# COLONIAL PIPELINE CO — Notice of Probable Violation

- **operation:** document
- **citation:** CPF 220085005
- **title:** COLONIAL PIPELINE CO — Notice of Probable Violation
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2008-03-26
- **effective on:** Not available
- **summary:** CLOSED notice of probable violation citing 195.567(a), 195.567(c), 195.573(a)(1), 195.573(e), 195.589(c).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-220085005.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-220085005.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-220085005
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/220085005
**body:**

Notice of Probable Violation involving COLONIAL PIPELINE CO. PHMSA's enforcement data identifies the cited regulations as 195.567(a),  195.567(c),  195.573(a)(1),  195.573(e),  195.589(c). The case was opened on 2008-03-26 and is reported as closed as of 2010-08-02. Proposed civil penalty: $135,000. Assessed civil penalty: $135,000. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220085005_Final Order_07122010  .pdf: https://primis.phmsa.dot.gov/enforcement-documents/220085005/220085005_Final%20Order_07122010%20%20.pdf

220085005_Final Order_07122010_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220085005/220085005_Final%20Order_07122010_text.pdf

220085005_nopv letter_03262008.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220085005/220085005_nopv%20letter_03262008.pdf

220085005_nopv letter_03262008_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220085005/220085005_nopv%20letter_03262008_text.pdf

220085005_operator response to notice_04302008.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220085005/220085005_operator%20response%20to%20notice_04302008.pdf

220085005_Final Order_07122010_text.pdf

JUL 12 2010
Mr. Tim Felt
President and Chief Executive Officer
Colonial Pipeline Company
1185 Sanctuary Parkway, Suite 100
Alpharetta, GA 30009-4738
RE: CPF 2-2008-5005
Dear Mr. Felt:
Enclosed please find the Final Order issued in the above-referenced case. It makes findings of
violation and assesses a civil penalty of $135,000. The penalty payment terms are set forth in the
Final Order. This enforcement action closes automatically upon payment. Service of the Final
Order by certified mail is deemed effective upon the date of mailing, or as otherwise provided
under 49 C.F.R. § 190.5.
Thank you for your cooperation in this matter.
Sincerely,
Jeffrey D. Wiese
Associate Administrator
for Pipeline Safety
Enclosure
cc: Mr. Doug Belden, General Manager, Colonial Pipeline Company
Mr. Wayne Lemoi, Director, Southern Region, PHMSA
CERTIFIED MAIL - RETURN RECEIPT REQUESTED [7005 1160 0001 0039 0584]



U.S. DEPARTMENT OF TRANSPORTATION
PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION
OFFICE OF PIPELINE SAFETY
WASHINGTON, D.C. 20590
______________________________
In the Matter of )
)
Colonial Pipeline Company, ) CPF No. 2-2008-5005
)
Respondent. )
______________________________)
FINAL ORDER
From November 27, 2007 to December 14, 2007, pursuant to 49 U.S.C. § 60117, a representative
of the Pipeline and Hazardous Materials Safety Administration (PHMSA), Office of Pipeline
Safety (OPS), conducted an on-site pipeline safety inspection of Colonial Pipeline Company’s
(Respondent or Colonial) facilities in South Carolina, Georgia, and Tennessee, and of company
records in Austell, Chattahoochee, and Ringgold, GA, and in Belton and Spartanburg, SC.
Based in Alpharetta, Georgia, Colonial Pipeline delivers gasoline, home heating oil, aviation fuel
and other refined petroleum products throughout the southern and eastern United States.
As a result of the inspection, the Director, Southern Region, OPS (Director), issued to
Respondent, by letter dated March 26, 2008, a Notice of Probable Violation, Proposed Civil
Penalty and Warning (Notice). In accordance with 49 C.F.R. § 190.207, the Notice proposed
finding that Respondent had committed certain violations of 49 C.F.R. Part 195 and proposed
assessing a civil penalty of $135,000 for the alleged violations. The Notice also proposed finding
that Respondent had committed certain other probable violations of 49 C.F.R. Part 195 and
warning Respondent to take appropriate corrective action or be subject to future enforcement
action.
Respondent responded to the Notice by letter dated April 30, 2008 (Response). With the
exception of Item 4A discussed below, Colonial did not dispute the allegations. Respondent
offered information explaining its actions in regard to the other items and requested that the
proposed penalty be reduced. Respondent did not request a hearing and therefore has waived its
right to one.
FINDINGS OF VIOLATION
The Notice alleged that Respondent violated 49 C.F.R. Part 195, as follows:
Item 3: The Notice alleged that Respondent violated 49 C.F.R. § 195.573(a)(1), which states:



2
§ 195.573 What must I do to monitor external corrosion control?
(a) Protected pipelines. You must do the following to determine
whether cathodic protection required by this subpart complies with
§ 195.571:
(1) Conduct tests on the protected pipeline at least once each calendar
year, but with intervals not exceeding 15 months. . . .
The Notice alleged that Respondent violated 49 C.F.R. § 195.573(a)(1) by failing to perform
tests to monitor external corrosion control at least once each calendar year, but with intervals not
exceeding 15 months, to determine whether its cathodic protection (CP) system complied with
49 C.F.R. § 195.571. Specifically, the Notice alleged that Colonial’s CP survey records showed
that tests had not been conducted within the required intervals, as evidenced by the following
information:
A. Line 02, Milepost 1835+28 Ridge Road. Surveys were not performed in 2005
and 2006 calendar years.
07/08/04: -1.4v
09/16/05: 0v (remarks indicate test lead was not found)
07/24/06: 0v (remarks indicate test lead was not found)
08/06/07: -1.986v;
B. Line 13, Milepost 635+73 Paces Ferry Rd. Surveys were not performed in
2005 and 2006 calendar years.
08/10/04: -0.915v
10/05/05: no reading (remarks indicate bad test lead)
08/13/06: no reading, no remarks
08/29/06: 0v (remarks indicate test station not found)
11/07/07: -0.974v;
C. Line 15, Milepost 1124+23 Remington Dr. Survey was not performed in 2005
calendar year.
08/10/04: -1.1v
10/05/05: no reading (remarks indicate test lead was not found)
08/12/06: no reading (remarks convey pipeline does not cross Remington)
08/29/06: -1.142v;
D. Line 16, Milepost 1356+28 PPL Xing. Surveys were not performed in 2004,
2005, and 2006 calendar years.
08/25/04: no reading (remarks indicate vegetation overgrowth, unable to
find)
10/03/05: 0v
08/27/06: no reading (remarks indicate test station not found)
11/10/07: -0.889v;



3
E. Line 16, Milepost 1378+78 Hwy. 29. Surveys were not performed in 2004 and
2005 calendar years.
08/30/04: no reading (remarks indicate no test station)
10/03/05: no reading, no remarks
08/26/06: -1.004v;
F. Line 19 Milepost 6801+78 L&N Railroad spur. Surveys were not performed in
2005 and 2006 calendar years.
10/13/05: 0.000 (remarks indicate not found)
12/13/06: no reading (remarks indicate not found)
12/01/07: -1.369v;
G. Line 19 Milepost 6582+50 Sewer Crossing. Survey was not performed in
2005 calendar year. The 15-month maximum time interval was exceeded in 2007
by at least 13 days (date of PHMSA inspection).
10/11/05: 0.000 (remarks indicate test station could not be found).
08/30/06: -1.022v
12/01/07: 0.000 (remarks indicate test station could not be found);
H. Line 20, I-265 (East side) Milepost 6965+06. Surveys were not performed in
2004 and 2005 calendar years.
07/30/04: no reading (remarks indicate markers were present, but test
station was not).
10/24/05: no reading (remarks indicate no test station was found)
12/12/06: -1.880v;
I. Line 20 Milepost 10+72 Span. Records indicate this location was not surveyed
in calendar year 2005;
J. Line 01, Milepost 1329+91 Rector Road. Survey was not performed in
calendar year 2006. Surveys were conducted on March 4, 2005 and May 10,
2007;
K. Line 20: The maximum allowed 15-month time period between the 2006 and
2007 surveys was exceeded at 22 test stations between Mileposts 3185+06 and
4474+09. Times exceeding the 15-month interval vary from 27 days to 56 days;
L. Sweetwater Pump Station surveys were performed on 08/08/06 and 11/16/07.
The 15-month maximum time interval was exceeded by 8 days.
In its Response, Colonial did not dispute these allegations but explained that it had an ongoing
corrosion control program in place to address test readings of cathodic protection levels that did
not meet one or more of its criteria. The company indicated that it had reviewed its procedures
relating to the scheduling and evaluation of annual surveys and that it planned to make certain



4
improvements to the procedures to ensure that future tests were completed within the time
requirements. Respondent stated that cathodic protection tests had been conducted in 2007 at all
locations, except for the location reflected in Item 3G. Colonial indicated that a new test station
would be installed at Line 19 Milepost 6582+50 Sewer Crossing and a test scheduled.
Respondent stated that it adhered to the continuing use of successfully applied criteria on its
pipeline system, as referenced in NACE International Standard RP 0169.
Accordingly, after considering all the evidence, I find that Respondent violated 49 C.F.R.
§ 195.573(a) (1) by failing to conduct tests to monitor external corrosion control on its protected
pipeline at least once each calendar year, with intervals not exceeding 15 months, to determine
whether its CP system complied with 49 C.F.R. § 195.571. Specifically, I find that Colonial’s
records reveal 12 instances (3A-3L) from 2004 to 2007 of its failure to complete tests within the
required interval.
Item 4: The Notice alleged that Respondent violated 49 C.F.R. §§ 195.573(e) and 195.401(b),
which state, in relevant part:
§ 195.573 What must I do to monitor external corrosion control?
(a) . . .
(e) Corrective action. You must correct any identified deficiency in
corrosion control as required by § 195.401(b). However, if the deficiency
involves a pipeline in an integrity management program under § 195.452, you
must correct the deficiency as required by § 195.452(h).
§ 195.401 General requirements.
(a) . . .
(b) Whenever an operator discovers any condition that could adversely
affect the safe operation of its pipeline system, it shall correct it within a
reasonable time. However, if the condition is of such a nature that it presents
an immediate hazard to persons or property, the operator may not operate the
affected part of the system until it has corrected the unsafe condition.
The Notice alleged that Respondent violated 49 C.F.R. § 195.573 by failing to correct certain
identified deficiencies in corrosion control, as required by § 195.401(b). Specifically, it alleged
that Colonial failed, within a reasonable time, to correct certain deficiencies that could adversely
affect the safe operation of its pipeline. PHMSA has generally considered a “reasonable time” to
be the maximum time allowed between required annual cathodic protection surveys (15 months
maximum from the discovery of a deficient survey reading).
The inspection revealed the following deficiencies:
A. Line 02 Milepost 7833+46, Liberty Church Road Survey reading taken on 03/01/06
was deficient. The deficiency was corrected in approximately 18 months.
03/01/06: -0.797v
03/22/07: -0.623v



5
A new cathodic protection system was completed on 08/25/07, with a close
interval survey (CIS) performed on 08/30/07;
B. Line 19 Mileposts 1078+35 Cochran Road, 1141+60 Woods Road, and 1165+60
Fence. Survey readings taken on 07/16/04 were deficient. Records indicate the deficient
conditions were not corrected until at least after 11/28/06 (28 + months from discovery).
Survey readings for these three locations are listed below:
Cochran Road Woods Road Fence
07/16/04: -0.69v 07/16/04: -.064v 07/16/04: -0.645v
09/09/05: -0.72v 09/09/05: -.0655v 09/09/05: -0.803v
11/28/06: -0.672v 11/28/06: -0.621v 11/30/06: -0.717v
09/18/07: -1.064v 09/18/07: -1.411v 09/19/07: -1.436v;
C. Atlanta Junction breakout tanks. No documentation was provided indicating actions
had been taken to correct “low” cathodic protection survey readings within a reasonable
time, as evidenced by the following information:
Tank #333 Bottom
08/23/04: N side -0.528v, W side -0.559v.
11/22/05: N side -0.418v, W side -0.522v.
No documented survey in 2006.
12/06/07 Observed during inspection: N side -0.492v, W side -0.541v. No
voltage on c.p. cable.
12/11/07: N side -0.858v, W side -0.949v;
Tank #334 Bottom
08/23/04: N side -0.394v, S side -0.480v, E side -0.302v, W side -0.445v.
11/22/05: N side -0.306v, S side -0.424v, E side -0.403v, W side -0.325v.
No documented survey in 2006.
12/06/07 Observed during inspection: N side -0.608v, S side -0.748v, E
side -0.780v,
W side -0.680v. No voltage on c.p. cable.
12/11/07: N side -0.508v, S side -0.577v, E side -0.451v, W side -0.571v;
Tank #335 Bottom
08/23/04: W side -0.775v
11/22/05: W side -0.578v
No documented survey in 2006.
12/11/07: W side -0.953v; and
Tank #353 Bottom
11/22/05: N side -0.650v, S side -0.625v, E side -0.626v, W side -0.590v.
No documented survey in 2006.
12/06/07 Observed during inspection: W side -0.810v.



6
12/12/07: N side -0.890v, S side -0.980v, E side -1.012v, W side -0.828v.
In its response to Item 4A, Colonial contested this allegation of violation, arguing that, in
addition to its annual survey, it had completed a CIS of this line segment on March 6, 2006.
Respondent further contended that it had performed additional testing of existing rectifiers and
groundbeds that influenced the area, in order to determine the proper solution to the exception.
The company argued that its records indicated that it had discovered a CP deficiency on
September 1, 2006, which was within the time allowed by §195.452(h) (2), and that an additional
CP system was then designed and installed to remediate the deficient area by August 25, 2007.
Respondent argued that the subject location was evaluated and repaired within a reasonable time
and was therefore consistent with regulatory requirements.
I reject the company’s argument that § 195.452(h)(2) applies to the deficiency identified here.
The requirement under § 195.573(e) that operators correct deficiencies involving pipelines
covered by an Integrity Management (IM) program in accordance with § 195.452(h) does not
supplant the requirement that they correct identified corrosion control deficiencies for such
pipelines within a reasonable time under §195.401(b). Under the integrity management
regulations, once an operator discovers an anomalous condition on its pipeline through the
integrity assessment process, it must promptly, but no later than 180 days after such assessment,
ascertain whether the condition “presents a potential threat to the integrity of the pipeline.” If so,
then the operator must establish a schedule for further evaluation and remediation of such
conditions based upon a prioritization of risk.
I interpret 49 C.F.R. § 195.573(e) to mean that corrosion control deficiencies identified through
an operator’s IM program may be corrected according to a prioritized schedule based upon risk,
but that such schedule does not negate or supplant the requirement that deficiencies identified
through an operator’s regular corrosion control program be corrected within a reasonable time.
To read the regulation otherwise would mean that corrosion control deficiencies on pipelines
located in higher-risk areas covered by an IM program could be remediated less promptly that
those located in lower-risk locations.
Respondent has not provided any evidence that the CP deficiency discovered on 03/01/06 was
corrected within a reasonable time. The risk of corrosion on the pipeline significantly increases
without proper cathodic protection systems. Accordingly, I find that Respondent’s records show
it failed to correct the identified corrosion control deficiencies within a reasonable time, as
required by § 195.573(e).
In its response to Item 4B, Colonial explained that it had addressed many areas for corrosion
each year, but the time required to determine if a deficiency actually existed (discovery of a
deficiency) and to make repairs varied, depending up conditions at each site. Colonial contended
that the timeline for making the required corrections in these particular locations was extended,
primarily due to difficult local site conditions and local permit requirements, and that
remediation had been made prior to the PHMSA inspection.



7
Respondent asserted that numerous attempts had been made in 2005 and 2006 to identify
locations to install new CP systems, but there was a lack of available electrical power in the areas
and that necessary right-of-way easements had not been obtained until 2007. While this may
have been true, it does not constitute a valid defense to the allegation of violation. Accordingly,
I find that Respondent’s records show it failed to correct the identified corrosion control
deficiencies within a reasonable time, as required by § 195.573(e).
In its response to Item 4C, Colonial explained that it had performed investigations and repairs of
the Atlanta Journal breakout tanks identified in the Notice and had completed the proposed
corrective actions. Accordingly, I find that Respondent’s records show it failed to correct the
identified corrosion control deficiencies within a reasonable time, as required by § 194.573(e).
Respondent has presented evidence showing that it has now completed follow-up investigations
and repairs, but not that any attempts were made to achieve compliance prior to the PHMSA
inspection. Respondent has an affirmative duty to achieve and maintain compliance. To
demonstrate compliance, operators must provide relevant documentation and records during a
pipeline safety inspection, as required by Federal pipeline safety laws and regulations. Having
considered information relative to Items 4(a)-(c), and after considering all the evidence, I find
Respondent violated 49 C.F.R. § 195.573(e) by failing to correct, within a reasonable time, the
cited deficiencies in corrosion control.
These findings of violation will be considered prior offenses in any subsequent enforcement
action taken against Respondent.
ASSESSMENT OF PENALTY
Under 49 U.S.C. § 60122, Respondent is subject to a civil penalty not to exceed $100,000 per
violation for each day of the violation, up to a maximum of $1,000,000 for any related series of
violations. In determining the amount of a civil penalty under 49 U.S.C. § 60122 and 49 C.F.R.
§ 190.225, I must consider the following criteria: the nature, circumstances, and gravity of the
violation, including adverse impact on the environment; the degree of Respondent’s culpability;
the history of Respondent’s prior offenses; the Respondent’s ability to pay the penalty and any
effect that the penalty may have on its ability to continue doing business; and the good faith of
Respondent in attempting to comply with the pipeline safety regulations. In addition, I may
consider the economic benefit gained from the violation without any reduction because of
subsequent damages, and such other matters as justice may require. The Notice proposed a total
civil penalty of $135,000 for the violations cited above.
The Notice in Item 3 proposed a civil penalty of $52,000 for Respondent’s violation of 49
C.F.R. § 195.573(a) (1), for failing to perform CP tests at least once each calendar year, with
intervals not exceeding 15 months. Inspection and testing at the required intervals are essential
to knowing that the pipeline equipment is being maintained, that it will function properly, and
that its integrity has not been compromised. Colonial requested a reduction in the proposed civil
penalty based on its good faith efforts to correct the deficiencies before the PHMSA inspection



8
and before the Notice was issued. I am not persuaded in this case that non-compliant test survey
frequencies could somehow be “corrected” after the fact or that such efforts demonstrate “good
faith” in attempting to achieve compliance. Respondent has not shown any circumstance that
would have prevented it from conducting CP tests on the pipeline within the required intervals or
that would have justified its failure to do so. Respondent has not shown any circumstances that
would justify reduction of the proposed civil penalty. Accordingly, having reviewed the record
and considered the assessment criteria, I assess Respondent a civil penalty of $52,000, for
violation of § 195.573(a) (1).
The Notice in Item 4 proposed a civil penalty of $83,000 for Respondent’s violation of
§ 195.573(e), for failing to correct identified corrosion control deficiencies within a reasonable
time, as required by § 195.401(b). An operator must provide protection for pipeline segments
through preventive and mitigative measures to prevent a pipeline failure and to mitigate the
consequences of a failure. The regulation requires safety precautions that minimize the risk of
accident or injury to human life, the environment and property. Colonial requested a reduction in
the amount of the proposed civil penalty because it disagreed that Item 4A constituted a violation
and because it had corrected the alleged deficiencies before the PHMSA inspection and before
the Notice was issued. During a pipeline safety inspection, operators must provide the
documentation and records to demonstrate compliance, as required by Federal pipeline safety
laws and regulations. Respondent failed to demonstrate compliance during the inspection or
during the post-inspection exit interview. Respondent has not shown any circumstances that
would justify reduction of the proposed civil penalty. Preventive maintenance is critical to the
safety of the public, environment and property. I find that the penalty proposed for this violation
is proportionate to the danger posed by the violation. Accordingly, having reviewed the record
and considered the assessment criteria, I assess Respondent a civil penalty of $83,000, for
violation of 49 C.F.R. § 195.573(e).
Furthermore, I find that Respondent has the ability to pay the penalties discussed above without
adversely affecting its ability to continue in business. Accordingly, having reviewed the record
and considered the assessment criteria, I assess Respondent a total civil penalty of $135,000.
Payment of the civil penalty must be made within 20 days of service. Federal regulations
(49 C.F.R. § 89.21(b)(3)) require this payment be made by wire transfer, through the Federal
Reserve Communications System (Fedwire), to the account of the U.S. Treasury. Detailed
instructions are contained in the enclosure. Questions concerning wire transfers should be
directed to: Financial Operations Division (AMZ-341), Federal Aviation Administration, Mike
Monroney Aeronautical Center, P.O. Box 269039, Oklahoma City, OK 73125; The Financial
Operations Division telephone number is (405) 954-8893.
Failure to pay the $135,000 civil penalty will result in accrual of interest at the current annual
rate in accordance with 31 U.S.C. § 3717, 31 C.F.R. § 901.9 and 49 C.F.R. § 89.23. Pursuant to
those same authorities, a late penalty charge of six percent (6%) per annum will be charged if
payment is not made within 110 days of service. Furthermore, failure to pay the civil penalty
may result in referral of the matter to the Attorney General for appropriate relief in a district
court of the United States.



9
WARNING ITEMS
With respect to Items 1, 2 and 5, the Notice alleged probable violations of Part 195 but did not
propose civil penalties or a compliance order for these items. Therefore, these are considered to
be warning items. The warnings were for:
49 C.F.R. § 195.567(a) (Notice Item 1) ─ Respondent’s alleged failure to have an
electrical test lead on Line 19, Milepost 1733+08. Respondent’s annual CP survey
records indicate that the pipeline was normally “probed” to obtain the pipe-to-soil
survey reading. Respondent demonstrated that it had taken certain actions to
address this item by installing a test lead on April 23, 2008;
49 C.F.R. § 195.567(c) (Notice Item 2) ─ Respondent’s alleged failure to
maintain test lead wires in a condition that would enable a person to determine the
pipeline’s CP status and obtain electrical measurements to determine whether the
cathodic protection complied with § 195.571. Colonial demonstrated that it was
taking certain actions to address this item with its corrosion control program by
installing and maintaining test leads at the sites identified in the Notice; and
49 C.F.R. § 195.589(c) (Notice Item 5) ─ Respondent’s alleged failure to
maintain records of the 2006 annual survey of its Atlanta Junction breakout tank
bottoms for as long as the pipeline remained in service, as required by
§§ 195.573(a) (1) and 195.573(d). Respondent demonstrated that it was taking
certain actions to address this item by developing instructions related to retaining
corrosion control information and documents. An evaluation of needed
improvements, if any, was planned by Respondent to ensure that proper records
were maintained.
Respondent presented information in its Response showing that it had taken certain actions to
address the cited items. Having considered such information, I find, pursuant to 49 C.F.R.
§ 190.205, that probable violations of 49 C.F.R. § 195.567(a) (Notice Item 1), 49 C.F.R.
§ 195.567(c) (Notice Item 2) and 49 C.F.R. § 195. 589(c) (Notice Item 5) have occurred and
Respondent is hereby advised to correct such conditions. In the event that OPS finds a violation
for any of these items in a subsequent inspection, Respondent may be subject to future
enforcement action.
Under 49 C.F.R. § 190.215, Respondent has a right to submit a Petition for Reconsideration of
this Final Order. The petition must be sent to: Associate Administrator, Office of Pipeline
Safety, PHMSA, 1200 New Jersey Avenue, SE, East Building, 2nd Floor, Washington, DC
20590, with a copy sent to the Office of Chief Counsel, PHMSA, at the same address. PHMSA
will accept petitions received no later than 20 days after receipt of service of the Final Order by
the Respondent, provided they contain a brief statement of the issue(s) and meet all other
requirements of 49 C.F.R. § 190.215. The filing of a petition automatically stays the payment of
any civil penalty assessed but does not stay any other provisions of the Final Order, including



10
any required corrective actions. If Respondent submits payment of the civil penalty, the Final
Order becomes the final administrative decision and the right to petition for reconsideration is
waived.
The terms and conditions of this Final Order are effective upon service in accordance with 49
C.F.R. § 190.5.
______________________________ _____________________________
Jeffrey D. Wiese Date Issued
Associate Administrator
for Pipeline Safety

220085005_Final Order_07122010  .pdf

U.S. Department of Transportation
1200 New Jersey Ave, S.E.
Pipeline and Hazardous Materials
Washington, D.C. 20590
Safety Administration
'JUL 1 2 2010
Mr. Tim Felt
President and Chief Executive Officer
Colonial Pipeline Company
1185 Sanctuary Parkway, Suite 100
Alpharetta, GA 30009-4738
RE: CPF 2-2008-5005
Dear Mr. Felt:
Enclosed please find the Final Order issued in the above-referenced case. It makes findings of
violation and assesses a civil penalty of $135,000. The penalty payment terms are set forth in the
Final Order. This enforcement action closes automatically upon payment. Service of the Final
Order by certified mail is deemed effective upon the date of mailing, or as otherwise providec
under 49 C.F.R. § 190.5.
Thank you for your cooperation in this matter.
Sincerely,
(
Jeffrey D. Wiese
Associate Administrator
for Pipeline Safety
Enclosure
Mr. Doug Belden, General Manager, Colonial Pipeline Company
Mr. Wayne Lemoi, Director, Southern Region, PHMSA
CERTIFIED MAIL - RETURN RECEIPT REQUESTED [7005 1160 0001 0039 0584]



U.S. DEPARTMENT OF TRANSPORTATION
PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION
OFFICE OF PIPELINE SAFETY
WASHINGTON, D.C. 20590
In the Matter of
)
Colonial Pipeline Company,
CPF No. 2-2008-5005
)
Respondent.
FINAL ORDER
From November 27, 2007 to December 14, 2007, pursuant to 49 U.S.C. § 60117, a representative
of the Pipeline and Hazardous Materials Safety Administration (PHMSA), Office of Pipeline
Safety (OPS), conducted an on-site pipeline safety inspection of Colonial Pipeline Company's
(Respondent or Colonial) facilities in South Carolina, Georgia, and Tennessee, and of company
records in Austell, Chattahoochee, and Ringgold, GA, and in Belton and Spartanburg, SC.
Based in Alpharetta, Georgia, Colonial Pipeline delivers gasoline, home heating oil, aviation fuel
and other refined petroleum products throughout the southern and eastern United States.
As a result of the inspection, the Director, Southern Region, OPS (Director), issued to
Respondent, by letter dated March 26, 2008, a Notice of Probable Violation, Proposed Civil
Penalty and Warning (Notice). In accordance with 49 C.F.R. § 190.207, the Notice proposed
finding that Respondent had committed certain violations of 49 C.F.R. Part 195 and proposed
assessing a civil penalty of $135,000 for the alleged violations. The Notice also proposed finding
that Respondent had committed certain other probable violations of 49 C.F.R. Part 195 and
warning Respondent to take appropriate corrective action or be subject to future enforcement
action.
Respondent responded to the Notice by letter dated April 30, 2008 (Response). With the
exception of Item 4A discussed below, Colonial did not dispute the allegations. Respondent
offered information explaining its actions in regard to the other items and requested that the
proposed penalty be reduced. Respondent did not request a hearing and therefore has waived its
right to one.
FINDINGS OF VIOLATION
The Notice alleged that Respondent violated 49 C.F.R. Part 195, as follows:
Item 3: The Notice alleged that Respondent violated 49 C.F.R. § 195.573(a)(1), which states:



2
$ 195.573 What must I do to monitor external corrosion control?
(a) Protected pipelines.
You must do the following to determine
whether cathodic protection required by this subpart complies with
§ 195.571:
(1) Conduct tests on the protected pipeline at least once each calendar
year, but with intervals not exceeding 15 months....
The Notice alleged that Respondent violated 49 C.F.R. § 195.573(a)(1) by failing to perform
tests to monitor external corrosion control at least once each calendar year, but with intervals not
exceeding 13 months, to determine whether its cathodic protection (CP) system complied with
49 C.F.R. $ 195.571. Specifically, the Notice alleged that Colonial's CP survey records showed
that tests had not been conducted within the required intervals, as evidenced by the following
information:
A. Line 02, Milepost 1835+28 Ridge Road. Surveys were not performed in 2005
and 2006 calendar years.
07/08/04:-1.4v
09/16/05: Ov (remarks indicate test lead was not found)
07/24/06: Ov (remarks indicate test lead was not found)
08/06/07: - 1.986v;
B. Line 13, Milepost 635+73 Paces Ferry Rd. Surveys were not performed in
2005 and 2006 calendar years.
08/10/04: -0.915
10/05/05: no reading (remarks indicate bad test lead)
08/13/06: no reading, no remarks
08/29/06: Ov (remarks indicate test station not found)
11/07/07: -0.974v;
C. Line 15, Milepost 1124+23 Remington Dr. Survey was not performed in 2005
calendar year.
08/10/04: -1.1v
10/05/05: no reading (remarks indicate test lead was not found)
08/12/06: no reading (remarks convey pipeline does not cross Remington)
08/29/06: - 1.142v;
D. Line 16, Milepost 1356+28 PPL Xing. Surveys were not performed in 2004,
2005, and 2006 calendar years.
08/25/04: no reading (remarks indicate vegetation overgrowth. unable to
find)
10/03/05: Ov
08/27/06: no reading (remarks indicate test station not found)
11/10/07: -0.889v;
E. Line 16, Milepost 1378+78 Hwy. 29. Surveys were not performed in 2004 and
2005 calendar years.
08/30/04: no reading (remarks indicate no test station)



3
10/03/05: no reading, no remarks
08/26/06: -1.004v;
F. Line 19 Milepost 6801+78 L&N Railroad spur. Surveys were not performed in
2005 and 2006 calendar years.
10/13/05: 0.000 (remarks indicate not found)
12/13/06: no reading (remarks indicate not found)
12/01/07: -1.369v;
G. Line 19 Milepost 6582+50 Sewer Crossing. Survey was not performed in
2005 calendar year. The 15-month maximum time interval was exceeded in 2007
by at least 13 days (date of PHMSA inspection).
10/11/05: 0.000 (remarks indicate test station could not be found).
08/30/06: -1.022v
12/01/07: 0.000 (remarks indicate test station could not be found);
H. Line 20, I-265 (East side) Milepost 6965+06. Surveys were not performed in
2004 and 2005 calendar years.
07/30/04: no reading (remarks indicate markers were present, but test
station was not).
10/24/05: no reading (remarks indicate no test station was found)
12/12/06: - 1.880v;
I. Line 20 Milepost 10+72 Span. Records indicate this location was not surveyed
in calendar year 2005;
J. Line 01, Milepost 1329+91 Rector Road. Survey was not performed in
calendar year 2006. Surveys were conducted on March 4, 2005 and May 10,
2007;
K. Line 20: The maximum allowed 15-month time period between the 2006 and
2007 surveys was exceeded at 22 test stations between Mileposts 3185+06 and
4474+09. Times exceeding the 15-month interval vary from 27 days to 56 days;
L. Sweetwater Pump Station surveys were performed on 08/08/06 and 11/16/07.
The 15-month maximum time interval was exceeded by 8 days.
In its Response, Colonial did not dispute these allegations but explained that it had an ongoing
corrosion control program in place to address test readings of cathodic protection levels that did
not meet one or more of its criteria. The company indicated that it had reviewed its procedures
relating to the scheduling and evaluation of annual surveys and that it planned to make certain
improvements to the procedures to ensure that future tests were completed within the time
requirements. Respondent stated that cathodic protection tests had been conducted in 2007 at all
locations, except for the location reflected in Item 3G. Colonial indicated that a new test station
would be installed at Line 19 Milepost 6582+50 Sewer Crossing and a test scheduled.



4
Respondent stated that it adhered to the continuing use of successfully applied criteria on its
pipeline system, as referenced in NACE International Standard RP 0169.
Accordingly, after considering all the evidence, I find that Respondent violated 49 C.F.R.
§ 195.573(a) (1) by failing to conduct tests to monitor external corrosion control on its protected
pipeline at least once each calendar year, with intervals not exceeding 15 months, to determine
whether its CP system complied with 49 C.F.R. $ 195.571. Specifically, I find that Colonial's
records reveal 12 instances (3A-3L) from 2004 to 2007 of its failure to complete tests within the
required interval.
Item 4: The Notice alleged that Respondent violated 49 C.F.R. $§ 195.573(e) and 195.401(b),
which state, in relevant part:
§ 195.573 What must I do to monitor external corrosion control?
(e) Corrective action. You must correct any identified deficiency in
corrosion control as required by § 195.401(b). However, if the deficiency
involves a pipeline in an integrity management program under § 195.452, you
must correct the deficiency as required by § 195.452(h).
$ 195.401 General requirements.
(b) Whenever an operator discovers any condition that could adversely
affect the safe operation of its pipeline system, it shall correct it within a
reasonable time. However, if the condition is of such a nature that it presents
an immediate hazard to persons or property, the operator may not operate the
affected part of the system until it has corrected the unsafe condition.
The Notice alleged that Respondent violated 49 C.F.R. § 195.573 by failing to correct certain
identified deficiencies in corrosion control, as required by § 195.401(b). Specifically, it alleged
that Colonial failed, within a reasonable time, to correct certain deficiencies that could adversely
affect the safe operation of its pipeline. PHMSA has generally considered a "reasonable time" to
be the maximum time allowed between required annual cathodic protection surveys (15 months
maximum from the discovery of a deficient survey reading).
The inspection revealed the following deficiencies:
A. Line 02 Milepost 7833+46, Liberty Church Road Survey reading taken on 03/01/06
was deficient. The deficiency was corrected in approximately 18 months.
03/01/06: -0.797v
03/22/07: -0.623
A new cathodic protection system was completed on 08/25/07, with a close
interval survey (CIS) performed on 08/30/07;
B. Line 19 Mileposts 1078+35 Cochran Road, 1141+60 Woods Road, and 1165+60
Fence. Survey readings taken on 07/16/04 were deficient. Records indicate the deficient



5
conditions were not corrected until at least after 11/28/06 (28 + months from discovery).
Survey readings for these three locations are listed below:
Cochran Road
Woods Road
Fence
07/16/04: -0.69v
07/16/04: - 064v
07/16/04: -0.645v
09/09/05: -0.72v
09/09/05: - 0655v
09/09/05: -0.803v
11/28/06: -0.672v
11/28/06: -0.621v
11/30/06: -0.717v
09/18/07: -1.064v
09/18/07: -1.411
09/19/07: -1.436v;
C. Atlanta Junction breakout tanks. No documentation was provided indicating actions
had been taken to correct "low" cathodic protection survey readings within a reasonable
time, as evidenced by the following information
Tank #333 Bottom
08/23/04: N side -0.528v, W side -0.559v.
11/22/05: N side -0.418v, W side -0.522v.
No documented survey in 2006.
12/06/07 Observed during inspection: N side -0.492v, W side -0.541v. No
voltage on c.p. cable.
12/11/07: N side -0.858v, W side -0.949v;
Tank #334 Bottom
08/23/04: N side -0.394v, S side -0.480v, E side -0.302v, W side -0.445v.
11/22/05: N side -0.306v, S side -0.424v, E side -0.403v, W side -0.325v.
No documented survey in 2006.
12/06/07 Observed during inspection: N side -0.608v, S side -0.748v, E
side -0.780v,
W side -0.680v. No voltage on c.p. cable.
12/11/07: N side -0.508v, S side -0.577v, E side -0.451v, W side -0.571v;
Tank #335 Bottom
08/23/04: W side -0.775v
11/22/05: W side -0.578v
No documented survey in 2006.
12/11/07: W side -0.953v; and
Tank #353 Bottom
11/22/05: N side -0.650v, S side -0.625v, E side -0.626v, W side -0.590v.
No documented survey in 2006.
12/06/07 Observed during inspection: W side -0.810v.
12/12/07: N side -0.890v, S side -0.980v, E side - 1.012v, W side -0.828v.
In its response to Item 4A, Colonial contested this allegation of violation, arguing that, in
addition to its annual survey, it had completed a CIS of this line segment on March 6, 2006.
Respondent further contended that it had performed additional testing of existing rectifiers and
groundbeds that influenced the area, in order to determine the proper solution to the exception.
The company argued that its records indicated that it had discovered a CP deficiency on



6
September 1, 2006, which was within the time allowed by $195.452(h) (2), and that an additional
CP system was then designed and installed to remediate the deficient area by August 25, 2007.
Respondent argued that the subject location was evaluated and repaired within a reasonable time
and was therefore consistent with regulatory requirements.
I reject the company's argument that § 195.452(h)(2) applies to the deficiency identified here.
The requirement under § 195.573(e) that operators correct deficiencies involving pipelines
covered by an Integrity Management (IM) program in accordance with § 195.452(h) does not
supplant the requirement that they correct identified corrosion control deficiencies for such
pipelines within a reasonable time under $195.401(b). Under the integrity management
regulations, once an operator discovers an anomalous condition on its pipeline through the
integrity assessment process, it must promptly, but no later than 180 days after such assessment,
ascertain whether the condition "presents a potential threat to the integrity of the pipeline." If so,
then the operator must establish a schedule for further evaluation 
- **truncated:** true