# FLORIDA GAS TRANSMISSION CO — Warning Letter

- **operation:** document
- **citation:** CPF 220071002W
- **title:** FLORIDA GAS TRANSMISSION CO — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2007-01-11
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.605(a).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-220071002w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-220071002w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-220071002w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/220071002W
**body:**

Warning Letter involving FLORIDA GAS TRANSMISSION CO. PHMSA's enforcement data identifies the cited regulation as 192.605(a). The case was opened on 2007-01-11 and is reported as closed as of 2007-01-11. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220071002W_Operator Response_01302007.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220071002W/220071002W_Operator%20Response_01302007.pdf

220071002W_Operator Response_03302007.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220071002W/220071002W_Operator%20Response_03302007.pdf

220071002W_Warning Letter_01112007.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220071002W/220071002W_Warning%20Letter_01112007.pdf

220071002W_Warning Letter_01112007.pdf

@
U.5. Deportmenf
of Trqnsportqlion
Pipellne ond
Hozordous Moferlots Sotety
Admlnl3lrqlion
233 Peachtr€e Slreet Ste. 600
Atlanta, GA 30303
WARNING LETTER
CERTIFIED MAIL. RETURN RECEIPT REOUESTED
January 11,2007
Eric J. Amundsen
Vice President Technical Services
Florida Gas Transmission Company
5444 Westheimer Road
Houston. T){77056-5306
cPF 2-2007-1002w
Dear Mr. Amundsen:
On April 3-6,2006., a representative of the Pipeline and Hazardous Materials Safety
Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code inspectSd
maintenance records in your office in Tallahassee, Florida.
As a result of the inspection, it appears that you have committed a probable violation of the
Pipeline Safety Regulations Title 49, Code of Federal Regulations. The item inspected and the
probable violation is:
$192.605 Procedural manual for operations, maintenance, and emergencies.
(a) General. Each operator shall prepare and follow for each pipeline, a manual of
written procedures for conducting operations and maintenance activities and for
emergency response. tr'or transmission lines, the manual must also include procedures for
handling abnormal operations. This manual must be reviewed and updated by the
operator at intervals not exceeding 15 months, but at least once each calendar year. This
manual must be prepared before operations of a pipeline system commence. Appropriate
parts of the manual must be kept at locations where operations and maintenance
activities are conducted.



Florida Gas Transmission Company uses a computerized database called MP2 to record
compliance inspection data. The MP2 system contains the following specific instructions for
completing pressure regulator inspections:
"ENTER THE FOLLOWING INFORMATION IN COMMENTS WHEN CLOSING WORK
ORDERS"
SET POINT:
, AS FOUND:
, AS LEFT:
LOCK UP: YES/NO.
It was found that in some areas of your company these procedures are not being used and
appear to be viewed by operating personnel as optional. Pressure regulator inspection records
were reviewed for the years 2004 and 2005. In the Munson Team Area, records for 20 pressure
regulators did not contain the required comments.
Under 49 United States Code, § 60122, you are subject to a civil penalty not to exceed
$100,000 for each violation for each day the violations persists up to a maximum of $1,000,000
for any related series of violations. We have reviewed the circumstances and supporting
documents involved in this case, and have decided not to conduct additional enforcement action
or penalty assessment proceedings at this time. We advise you to correct the item identified in
this letter. Be advised that failure to do so will result in Florida Gas Transmission Company
being subject to additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer to
CPF 2-2007-1002W.
Sincerely,
slinda Daughty
Linda Daugherty
Director, Southern Region
Pipeline and Hazardous Materials Safety Administration
2
- **truncated:** false
- **body characters:** 3808