# COUNTRYMARK REFINING AND LOGISTICS, LLC — Notice of Probable Violation

- **operation:** document
- **citation:** CPF 32025022NOPV
- **title:** COUNTRYMARK REFINING AND LOGISTICS, LLC — Notice of Probable Violation
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** current
- **official:** true
- **published on:** 2025-07-18
- **effective on:** Not available
- **summary:** OPEN notice of probable violation citing 195.444(c), 195.446(a), 195.446(c)(2), 195.446(c)(3), 195.446(c)(4), 195.446(h).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-32025022nopv.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-32025022nopv.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-32025022nopv
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/32025022NOPV
**body:**

Notice of Probable Violation involving COUNTRYMARK REFINING AND LOGISTICS, LLC. PHMSA's enforcement data identifies the cited regulations as 195.444(c),  195.446(a),  195.446(c)(2),  195.446(c)(3),  195.446(c)(4),  195.446(h). The case was opened on 2025-07-18 and is reported as open. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

32025022NOPV_Final Order_10142025_(24-297198).pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025022NOPV/32025022NOPV_Final%20Order_10142025_(24-297198).pdf

32025022NOPV_Final Order_10142025_(24-297198)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025022NOPV/32025022NOPV_Final%20Order_10142025_(24-297198)_text.pdf

32025022NOPV_Operator Response to Notice_07312025_(24-297198).pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025022NOPV/32025022NOPV_Operator%20Response%20to%20Notice_07312025_(24-297198).pdf

32025022NOPV_PCO_07182025_(24-297198).pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025022NOPV/32025022NOPV_PCO_07182025_(24-297198).pdf

32025022NOPV_PCO_07182025_(24-297198)_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/32025022NOPV/32025022NOPV_PCO_07182025_(24-297198)_text.pdf

32025022NOPV_Final Order_10142025_(24-297198)_text.pdf

October 14, 2025
VIA ELECTRONIC MAIL TO: matt.smorch@countrymark.com
Matt Smorch
President and CEO
CountryMark Refining and Logistics, LLC
225 South East Street, Suite 144
Indianapolis, IN 46202
Re: CPF No. 3-2025-022-NOPV
Dear Mr. Smorch:
Enclosed please find the Final Order issued in the above-referenced case. It makes findings of
violation and specifies actions that need to be taken to comply with the pipeline safety
regulations. When the terms of the compliance order are completed, as determined by the
Director, Central Region, this enforcement action will be closed. Service of the Final Order by
e-mail is effective upon the date of transmission and acknowledgement of receipt as provided
under 49 CFR § 190.5.
Thank you for your cooperation in this matter.
Sincerely,
Linda Daugherty
Acting Associate Administrator
for Pipeline Safety
Enclosures (Final Order and NOPV)
cc: David Barrett, Acting Director, Central Region, Office of Pipeline Safety, PHMSA
Blair Currie, Manager Pipeline Integrity, CountryMark Refining and Logistics, LLC,
blair.currie@countrymark.com
CONFIRMATION OF RECEIPT REQUESTED



U.S. DEPARTMENT OF TRANSPORTATION
PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION
OFFICE OF PIPELINE SAFETY
WASHINGTON, D.C. 20590
____________________________________
In the Matter of )
CountryMark Refining and )
Logistics, LLC, ) CPF No. 3-2025-022-NOPV
)
)
)
Respondent. )
____________________________________)
FINAL ORDER
On July 18, 2025, pursuant to 49 CFR § 190.207, the Acting Director, Central Region, Office of
Pipeline Safety (OPS), issued a Notice of Probable Violation and Proposed Compliance Order
(Notice) to CountryMark Refining and Logistics, LLC (Respondent). The Notice proposed
finding that Respondent had violated the pipeline safety regulations in 49 CFR Part 195. The
Notice also proposed certain measures to correct the violations. Respondent did not contest the
allegations of violation or corrective measures.
Pursuant to 49 CFR § 190.213, I find Respondent violated the pipeline safety regulations listed
below, as more fully described in the enclosed Notice, which is incorporated by reference:
49 CFR § 195.444(c) (Item 1) ─ Respondent failed to comply with API RP 1130
in operating, maintaining, testing, record keeping, and dispatcher training of its
computational pipeline monitoring leak detection system.
49 CFR § 195.446(c)(2) (Item 2) ─ Respondent failed to have and follow written
control room management procedures for conducting a point-to-point verification
between SCADA displays and related field equipment when field equipment is
added or moved and when other changes that affect pipeline safety are made to
field equipment or SCADA displays.
49 CFR § 195.446(c)(3) (Item 3) ─ Respondent failed to have and follow written
control room management procedures to test and verify an internal
communication plan to provide adequate means for safe manual operation of the
pipeline, at least once each calendar year, but at intervals not to exceed 15
months.



49 CFR § 195.446(c)(4) (Item 4) ─ Respondent failed to have and follow written
control room management procedures to test its backup SCADA system at least
once each calendar year, but at intervals not to exceed 15 months.
49 CFR § 195.446(h) (Item 5) ─ Respondent failed to establish a controller
training program that trained each controller to carry out their roles and
responsibilities.
These findings of violation will be considered prior offenses in any subsequent enforcement
action taken against Respondent.
Compliance Actions
Pursuant to 49 U.S.C. § 60118(b) and 49 CFR § 190.217, Respondent is ordered to take the
actions proposed in the enclosed Notice to correct the violations. The Director may grant an
extension of time to comply with any of the required items upon a written request timely
submitted by the Respondent and demonstrating good cause for an extension. Upon completion
of the ordered actions, Respondent may request that the Director close the case. Failure to
comply with this Order may result in the assessment of civil penalties under 49 CFR § 190.223
or in referral to the Attorney General for appropriate relief in a district court of the United States.
The terms and conditions of this order are effective upon service in accordance with 49 CFR
§ 190.5.
___________________________________ __________________________
Linda Daugherty Date Issued
Acting Associate Administrator
for Pipeline Safety



NOTICE OF PROBABLE VIOLATION
and
PROPOSED COMPLIANCE ORDER
VIA ELECTRONIC MAIL TO: matt.smorch@countrymark.com,
blair.curry@countrymark.com
July 18, 2025
Mr. Matt Smorch
President and CEO
CountryMark Refining and Logistics, LLC
225 S. East St, Suite 144
Indianapolis, IN 46202
CPF 3-2025-022-NOPV
Dear Mr. Smorch:
From August 5 through September 24, 2024, a representative of the Pipeline and Hazardous
Materials Safety Administration (PHMSA), Office of Pipeline Safety (OPS), pursuant to Chapter
601 of 49 United States Code (U.S.C.), conducted an inspection of CountryMark Refining and
Logistics, LLC’s (CountryMark) Control Room Management procedures and records in Mt.
Vernon, Indiana.
As a result of the inspection, it is alleged that CountryMark has committed probable violations of
the Pipeline Safety Regulations, Title 49, Code of Federal Regulations (CFR). The items
inspected and the probable violations are:
1. § 195.444 Leak detection.
(a) . . . .
(c) CPM leak detection systems. Each computational pipeline monitoring (CPM)
leak detection system installed on a hazardous liquid pipeline must comply with API
RP 1130 (incorporated by reference, see § 195.3) in operating, maintaining, testing,
record keeping, and dispatcher training of the system.
CountryMark failed to comply with API RP 1130 in operating, maintaining, testing, record
keeping, and dispatcher training of the system as required by § 195.444(c).



During the inspection, PHMSA reviewed CountryMark’s procedures related to its computational
pipeline monitoring (CPM) leak detection system and observed that CountryMark relied on a
third-party vendor for all CPM activities other than control room monitoring. This third-party
vendor conducted off-site monitoring of the CPM system and would also conduct reviews of any
false alarms, data base and algorithm updates. The third-party vendor also offered training, upon
request, for CountryMark’s controllers and control room staff.
The operator relied entirely on the third-party contractor to carry out the requirements outlined in
API RP 1130 as it related to CountryMark’s CPM leak detection system. A review of
CountryMark’s manual demonstrated that there were no operator procedures in place to verify
compliance with API RP 1130’s requirements by the third-party vendor, including the API RP
1130 requirement to conduct an initial test of the CPM system, the requirement to train
controllers in how to use the CPM leak detection system, the requirement to maintain records of
any maintenance or changes to the CPM leak detection system, and the requirements for making
sure the instruments used in gathering data such as pressure or temperature transmitters or
defining the output of the CPM system were set to certain specifications. CRM Plan Section
1.5.1 did not include API RP 1130 as a reference used to develop and implement the CRM Plan.
CountryMark is responsible for making sure that any CPM leak detection program installed on
its pipeline complies with the pipeline safety regulations. A request was made for the initial test
when the CPM leak detection was installed, and no record was provided.1 The operator
indicated no other test of the CPM system had been conducted as required by API RP 1130.
Therefore, CountryMark failed to comply with API RP 1130, as required pursuant to
§ 195.444(c).
2. § 195.446 Control room management.
(a) General. This section applies to each operator of a pipeline facility with
controller working in a control room who monitors and controls all or part of a
pipeline facility through a SCADA system. Each operator must have and follow
written control room management procedures that implement the requirements of
this section. . . .
(b) . . . .
(c) Provide adequate information. Each operator must provide its controllers with
the information, tools, processes and procedures necessary for the controllers to
carry out the roles and responsibilities the operator has defined by performing each
of the following:
(1) . . . .
(2) Conduct a point-to-point verification between SCADA displays and related field
equipment when field equipment is added or moved and when other changes that
affect pipeline safety are made to field equipment or SCADA displays.
1 See API Recommended Practice 1130, “Computational Pipeline Monitoring for Liquids:
Pipeline Segment,” 3rd edition, September 2007, (API RP 1130), at 6.2.2 (“...a new CPM system
should be tested to verity that it has achieved the design or expected performance and to establish
a baseline of performance.”).



CountryMark failed to have and follow procedures and forms for conducting a point-to-point
verification between SCADA displays and related field equipment when field equipment is
added or moved and when other changes that affect pipeline safety are made to field equipment
or SCADA displays that were compliant with § 195.446(c)(2).
PHMSA reviewed CountryMark’s procedures on how to conduct a point-to-point verification
between SCADA displays in the control room and the field for when field equipment is added,
moved, or otherwise changed, by inspecting its Control Room Management (CRM) Plan, Section
4.5 Point-to-Point Verification, and the procedure attached to its Form F-195.446(c)(2). PHMSA
found that CountryMark’s CRM Plan, Section 4.5 Point-to-Point Verification, and the associated
procedure attached to form F-195.446(c)(2) did not support the verification of the point-to-point
test. Additionally, during the PHMSA inspection, PHMSA reviewed CountryMark’s records for
point-to-point verification for RP025-PTB on May 1, 2024, for N450-T502 on November 15,
2023, and for the 2024 Peru Project. CountryMark personnel used form F-195.446(c)(2) Point-
to-Point Verification to document the point-to-point activity. While reviewing the records,
PHMSA observed that a number of details were missing from the documentation. Missing
details in the procedures and records included: the location sequence match between SCADA
and field equipment, whether the test was live or simulated, and verification that all screens
where a point presented were verified and verification that the alarms presented at the correct set
point with the correct priority and description. This information is necessary to conduct a point-
to-point verification between SCADA displays and related field equipment because the point-to-
point verification is the first step in verifying the information presented to the controller is
correct for the live field value, alarming and represents accurately the field device and its
location on the SCADA display.
Therefore, CountryMark was not in compliance with § 195.446(c)(2).
3. § 195.446 Control room management.
(a) General. This section applies to each operator of a pipeline facility with
controller working in a control room who monitors and controls all or part of a
pipeline facility through a SCADA system. Each operator must have and follow
written control room management procedures that implement the requirements of
this section . . .
(b) . . . .
(c) Provide adequate information. Each operator must provide its controllers with
the information, tools, processes and procedures necessary for the controllers to
carry out the roles and responsibilities the operator has defined by performing each
of the following:
(1) . . . .
(3) Test and verify an internal communication plan to provide adequate means for
manual operation of the pipeline safely, at least once each calendar year, but at
intervals not to exceed 15 months;
CountryMark failed to have and follow procedures and forms for testing and verifying an
internal communication plan to provide adequate means for safe manual operation of the



pipeline, at least once each calendar year, but at intervals not to exceed 15 months, that were
compliant with § 195.446(c)(3).
During the PHMSA inspection, PHMSA reviewed CountryMark’s CRM Plan Section 4.6 and its
corresponding form, F-195.446(c)(3). When reviewing CRM Plan Section 4.6, PHMSA
observed that paragraphs 4.6.1 and 4.6.6 did not provide controllers sufficient detail and
direction regarding what was required to manually operate and document the pipeline if
abnormal conditions leading to a catastrophic failure of SCADA or the communication system
occurred. The procedures lacked any instructions on how the pipeline system would be
monitored and documented if CountryMark needed to implement manual operation. There were
instructions on how to shut down the system, but no considerations for how to document shut
down was complete, how leak detection was to continue, or for monitoring and reporting
abnormal operating conditions and emergencies. This information is necessary to test and verify
an internal communication plan for safe manual operation of the pipeline because even though
the pipeline is shut down and not moving product, the pipeline is still operating and several
functions that are monitored and controlled from the control room must continue to ensure
pipeline safety.
PHMSA also reviewed CountryMark’s form F-195.446(c)(3), entitled “Testing of the Internal
Communication Plan,” and used by operator personnel when documenting tests of the Internal
Communications Plan. PHMSA specifically looked at the forms used during the calendar years
2021, 2022, and 2023 and identified that the test of the Internal Communications Plan consisted
of two segments: a test of communication failure and a checklist to verify controller knowledge
of actions to be taken in the event of a lost in communications. PHMSA observed that rather
than actually testing the specified Plan, the exercise evaluated the controller’s knowledge
regarding procedural and operational practices required for the safe manual operation of the
pipeline. This does not constitute testing the plan.
In light of these deficiencies, CountryMark was not in compliance with § 195.446(c)(3).
4. § 195.446 Control room management.
(a) General. This section applies to each operator of a pipeline facility with
controller working in a control room who monitors and controls all or part of a
pipeline facility through a SCADA system. Each operator must have and follow
written control room management procedures that implement the requirements of
this section . . . .
(b) . . . .
(c) Provide adequate information. Each operator must provide its controllers with
the information, tools, processes and procedures necessary for the controllers to
carry out the roles and responsibilities the operator has defined by performing each
of the following:
(1) . . . .
(4) Test any backup SCADA systems at least once each calendar year, but at
intervals not to exceed 15 months; and



CountryMark failed to have and follow procedures to test its backup SCADA server at least once
each calendar year, but at intervals not to exceed 15 months, as required by § 195.446(c)(4).
During the PHMSA inspection, PHMSA observed that while CountryMark did not have a
backup control room, it did have a backup server. Specifically, CountryMark had two servers
that were geographically separate but operated together. CountryMark designed the primary
server to automatically switch to the secondary backup server upon failure. Thus, the secondary
server was a functional backup SCADA system to the primary server. CountryMark did not
view this as a backup SCADA system; therefore, it did not have procedures to test it. PHMSA
learned during its inspection that CountryMark’s IT Group, who managed the maintenance of the
servers, would perform a swap of the servers during periods of maintenance, but this procedure
was completed on an as-needed basis, was informal, and not documented.
Therefore, CountryMark was not in compliance with § 195.446(c)(4).
5. § 195.446 Control room management.
(a) General. This section applies to each operator of a pipeline facility with
controller working in a control room who monitors and controls all or part of a
pipeline facility through a SCADA system. Each operator must have and follow
written control room management procedures that implement the requirements of
this section. . . .
(b) . . . .
(h) Training. Each operator must establish a controller training program and
review the training program content to identify potential improvements at least
once each calendar year, but at intervals not to exceed 15 months. An operator's
program must provide for training each controller to carry out the roles and
responsibilities defined by the operator. In addition, the training program must
include the following elements....
CountryMark failed to establish a controller training program with content to provide training to
each controller on how to carry out the controller’s roles and responsibilities defined by the
operator as required.
PHMSA reviewed CountryMark’s CRM Plan, Section 9.3, which included a list of 26 topics
included in the training. PHMSA also reviewed CountryMark’s CRM Plan, Section 9.3, which
provided a framework for controller training beginning with an initial training that lasted for 90
days and included controller orientation, fatigue training, third-party computer-based training
and operator qualification. This 90-day training, per the CRM Plan, would then be followed by
another 90 days of operational training that would provide the trainee with on-the-job training
supervised by a qualified controller trainer. The CRM Plan stated that the qualified controller
trainer would evaluate the trainee during this period and complete form F-195.446(h)(3), entitled
“90 Day OTJT Check-List,” which was a checklist assessment of the trainee’s familiarity with
various sections of the CRM Plan.
While CountryMark had the above-mentioned CRM Plan, CountryMark did not establish a
controller training program with training program content that could be reviewed to identify
potential improvements. CountryMark did not develop training program content to uniformly



instruct controllers on how to carry out their roles and responsibilities. Rather the training
employed merely consisted of discussions with the trainee about the 26 topics. This process did
not denote what competencies a trainee was required to demonstrate to receive an acceptable
performance rating, or what metrics would be used to evaluate their knowledge or ability to carry
out their assigned roles and responsibilities. Further, absent consistent, uniform training program
content, there was no means by which CountryMark could carry out a substantive review of the
program to identify potential improvements in the training. No uniform content for this training
had been developed. Rather the training merely consisted of discussions with the trainee about
the 26 topics. Therefore, CountryMark was not in compliance with § 195.446(h).
Proposed Civil Penalty
Under 49 U.S.C. § 60122 and 49 CFR § 190.223, you are subject to a civil penalty not to exceed
$272,926 per violation per day the violation persists, up to a maximum of $2,729,245 for a
related series of violations. For violation occurring on or after December 28, 2023 and before
December 30, 2024 the maximum penalty may not exceed $266,015 per violation per day the
violation persists, up to a maximum of $2,660,135 for a related series of violations. For violation
occurring on or after January 6, 2023 and before December 28, 2023 the maximum penalty may
not exceed $257,664 per violation per day the violation persists, up to a maximum of $2,576,627
for a related series of violations. For violation occurring on or after March 21, 2022 and before
January 6, 2023 the maximum penalty may not exceed $239,142 per violation per day the
violation persists, up to a maximum of $2,391,412 for a related series of violations. For violation
occurring on or after May 3, 2021 and before March 21, 2022 the maximum penalty may not
exceed $225,134 per violation per day the violation persists, up to a maximum of $2,251,334 for
a related series of violations. For violation occurring on or after January 11, 2021 and before
May 3, 2021 the maximum penalty may not exceed $222,504 per violation per day the violation
persists, up to a maximum of $2,225,034 for a related series of violations. For violation
occurring on or after July 31, 2019, and before January 11, 2021 the maximum penalty may not
exceed $218,647 per violation per day the violation persists, up to a maximum of $2,186,465 for
a related series of violations.
We have reviewed the circumstances and supporting documents involved in this case, and have
decided not to propose a civil penalty assessment at this time.
Proposed Compliance Order
With respect to items 1, 2, 3, 4, and 5 pursuant to 49 U.S.C. § 60118, the Pipeline and Hazardous
Materials Safety Administration proposes to issue a Compliance Order to CountryMark. Please
refer to the Proposed Compliance Order, which is enclosed and made a part of this Notice.
Response to this Notice
Enclosed as part of this Notice is a document entitled Response Options for Pipeline Operators
in Enforcement Proceedings. Please refer to this document and note the response options. All
material you submit in response to this enforcement action may be made publicly available. If



you believe that any portion of your responsive material qualifies for confidential treatment
under 5 U.S.C. § 552(b), along with the complete original document you must provide a second
copy of the document with the portions you believe qualify for confidential treatment redacted
and an explanation of why you believe the redacted information qualifies for confidential
treatment under 5 U.S.C. § 552(b).
Following your receipt of this Notice, you have 30 days to respond as described in the enclosed
Response Options. If you do not respond within 30 days of receipt of this Notice, this constitutes
a waiver of your right to contest the allegations in this Notice and authorizes the Associate
Administrator for Pipeline Safety to find facts as alleged in this Notice without further notice to
you and to issue a Final Order. If you are responding to this Notice, we propose that you submit
your correspondence to my office within 30 days from receipt of this Notice. The Region
Director may extend the period for responding upon a written request timely submitted
demonstrating good cause for an extension.
In your correspondence on this matter, please refer to CPF 3-2025-022-NOPV and, for each
document you submit, please provide a copy in electronic format whenever possible.
Sincerely,
Dave Barrett
Acting Director, Central Region, Office of Pipeline Safety
Pipeline and Hazardous Materials Safety Administration
cc: Blair Curry, Manager Pipeline Integrity, Blair.Currie@CountryMark.com
Enclosures: Proposed Compliance Order
Response Options for Pipeline Operators in Enforcement Proceedings



PROPOSED COMPLIANCE ORDER
Pursuant to 49 United States Code § 60118, the Pipeline and Hazardous Materials Safety
Administration (PHMSA) proposes to issue to CountryMark a Compliance Order incorporating
the following remedial requirements to ensure the compliance of CountryMark with the pipeline
safety regulations:
A. B. C. In regard to Item 1 of the Notice pertaining to CountryMark’s failure to have a procedure
to comply with API RP 1130 as required by § 195.444 and failing to have conducted an
initial test of the CPM system, CountryMark must develop procedures to comply with the
requirements of API RP 1130 and conduct and document an initial test of the CPM
system.
(1) Within 150 days of receipt of the Final Order, CountryMark must present to the
Region Director the procedures for review and approval.
(2) Within 210 days of receipt of the Final Order, CountryMark must conduct and
document a test of the CPM system, address and correct any findings and action
items, and present to the Region Director for review and approval documentation
showing the test results, action items, and corrections. This test would constitute
the initial test requirement.
In regard to Item 2 of the Notice pertaining to CountryMark’s procedures and point-to-
point verifications being not thorough to demonstrate compliance, CountryMark must
develop procedures and forms to document the verification. The procedure and form(s)
must be presented to the Region Director within 30 days of receipt of the Final Order for
review and approval. CountryMark must also train personnel in the new procedure and
form, conduct a P2P verification for RP025-PTB and for N450-T502 and correct any
identified deficiencies. The records documenting the training, P2P verification, and
corrections must be presented to the Region Director for review 90 days of receipt of the
Final Order.
In regard to Item 3 of the Notice pertaining to CountryMark’s failure to test and verify an
internal communication plan for manual safe operation of the pipeline, CountryMark
must:
(1) Within 90 days of receipt of the Final Order, submit to the Region Director for
review and approval a finalized procedure(s) and communication plan applicable to
all jurisdictional pipelines. The procedure(s) must ensure controllers and
appropriate personnel have adequate information and guidance to perform manual
operations effectively during a SCADA system failure. This submission must
demonstrate compliance with regulatory requirements and ensure the safe and
effective operation of the pipeline system during SCADA system failures, including
a robust internal communication plan that is regularly tested and validated. The
plan must address at least the following elements:
i. Procedures for shutting down the pipeline system, including idling
operations, during a SCADA system failure;



D. E. ii. Processes for monitoring pipeline systems to ensure safety under each flow
condition;
iii. A process for maintaining pipeline system normal operations to allow the
manual delivery and receipt of product;
iv. Methods for conducting manual leak detection and verifying system
integrity.
v. Identification of abnormal operating parameters and corresponding actions.
vi. Emergency response specific to manual operations;
vii. Requirements for recording and documenting information during manual
operation scenarios;
viii. Personnel and shift requirements necessary to sustain manual pipeline
operations; and
ix. Annual testing and verification of the internal communication plan, with
intervals not to exceed 15 months.
`
(2) Within 120 days of receipt of the Final Order:
i. Conduct training for all applicable control room and other operational
personnel involved in manual operation.
(3) Within 180 days of receipt of the Final Order:
i. Schedule a test to verify the internal communication plan provides an adequate
means for manual operation of the pipeline safely; and
ii. Notify the Region Director of the date and details for the test, to allow
PHMSA to schedule an observation inspection.
In regard to Item 4 of the Notice pertaining to CountyMark failing to test its SCADA
backup server, CountryMark must:
(1) Within 30 days of receipt of the Final Order, develop procedures to establish test
requirements for the backup server that includes a form to document elements of the
SCADA operation, and submit to the Region Director for review and approval a
finalized procedure and forms.
(2) Within 90 days of receipt of the Final Order, CountryMark must:
i. Complete a test of the backup SCADA server using the approved procedure
and forms,
ii. iii. Correct any deficiencies identified by the test, and
Submit the test record and any corrective actions to the Regional Director for
review and approval.
In regard to Item 5 of the Notice pertaining to CountryMark failing to establish a
controller training program and review the training program content to identify potential
improvements at least once each calendar year, but at intervals not to exceed 15 months,
CountryMark must:



F. (1) (2) (3) Within 45 days of receipt of the Final Order, develop procedures to include the
roles and responsibilities of the controllers as well as an outline of the controller
training program, and provide them to the Region Director for review and approval.
The training program must include:
i. Stages of training
ii. Periodic assessments, evaluation and feedback for the controller trainee
iii. Requirements for operator qualification that includes knowledge and skill
assessments.
Within 90 days of receipt of the Final Order, present to the Region Director for
review and approval:
i. Training content to be included by each stage of the training program and a
way to verify the controller completed the training. Training content must
include controllers’ roles and responsibilities as well as requirements found
in § 195.446(h)(1-6)
Within 120 days of receipt of the Final Order, present to the Region Director for
review and approval:
i. A procedure to review the content of the training program once each calendar
year as required by § 195.446(h). The procedure must provide the detail of
how the content will be evaluated to ensure it is current and relevant to
support training for the controllers to carry out their roles and responsibilities
in addition to the items identified in § 195.446(h)(1)-(6).
It is requested (not mandated) that CountryMark maintain documentation of the safety
improvement costs associated with fulfilling this Compliance Order and submit the total
to the Director, Central Region, Office of Pipeline Safety, Pipeline and Hazardous
Materials Safety Administration. It is requested that these costs be reported in two
categories: (1) total cost associated with preparation/revision of plans, procedures, studies
and analyses, and (2) total cost associated with replacements, additions and other changes
to pipeline infrastructure.