# FLINT HILLS RESOURCES, LC — Notice of Probable Violation

- **operation:** document
- **citation:** CPF 32021032NOPV
- **title:** FLINT HILLS RESOURCES, LC — Notice of Probable Violation
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2021-04-26
- **effective on:** Not available
- **summary:** CLOSED notice of probable violation citing 195.264(b)(1), 195.430(c), 195.452(f)(3), 195.452(i)(1), 195.589(c).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-32021032nopv.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-32021032nopv.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-32021032nopv
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/32021032NOPV
**body:**

Notice of Probable Violation involving FLINT HILLS RESOURCES, LC. PHMSA's enforcement data identifies the cited regulations as 195.264(b)(1),  195.430(c),  195.452(f)(3),  195.452(i)(1),  195.589(c). The case was opened on 2021-04-26 and is reported as closed as of 2021-06-08. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

32021032NOPV_Final Order_06082021_(21-210185).pdf: https://primis.phmsa.dot.gov/enforcement-documents/32021032NOPV/32021032NOPV_Final%20Order_06082021_(21-210185).pdf

32021032NOPV_Final Order_06082021_(21-210185)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/32021032NOPV/32021032NOPV_Final%20Order_06082021_(21-210185)_text.pdf

32021032NOPV_Operator Response to Notice_05122021_(21-210185).pdf: https://primis.phmsa.dot.gov/enforcement-documents/32021032NOPV/32021032NOPV_Operator%20Response%20to%20Notice_05122021_(21-210185).pdf

32021032NOPV_PCO_04262021_(21-210185).pdf: https://primis.phmsa.dot.gov/enforcement-documents/32021032NOPV/32021032NOPV_PCO_04262021_(21-210185).pdf

32021032NOPV_PCO_04262021_(21-210185)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/32021032NOPV/32021032NOPV_PCO_04262021_(21-210185)_text.pdf

32021032NOPV_Final Order_06082021_(21-210185)_text.pdf

June 6, 2021
VIA ELECTRONIC MAIL TO: jeff.ramsey@fhr.com
Mr. Jeff Ramsey
President and Chief Executive Officer
Flint Hills Resources, LLC
4111 E. 37th Street North
Wichita, Kansas 67220
Re: CPF No. 3-2021-032-NOPV
Dear Mr. Ramsey:
Enclosed please find the Final Order issued in the above-referenced case. It makes a finding of
violation and finds that the proposed actions to comply with the pipeline safety regulations have
been completed. This case is now closed. Service of the Final Order by electronic mail is
effective upon the date of transmission as provided under 49 C.F.R. § 190.5.
Thank you for your cooperation in this matter.
Sincerely,
Alan K. Mayberry
Associate Administrator
for Pipeline Safety
Enclosures (Final Order and NOPV)
cc: Mr. Gregory Ochs, Director, Central Region, Office of Pipeline Safety, PHMSA
Ms. Kimberly A. Gerold, Manager, Pipeline Safety, Flint Hills Resources, LLC,
kim.gerold@fhr.com
CONFIRMATION OF RECEIPT REQUESTED



U.S. DEPARTMENT OF TRANSPORTATION
PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION
OFFICE OF PIPELINE SAFETY
WASHINGTON, D.C. 20590
In the Matter of )
Flint Hills Resources, LLC, ) CPF No. 3-2021-032-NOPV
)
)
)
Respondent. )
____________________________________)
FINAL ORDER
On April 26, 2021, pursuant to 49 C.F.R. § 190.207, the Director, Central Region, Office of
Pipeline Safety (OPS), issued a Notice of Probable Violation and Proposed Compliance Order
(Notice) to Flint Hills Resources (Respondent). The Notice proposed finding that Respondent
had violated the pipeline safety regulations in 49 C.F.R. Part § 195.264(b)(1) and proposed
certain measures to correct the violation. Respondent did not contest the allegation of violation
or the corrective measures.
Based upon a review of all of the evidence, pursuant to § 190.213, I find Respondent violated the
pipeline safety regulation listed below, as more fully described in the enclosed Notice, which is
incorporated by reference:
49 C.F.R. § 195.264(b)(1) (Item 1) ─ Respondent failed to install the tank
impoundment drain valve in accordance with Section 22.11.2 of NFPA-30.
Specifically, the drain valve for Tanks 12, 13, 14, and 15 was only operable from
inside the diked area, despite Section 22.11.2 requiring drain valves to be
operable from outside the diked area.
This finding of violation will be considered a prior offense in any subsequent enforcement action
taken against Respondent.
COMPLIANCE ACTIONS
The Director has indicated that Respondent completed the actions proposed in the Notice to
correct the violations. Therefore, it is not necessary to include the proposed compliance terms in
this Final Order.



CPF No. 3-2021-032-NOPV
Page 2
WARNING ITEMS
With respect to Items 2, 3, 4, and 5, the Notice alleged probable violations of 49 C.F.R. §§
195.430(c), 195.452(f)(3), 195.452(i)(1), and 195.589(c), respectively, but did not propose a civil
penalty or compliance order for these items. Therefore, these are considered to be warning
items. If OPS finds a violation of any of these items in a subsequent inspection, Respondent may
be subject to future enforcement action.
The terms and conditions of this order are effective upon service in accordance with 49 C.F.R.
§ 190.5.
June 8, 2021
Alan K. Mayberry Date Issued
Associate Administrator
for Pipeline Safety
- **truncated:** false