed as of 2020-04-07. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

120205006W_Operator Response to Notice_05142020.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120205006W/120205006W_Operator%20Response%20to%20Notice_05142020.pdf

120205006W_Warning Letter_04072020.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120205006W/120205006W_Warning%20Letter_04072020.pdf

120205006W_Warning Letter_04072020_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/120205006W/120205006W_Warning%20Letter_04072020_text.pdf

120205006W_Warning Letter_04072020_text.pdf

WARNING LETTER
OVERNIGHT EXPRESS DELIVERY
April 7, 2020
Matt Lamb
Vice President, Eastern Pipeline Operations
Dominion Energy Transmission, Inc.
925 White Oaks Boulevard
Bridgeport, WV 26330
CPF 1-2020-5006W
Dear Mr. Lamb:
From July 16-18, 2019, representatives of the Pipeline and Hazardous Materials Safety
Administration (PHMSA), pursuant to Chapter 601 of 49 United States Code (U.S.C.), inspected
Dominion Energy Transmission, Inc.’s (Dominion) propane pipeline system in Pennsylvania and
West Virginia.
As a result of the inspection, it is alleged that you have committed a probable violation of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations (CFR). The item inspected and
the probable violation is:
1. § 195.420 Valve Maintenance
(a) Each operator shall maintain each valve that is necessary for the
safe operation of its pipeline systems in good working order at all times.
Dominion failed to maintain a valve that is necessary for safe operation of its pipeline systems in
good working order at all times. Specifically, a vapor leak was evident at Dominion’s Lower Run
Gate Valve (GA-20) at the time of the inspection and was identified as having been present for
approximately one month prior.
During the field inspection on July 16, 2019, the PHMSA inspectors observed a vapor leak at GA-
20 on the isolation valve between the launcher/receiver trap and the main line. When Dominion
was questioned about the vapor leak, the response was that there had been an on-going problem



CPF 1-2020-5006W
with leakage since the valve was installed and pressurized approximately one month prior.
Dominion then stated that the line was scheduled for blow down within a week, and the repair or
replacement would be attempted at that time. This demonstrates that Dominion was aware of the
condition of the valve but neither disclosed it to PHMSA nor took steps to immediately mitigate
the leak.
Therefore, Dominion failed to maintain its isolation valve at GA-20 in safe working order at all
times, as required by § 195.420(a).
Under 49 U.S.C. § 60122 and 49 CFR § 190.223, you are subject to a civil penalty not to exceed
$218,647 per violation per day the violation persists, up to a maximum of $2,186,465 for a related
series of violations. For violation occurring on or after November 27, 2018 and before July 31,
2019, the maximum penalty may not exceed $213,268 per violation per day, with a maximum
penalty not to exceed $2,132,679. For violation occurring on or after November 2, 2015 and before
November 27, 2018, the maximum penalty may not exceed $209,002 per violation per day, with a
maximum penalty not to exceed $2,090,022. For violations occurring prior to November 2, 2015,
the maximum penalty may not exceed $200,000 per violation per day, with a maximum penalty
not to exceed $2,000,000 for a related series of violations. We have reviewed the circumstances
and supporting documents involved in this case, and have decided not to conduct additional
enforcement action or penalty assessment proceedings at this time. We advise you to correct the
item(s) identified in this letter. Failure to do so will result in Dominion Energy Transmission, Inc.
being subject to additional enforcement action.
Be advised that all material you submit in response to this enforcement action is subject to being
made publicly available. If you believe that any portion of your responsive material qualifies for
confidential treatment under 5 U.S.C. 552(b), along with the complete original document you must
provide a second copy of the document with the portions you believe qualify for confidential
treatment redacted and an explanation of why you believe the redacted information qualifies for
confidential treatment under 5 U.S.C. 552(b).
No reply to this letter is required. If you choose to reply, please submit all correspondence in this
matter to Robert Burrough, Director, PHMSA Eastern Region, 840 Bear Tavern Road, Suite 300,
West Trenton, NJ 08628. Please refer to CPF 1-2020-5006W on each document you submit, and
whenever possible provide a signed PDF copy in electronic format. Smaller files may be emailed
to robert.burrough@dot.gov. Larger files should be sent on USB flash drive accompanied by the
original paper copy to the Eastern Region Office.
Sincerely,
Robert Burrough
Director, Eastern Region
Pipeline and Hazardous Materials Safety Administration
120205006W_Warning Letter_04072020_text Page 2 of 2
- **truncated:** false
- **body characters:** 5296