# AMERIGAS PROPANE LP — Warning Letter

- **operation:** document
- **citation:** CPF 220190004W
- **title:** AMERIGAS PROPANE LP — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2019-06-07
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.11(b), 192.465(a), 192.465(d), 192.616(j).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-220190004w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-220190004w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-220190004w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/220190004W
**body:**

Warning Letter involving AMERIGAS PROPANE LP. PHMSA's enforcement data identifies the cited regulations as 192.11(b),  192.465(a),  192.465(d),  192.616(j). The case was opened on 2019-06-07 and is reported as closed as of 2019-06-07. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

220190004W_Warning Letter_06072019.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220190004W/220190004W_Warning%20Letter_06072019.pdf

220190004W_Warning Letter_06072019_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/220190004W/220190004W_Warning%20Letter_06072019_text.pdf

220190004W_Warning Letter_06072019_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
June 7, 2019
Mr. Hugh Gallagher
President and CEO
AmeriGas Propane, LP
460 N. Gulph Road
King of Prussia, PA 19406
CPF 2- 2019-0004W
Dear Mr. Gallagher:
From July 16 to 20, 2018, a representative of the Pipeline and Hazardous Materials Safety
Administration (PHMSA), Southern Region, Office of Pipeline Safety(OPS), inspected
AmeriGas Propane, LP (AmeriGas) liquefied petroleum gas (LP-Gas) records and selected
procedures in AmeriGas’ Fort Lauderdale, Florida, district office and pipeline facilities in
Broward County, Florida, pursuant to Chapter 601 of 49 United States Code (U.S.C.).
As a result of the inspection, it is alleged that AmeriGas has committed probable violations of
the Pipeline Safety Regulations, Title 49, Code of Federal Regulations (CFR). The items
inspected and the probable violations are:
1. § 192.11 Petroleum gas systems.
(a) . . . .
(b) Each pipeline system subject to this part that transports only petroleum gas
or petroleum gas/air mixtures must meet the requirements of this part and of
ANSI/NFPA 58 and 59.
1



AmeriGas failed to meet the requirements of NFPA-58 (2004)1 for each pipeline system
that transports petroleum gas, as follows:
A. NFPA 58 § 5.2.8.3
The markings specified for ASME containers shall be on a stainless steel metal
nameplate attached to the container, located to remain visible after the
container is installed.
(A) . . . .
(B) Where the container is buried, mounded, insulated, or otherwise covered so
the nameplate is obscured, the information contained on the nameplate shall be
duplicated and installed on adjacent piping or on a structure in a clearly visible
location.
(C) . . . .
AmeriGas failed to meet the requirements of NFPA 58 § 5.2.8.32 which, in part,
required that nameplates attached to containers be located to remain visible after the
container installation or, when the nameplate was obscured because the tank was
buried, mounded, insulated, or otherwise covered, that the information contained on
the nameplate was duplicated and installed on adjacent piping or on a structure in a
clearly visible location.3
The PHMSA inspector and AmeriGas employees were unable to locate visible
nameplates attached to containers or the information from the nameplates duplicated
and installed in a clearly visible location for containers as follows:
 Larkdale system – 4 containers (tanks 3, 4, 7, and 8)
 Madison #1 system – 2 containers (tanks 1 and 2)
 Madison #4 system – 1 container (tank 4)
 Madison #5 system – 1 container (tank 5)
 Royal Palm system – 4 containers (tanks 1, 2, 8, and 9)
B. NFPA 58 § 5.7.11.4
Connections to ASME containers installed underground shall be located within
a substantial dome, housing, or manhole and shall have a cover.
(A) . . . .
1 The 2004 edition of NFPA 58, “Liquefied Petroleum Gas Code (LP-Gas Code),” is the edition currently
incorporated, by reference, in §192.7.
2 NFPA 58 (2004) § 5.2.8.3 is referenced here for simplicity. In general, pipeline facilities must meet the design
and construction requirements that are in place at the time of construction. PHMSA acknowledges that
some or all of the ASME containers referenced in this letter were installed prior to incorporation of the
2004 edition of the NFPA 58 standard, and, as such, must meet the design and construction requirements of
the NFPA 58 edition incorporated by reference at the time they were constructed. In citing § 5.2.8.3, of
NFPA 58 (2004), PHMSA is citing the general requirement that the nameplate remain visible after the
containers are installed – a requirement that has existed since, at least, the 1969 edition.
3 The exception allowing the information contained on the nameplate, of a buried tank, to be duplicated and
installed in a clearly visible location was first introduced, in an edition incorporated into 49 C.F.R.
Part 192, in the 1992 edition of NFPA 58.
2



(B) Such manholes or housings shall be ventilated.
(C) The area of ventilation openings shall equal or exceed the combined
discharge areas of the pressure relief devices and other vent lines that discharge
into the manhole or housing.
AmeriGas failed to meet the requirements of NFPA 58 § 5.7.11.4 (B) and (C), which
required, in part, that the area of ventilation openings on underground ASME
containers equaled or exceeded the combined discharge areas of pressure relief
devices and vent lines that discharged into the manhole or housing.
The PHMSA inspector observed and documented manholes or housings for which
the area of ventilation openings did not equal or exceed the combined discharge
areas of pressure relief devices and vent lines that discharged into the manhole or
housing, as follows:
 Larkdale system – 3 containers (tanks 3, 7, and 8)
 Madison #1 system – 2 containers (tanks 1 and 2)
 Madison #4 system – 1 container (tank 4)
 Madison #5 system – 1 container (tank 5)
 Shoppes at Cleary – 1 container (tank 1)
 Royal Palm system – 3 containers (tanks 1, 2, and 8)
C. NFPA 58 § 6.7.2.3
Pressure relief devices on the following ASME containers shall be installed so
that any gas released is vented away from the container upward and
unobstructed to the open air:
(1) Containers of 125 gal (0.5 m3) or more water capacity installed in stationary
service
(2) . . . .
AmeriGas failed to ensure that pressure relief devices on containers of 125 gallons or
more water capacity installed in stationary service were installed so that any gas
released would be vented away from the container upward and unobstructed to the
open air.
The PHMSA inspector identified container relief devices that were installed with
regulators or piping located directly above the relief device such that any gas
released would not be vented away from the container and unobstructed to the open
air, as follows:
 Madison #1 system – relief on tank 2
 Madison #4 system – relief on tank 4
 Royal Palm system – reliefs on tanks 2 and 8
D. NFPA 58 § 6.7.2.4
Rain caps or other means shall be provided to minimize the possibility of the
entrance of water or other extraneous matter into the relief device or any
discharge piping. Provision shall be made for drainage where the accumulation
of water is anticipated.
3



2. 3. NFPA 58 § 6.7.2.5 The rain cap or other protector shall be designed to remain
in place, except during pressure relief device operation and shall not restrict
pressure relief device flow.
AmeriGas failed to meet the requirements of NFPA 58 §§ 6.7.2.4 and 6.7.2.5, which
required it to protect the container relief device from the entrance of water or other
extraneous matter by providing a rain cap or other protector and ensuring that the
rain cap or other protector remained in place.
PHMSA inspectors observed and documented container relief devices with water
and/or extraneous matter in them due to lack of a rain cap or other protection, or the
rain cap or other protection not in place as designed. Container relief devices with
water and/or extraneous matter in them were identified on tank 1 of the Nob Hill
system and tank 2 at the Royal Palm system.
§ 192.465 External corrosion control: Monitoring
(a) Each pipeline that is under cathodic protection must be tested at least once
each calendar year, but with intervals not exceeding 15 months, to determine
whether the cathodic protection meets the requirements of §192.463. […]
AmeriGas failed to test each pipeline under cathodic protection at least once each
calendar year, but with intervals not exceeding 15 months, to determine whether the
cathodic protection met the requirements of §192.463.
AmeriGas did not test its pipelines systems at Nob Hill and the Shoppes at Cleary at least
once in calendar year 2015. Based upon AmeriGas records, testing was conducted on the
Nob Hill system on November 17, 2014, and January 21, 2016, and on the Shoppes at
Cleary system on November 17, 2014, and January 19, 2016. While the testing was
completed within a 15 month interval, it was not completed at least once each calendar
year.
§ 192.465 External corrosion control: Monitoring
(a) . . . .
(d) Each operator shall take prompt remedial action to correct any deficiencies
indicated by the monitoring.
AmeriGas did not take prompt remedial action to correct deficiencies indicated by
external corrosion control monitoring. AmeriGas records showed that AmeriGas
identified low4 tank-to-soil (T/S) potentials during its cathodic protection monitoring in
January 2017, that were not promptly corrected as evidenced by continued low readings
in December 2017, and January 2018.
4 The criteria for cathodic protection are contained in 49 CFR Part 192, Appendix D. The criterion being
referenced in this letter is a negative (cathodic) voltage of at least 850 mV with reference to a saturated
copper-copper sulfate half-cell. Accordingly, a low reading is any reading less negative than -850 mV.
4



The tanks with low T/S potentials and the range of readings5 (in mV) were as follows:
Larkdale
01/31/2017 12/28/2017 01/26/2018
Tank 3 -630 to -490 -600 to -470 -600 to -470
Tank 4 -530 to -270 -520 to -340 -520 to -380
Tank 7 -700 to -320 -520 to -400 -520 to -400
Tank 8 -750 to -500 no readings taken -790 to -580
Tank 9 -870 to -730 no readings taken -450 to -330
4. § 192.616 Public awareness.
(a) . . . .
(j) Unless the operator transports gas as a primary activity, the operator of a
master meter or petroleum gas system is not required to develop a public awareness
program as prescribed in paragraphs (a) through (g) of this section. Instead the
operator must develop and implement a written procedure to provide its customers
public awareness messages twice annually. If the master meter or petroleum gas
system is located on property the operator does not control, the operator must
provide similar messages twice annually to persons controlling the property. […]
AmeriGas failed to meet the requirements of the regulation because it did not deliver
public awareness messages to all persons controlling property upon which its petroleum
gas systems were located. During a field visit, the PHMSA inspector attempted to verify
customer and non-customer addresses whose property contained portions of the
operator’s petroleum gas systems against AmeriGas’ January 2018 public awareness
message mailing list. Numerous non-customer addresses on the Royal Palm system were
not included in the referenced mailing list - specific examples include properties on
NW 26th Avenue, NW 27th Lane, and NW 33rd Terrace.
Under 49 U.S.C. § 60122 and 49 CFR § 190.223, you are subject to a civil penalty not to exceed
$213,268 per violation per day the violation persists, up to a maximum of $2,132,679 for a
related series of violations. For violation occurring on or after November 2, 2015 and before
November 27, 2018, the maximum penalty may not exceed $209,002 per violation per day,
with a maximum penalty not to exceed $2,090,022. For violations occurring prior to November
2, 2015, the maximum penalty may not exceed $200,000 per violation per day, with a maximum
penalty not to exceed $2,000,000 for a related series of violations. We have reviewed the
circumstances and supporting documents involved in this case, and have decided not to conduct
additional enforcement action or penalty assessment proceedings at this time. We advise you
to correct the items identified in this letter. Failure to do so will result in AmeriGas being
subject to additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer
to CPF 2-2019-0004W. Be advised that all material you submit in response to this
5 AmeriGas takes multiple tank-to-soil (T/S) potential readings, typically four, around each tank to test for
adequate levels of cathodic protection. Tanks are not deemed to have adequate cathodic protection until all
readings meet the cathodic protection criterion.
5



enforcement action is subject to being made publicly available. If you believe that any
portion of your responsive material qualifies for confidential treatment under 5 U.S.C. 552(b),
along with the complete original document you must provide a second copy of the document
with the portions you believe qualify for confidential treatment redacted and an explanation of
why you believe the redacted information qualifies for confidential treatment under 5 U.S.C.
552(b).
Sincerely,
James A. Urisko
Director, Office of Pipeline Safety
PHMSA Southern Region
6