# SOUTHSIDE APARTMENTS — Warning Letter

- **operation:** document
- **citation:** CPF 220140011W
- **title:** SOUTHSIDE APARTMENTS — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2014-08-11
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.1015(a), 192.481(a), 192.481(c), 192.625(f)(1), 192.625(f)(2), 192.721(b)(2), 192.747(a).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-220140011w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-220140011w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-220140011w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/220140011W
**body:**

Warning Letter involving SOUTHSIDE APARTMENTS. PHMSA's enforcement data identifies the cited regulations as 192.1015(a),  192.481(a),  192.481(c),  192.625(f)(1),  192.625(f)(2),  192.721(b)(2),  192.747(a). The case was opened on 2014-08-11 and is reported as closed as of 2014-08-11. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220140011W_warning letter_08112014.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220140011W/220140011W_warning%20letter_08112014.pdf

220140011W_warning letter_08112014_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220140011W/220140011W_warning%20letter_08112014_text.pdf

220140011W_warning letter_08112014_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
August 11, 2014
Ms. Valerie Jones
Property Manager
Southside Apartments
2301 Westmont Street
Jacksonville, FL 32207
CPF 2-2014-0011W
Dear Ms Jones:
On June 17, 2014, representatives of the Pipeline and Hazardous Materials Safety Administration
(PHMSA), Southern Region, Office of Pipeline Safety, pursuant to Chapter 601 of 49 United
States Code, inspected the Southside Apartments master meters and downstream piping and
facilities. The Southside Apartments are served by 4 master meters; each meter serves
3 buildings and 60 units.
As a result of the inspection, it appears that Southside Apartments has committed probable
violations of the Pipeline Safety Regulations, Title 49, Code of Federal Regulations. The items
inspected and the probable violations are as follows:
1. §192.481 Atmospheric corrosion control: Monitoring.
(a) Each operator must inspect each pipeline or portion of pipeline that is exposed to
the atmosphere for evidence of atmospheric corrosion, as follows:
Then the frequency of inspection is:
At least once every 3 calendar years, but with intervals
not exceeding 39 months
At least once each calendar year, but with intervals not
exceeding 15 months
If the pipeline is located: Onshore Offshore ... (c) If atmospheric corrosion is found during an inspection, the operator must
provide protection against the corrosion as required by Sec. 192.479.



Southside Apartments did not present records to demonstrate that it had inspected its onshore
pipeline exposed to the atmosphere for evidence of atmospheric corrosion at least once every
3 calendar years, but with intervals not exceeding 39 months.
2. §192.625 Odorization of gas.
... (f) To assure the proper concentration of odorant in accordance with this section,
each operator must conduct periodic sampling of combustible gases using an
instrument capable of determining the percentage of gas in air at which the odor
becomes readily detectable. Operators of master meter systems may comply with this
requirement by-
(1) Receiving written verification from their gas source that the gas has the proper
concentration of odorant; and
(2) Conducting periodic "sniff" tests at the extremities of the system to confirm that
the gas contains odorant.
Southside Apartments did not present records to demonstrate that it had assured the proper
concentration of odorant in its pipeline system by receiving written verification from its gas
source that the gas has the proper concentration of odorant or by conducting periodic "sniff"
tests at the extremities of the system to confirm that the gas contains odorant.
3. §192.721 Distribution systems: Patrolling.
… (b) Mains in places or on structures where anticipated physical movement or
external loading could cause failure or leakage must be patrolled -
… (2) Outside business districts, at intervals not exceeding 7 1/2 months, but at least
twice each calendar year.
Southside Apartments did not present records to show it had patrolled its distribution system
in the residential area at intervals not exceeding 7½ months, but at least twice each calendar
year.
4. §192.747 Valve maintenance: Distribution systems.
(a) Each valve, the use of which may be necessary for the safe operation of a
distribution system, must be checked and serviced at intervals not exceeding 15 months,
but at least once each calendar year.
Southside Apartments did not present records to demonstrate that it had checked and serviced
its shut off (or key valve) which may be necessary for the safe operation of its distribution
system at intervals not exceeding 15 months, but at least once each calendar year.
5. §192.1015 What must a master meter or small liquefied petroleum gas (LPG) operator
do to implement this subpart?
(a) General. No later than August 2, 2011 the operator of a master meter system or a
small LPG operator must develop and implement an IM program that includes a
written IM plan as specified in paragraph (b) of this section. The IM program for these
pipelines should reflect the relative simplicity of these types of pipelines.
Southside Apartments did not present records to demonstrate that it had developed and
2



implemented an IM program.
Under 49 United States Code, § 60122, Southside Apartments is subject to a civil penalty not to
exceed $ 200,000 per violation per day the violation persists up to a maximum of $2,000,000 for
a related series of violations. For violations occurring prior to January 4, 2012, the maximum
penalty may not exceed $100,000 per violation per day, with a maximum penalty not to exceed
$1,000,000 for a related series of violations. We have reviewed the circumstances and supporting
documents involved in this case and have decided not to conduct additional enforcement action
or penalty assessment proceedings at this time. We advise you to correct the items identified in
this letter. Failure to do so will result in the Southside Apartments being subject to additional
enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer to
CPF 2-2014-0011W. Be advised that all material you submit in response to this enforcement
action is subject to being made publicly available. If you believe that any portion of your
responsive material qualifies for confidential treatment under 5 U.S.C. 552(b), along with the
complete original document you must provide a second copy of the document with the portions
you believe qualify for confidential treatment redacted and an explanation of why you believe
the redacted information qualifies for confidential treatment under 5 U.S.C. 552(b).
Sincerely,
Wayne T. Lemoi
Director, Office of Pipeline Safety
PHMSA Southern Region
3
- **truncated:** false
- **body characters:** 6495