# GULF SOUTH PIPELINE COMPANY, LLC — Warning Letter

- **operation:** document
- **citation:** CPF 220161001W
- **title:** GULF SOUTH PIPELINE COMPANY, LLC — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2016-03-02
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.706(a).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-220161001w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-220161001w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-220161001w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/220161001W
**body:**

Warning Letter involving GULF SOUTH PIPELINE COMPANY, LLC. PHMSA's enforcement data identifies the cited regulation as 192.706(a). The case was opened on 2016-03-02 and is reported as closed as of 2016-03-02. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220161001W_Warning Letter_03022016.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220161001W/220161001W_Warning%20Letter_03022016.pdf

220161001W_Warning Letter_03022016_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220161001W/220161001W_Warning%20Letter_03022016_text.pdf

220161001W_Warning Letter_03022016_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
March 2, 2016
Mr. Richard Keyser
Gulf South Pipeline Company, LP
Senior Vice President of Operations
9 Greenway Plaza, Suite 2800
Houston, Texas 77046
CPF 2-2016-1001W
Dear Mr. Keyser:
On October 19-22, 2015, a representative of the Pipeline and Hazardous Materials Safety
Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code inspected
Gulf South Pipeline Company’s (Gulf South) records in Petal, Mississippi.
As a result of the inspection, it appears that Gulf South has committed a probable violation of
the Pipeline Safety Regulations, Title 49, Code of Federal Regulations. The items inspected
and the probable violation is:
1. §192.706 Transmission lines: Leakage surveys.
Leakage surveys of a transmission line must be conducted at intervals not exceeding
15 months, but at least once each calendar year. However, in the case of a
transmission line which transports gas in conformity with §192.625 without an odor
or odorant, leakage surveys using leak detector equipment must be conducted–
(a) In Class 3 locations, at intervals not exceeding 7½ months, but at least twice each
calendar year;
Gulf South did not provide evidence that it conducted leakage surveys using leak detector
equipment on a transmission pipeline, which transports gas without an odor or odorant, in
Class 3 locations at least twice each calendar year, at intervals not exceeding 7 ½ months.
Gulf South records did not indicate leakage surveys were conducted in 2014 and 2015 for
all Class 3 locations on line MS100-001 where gas is transported without an odor or
odorant, as required. On April 29, 2014, Gulf South determined sections of Line MS100-
001 (which transports gas without an odor or odorant) were within Class 3 locations. Gulf
South’s leak survey records for 2014 and 2015, reviewed in October 2015, did not



document all Class 3 locations along Line MS100-001 were surveyed using leak detector
equipment. Gulf South records documented the following:
• On July 7, 2014, a leakage survey using gas detection equipment was conducted
on line MS100-001 from Mile Post 0.937 (Station 49+47) to Mile Post 2.207
(Station 116+53). The records do not document instrumented leakage surveys
were conducted on line MS100-001 in the following Class 3 locations:
o Station 26+93 to station 32+69
o Station 47+71 to Station 49+47
o Station 116+53 to Station 152+85 (north of Forrest Compressor Station)
o Station 136+75 to Station 208+85 (west of Forrest Compressor Station)
• On January 26 and February 26, 2015, leakage surveys using gas detection
equipment were conducted on Line MS100-001 from Station 49+48 to Station
116+57, Station 71+79 to Station 152+85, and Station 136+75 to Station 208+85.
The records do not document instrumented leakage surveys were conducted on
line MS100-001 in the Class 3 location from Station 26+93 to Station 32+69.
Under 49 United States Code, § 60122, you are subject to a civil penalty not to exceed
$200,000 per violation per day the violation persists up to a maximum of $2,000,000 for a
related series of violations. For violations occurring prior to January 4, 2012, the maximum
penalty may not exceed $100,000 per violation per day, with a maximum penalty not to
exceed $1,000,000 for a related series of violations. We have reviewed the circumstances and
supporting documents involved in this case, and have decided not to conduct additional
enforcement action or penalty assessment proceedings at this time. We advise you to correct
the items identified in this letter. Failure to do so will result in Gulf South being subject to
additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer
to CPF 2-2016-1001W. Be advised that all material you submit in response to this
enforcement action is subject to being made publicly available. If you believe that any
portion of your responsive material qualifies for confidential treatment under 5 U.S.C. 552(b),
along with the complete original document you must provide a second copy of the document
with the portions you believe qualify for confidential treatment redacted and an explanation of
why you believe the redacted information qualifies for confidential treatment under 5 U.S.C.
552(b).
Sincerely,
Chris Taylor
Acting Director, Office of Pipeline Safety
PHMSA Southern Region
2