# LA BELLASARA — Warning Letter

- **operation:** document
- **citation:** CPF 220130007W
- **title:** LA BELLASARA — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2013-04-17
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.625(f), 192.723(a), 192.747.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-220130007w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-220130007w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-220130007w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/220130007W
**body:**

Warning Letter involving LA BELLASARA. PHMSA's enforcement data identifies the cited regulations as 192.625(f),  192.723(a),  192.747. The case was opened on 2013-04-17 and is reported as closed as of 2013-04-17. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220130007W_Warning letter_04172013.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220130007W/220130007W_Warning%20letter_04172013.pdf

220130007W_warning letter_04172013_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220130007W/220130007W_warning%20letter_04172013_text.pdf

220130007W_warning letter_04172013_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
April 17, 2013
Mr. Jeffery Young
Property Manager
La Bellasara
464 Golden Gate Point
Sarasota, FL 34236
CPF 2-2013-0007W
Dear Mr. Young:
On February14, 2013, representatives of the Pipeline and Hazardous Materials Safety
Administration (PHMSA), Southern Region, Office of Pipeline Safety, pursuant to Chapter
601 of 49 United States Code, inspected the La Bellasara master meter and downstream
piping and facilities at 464 Golden Gate Point, Sarasota, Florida.
As a result of the inspection, it appears that La Bellasara has committed probable violations of
the Pipeline Safety Regulations, Title 49, Code of Federal Regulations. The items inspected
and the probable violations are as follows:
1. §192.625 Odorization of gas.
... (f) To assure the proper concentration of odorant in accordance with this section,
each operator must conduct periodic sampling of combustible gases using an
instrument capable of determining the percentage of gas in air at which the odor
becomes readily detectable. Operators of master meter systems may comply with
this requirement by-
(1) Receiving written verification from their gas source that the gas has the proper
concentration of odorant; and
(2) Conducting periodic "sniff" tests at the extremities of the system to confirm that
the gas contains odorant.
La Bellasara did not present to the PHMSA inspector any records to demonstrate that it
had assured the proper concentration of odorant in its pipeline system by receiving written
verification from its gas source that the gas has the proper concentration of odorant or by
conducting periodic "sniff" tests at the extremities of the system to confirm that the gas
contains odorant.



2. §192.723 Distribution systems: Leakage surveys.
(a) Each operator of a distribution system shall conduct periodic leakage surveys in
accordance with this section.
(b) The type and scope of the leakage control program must be determined by the
nature of the operations and the local conditions, but it must meet the following
minimum requirements:
... (2) A leakage survey with leak detector equipment must be conducted outside
business districts as frequently as necessary, but at least once every 5 calendar years
at intervals not exceeding 63 months. However, for cathodically unprotected
distribution lines subject to § 192.465(e) on which electrical surveys for corrosion are
impractical, a leakage survey must be conducted at least once every 3 calendar years
at intervals not exceeding 39 months.
La Bellasara did not present to the PHMSA inspector any records to demonstrate that it
had conducted a leakage survey with leak detector equipment at its 9 story buildings with
29 residential units at least once every 5 calendar years and at intervals not exceeding 63
months.
3. §192.747 Valve maintenance: Distribution systems.
(a) Each valve, the use of which may be necessary for the safe operation of a
distribution system, must be checked and serviced at intervals not exceeding 15
months, but at least once each calendar year.
(b) Each operator must take prompt remedial action to correct any valve found
inoperable, unless the operator designates an alternative valve.
La Bellasara did not present to the PHMSA inspector any records to demonstrate that it
had checked and serviced its shut off (or key valve) which may be necessary for the safe
operation of its distribution system at intervals not exceeding 15 months, but at least once
each calendar year.
Under 49 United States Code, § 60122, La Bellasara is subject to a civil penalty not to exceed
$ 200,000 per violation per day the violation persists up to a maximum of $2,000,000 for a
related series of violations. For violations occurring prior to January 4, 2012, the maximum
penalty may not exceed $100,000 per violation per day, with a maximum penalty not to
exceed $1,000,000 for a related series of violations. We have reviewed the circumstances and
supporting documents involved in this case and have decided not to conduct additional
enforcement action or penalty assessment proceedings at this time. We advise you to correct
the items identified in this letter. Failure to do so will result in La Bellasara, being subject to
additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer
to CPF 2-2013-0007W. Be advised that all material you submit in response to this
enforcement action is subject to being made publicly available. If you believe that any
portion of your responsive material qualifies for confidential treatment under 5 U.S.C. 552(b),
along with the complete original document you must provide a second copy of the document
with the portions you believe qualify for confidential treatment redacted and an explanation of
2



why you believe the redacted information qualifies for confidential treatment under 5 U.S.C.
552(b).
Sincerely,
Wayne T. Lemoi
Director, Office of Pipeline Safety
PHMSA Southern Region