# TALOS ENERGY, LLC — Notice of Amendment

- **operation:** document
- **citation:** CPF 420195009M
- **title:** TALOS ENERGY, LLC — Notice of Amendment
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2019-03-08
- **effective on:** Not available
- **summary:** CLOSED notice of amendment citing 195.402(a), 195.402(c)(3).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-420195009m.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-420195009m.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-420195009m
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/420195009M
**body:**

Notice of Amendment involving TALOS ENERGY, LLC. PHMSA's enforcement data identifies the cited regulations as 195.402(a),  195.402(c)(3). The case was opened on 2019-03-08 and is reported as closed as of 2020-02-28. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

420195009M_Closure Letter_02282020.pdf: https://primis.phmsa.dot.gov/enforcement-documents/420195009M/420195009M_Closure%20Letter_02282020.pdf

420195009M_Closure Letter_02282020_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/420195009M/420195009M_Closure%20Letter_02282020_text.pdf

420195009M_Notice of Amendment_03082019.pdf: https://primis.phmsa.dot.gov/enforcement-documents/420195009M/420195009M_Notice%20of%20Amendment_03082019.pdf

420195009M_Notice of Amendment_03082019_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/420195009M/420195009M_Notice%20of%20Amendment_03082019_text.pdf

420195009M_Operator Response to Notice_06192019.pdf: https://primis.phmsa.dot.gov/enforcement-documents/420195009M/420195009M_Operator%20Response%20to%20Notice_06192019.pdf

420195009M_Notice of Amendment_03082019_text.pdf

NOTICE OF AMENDMENT
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
March 8, 2019
Melissa Logan
Regulatory Manager
Talos Energy, LLC
500 Dallas Street
Houston, Texas 77002
CPF-4-2019-5009M
Dear Ms. Logan:
From July 31, 2017 to October 19, 2017, representatives of the Pipeline and Hazardous Materials
Safety Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code inspected
Talos Energy, LLC (Talos) procedures for the Main Pass 72A offshore liquid platform.
On the basis of the inspection, PHMSA has identified the apparent inadequacies found within
Talos plans or procedures, as described below:
1. §195.402 Procedural manual for operations, maintenance, and emergencies.
(a) General. Each operator shall prepare and follow for each pipeline system a manual of
written procedures for conducting normal operations and maintenance activities and
handling abnormal operations and emergencies. This manual shall be reviewed at intervals
not exceeding 15 months, but at least once each calendar year, and appropriate changes
made as necessary to ensure that the manual is effective. This manual shall be prepared
before initial operations of a pipeline system commence, and appropriate parts shall be kept
at locations where operations and maintenance activities are conducted
Throughout the Talos Operation & Maintenance Manual the procedures replicate, paraphrase and
reference the regulations. The procedures need to provide specific detail, unique to Talos,
discussing how they will safely complete the process in order to satisfy the requirements of
§195.402(a).



The following procedures in the Talos Operations & Maintenance Manual need to be amended to
include the necessary provisions to comply with the code sections as intended:
1. Section 1 Introduction, parrots the code and lacks the specificity necessary to comply with
2. 3. 4. 5. 6. 7. §195.402(c)(13);
Section 3.2 Startup and Section 3.3 Shutdown, parrots the code and does not discuss starting
up and shutting down a pipeline in enough detail to satisfy §195.402(c)(7);
Section 13 Abnormal Operations, parrots the code, references the previous operator, and
does not discuss the following items in enough detail to satisfy §195.402(d); responding to,
investigating and correcting abnormal operating conditions, follow up monitoring, correcting
variations from normal operation, accurately listing appropriate personnel to notify, and
periodically reviewing the response of operator personnel to determine the effectiveness of
responding to abnormal operations;
Section 14.1 Safety Related Condition, parrots the code and lacks the specificity necessary
to comply with §195.402(f);
Section 16 Welder Qualifications, parrots the code and does not discuss the following items
in enough detail to satisfy §195.214, §195.222(a), §195.226(a), and §195.234(c); using a
qualified welding procedure, qualifying tests, qualifying welders, arc burns and ground wires,
and non-destructive testing of welding;
Section 18 Damage Prevention, incorrectly labels the Facility Supervisor position and lacks
the specificity necessary to comply with §195.402(c)(12); and
Section 19 Emergency Response Plans, parrots the code and does not discuss the following
items in enough detail to satisfy §195.402(c)(5), §195.402(e), §195.403(a), §195.403(b);
receiving, identifying and classifying Notices of Events, response guidelines, emergency
shutdown or pressure reduction, controlling spills to minimize possible ignition, minimizing
public exposure to injury, characteristics and hazards of hazardous liquids transported,
conditions that are likely to cause emergencies, steps necessary to control a release of
hazardous liquid, types, sizes and consequences of fire and appropriate response, review of
emergency response personnel performance, and training of supervisors on emergency
response procedures.
Talos must amend its processes and procedures to adequately describe the requirements for the
procedures listed above and to ensure compliance with §195.402(a).
2. §195.402 Procedural manual for operations, maintenance, and emergencies.
(c) Maintenance and normal operations. The manual required by paragraph (a) of this
section must include procedures for the following to provide safety during maintenance and
normal operations:
(3) Operating, maintaining, and repairing the pipeline system in accordance with each of
the requirements of this subpart and subpart H of this part.
Throughout the Talos Operation & Maintenance Manual the procedures replicate, paraphrase and
reference the regulations. The procedures need to provide specific detail, unique to Talos,
discussing how they will safely complete the process in order to satisfy the requirements of
§195.402(c)(3)
2



The following procedures in the Talos Operations & Maintenance Manual need to be amended to
include the necessary provisions to comply with the code sections as intended:
1. 2. 3. 4. 5. 6. Section 4.4 Record Retention, parrots the code and does not discuss maintaining pump station
operating records and the retention of maps and records of cathodic systems in sufficient detail
to satisfy §195.404(b) and §195.589(a);
Section 8.1 Scraper & Sphere Facilities, parrots the code and fails to discuss safety devices
on scraper and sphere facilities in sufficient detail to satisfy §195.426;
Section 9.1 Maximum Operating Pressure, does not discuss the establishment of Maximum
Operating Pressure in sufficient detail to satisfy §195.406(a);
Section 10 Corrosion Control, parrots the code and does not discuss the following items in
enough detail to satisfy §195.561, §195.571, §195.573, §195.575(a), §195.577(a), §195.579,
§195.581(a) §195.583(a), §195.585(a) and §195.587; repair of exposed pipe, corrosion
monitoring criteria, where and how corrosion testing is done, correction of identified corrosion
deficiencies, electrical isolation of submerged pipelines, testing for and responding to stray
currents, investigating and remediating internal corrosion, corrosion inhibitor testing,
examining removed pipe, inspecting aboveground pipelines for atmospheric corrosion,
repairing and replacing externally corroded pipe, and evaluating remaining strength of
internally and externally corroded pipe;
Section 11.1 Valve Inspections and Section 11.2 Valve Inspection Procedure, parrots the
code and fails to discuss valve maintenance in sufficient detail to satisfy §195.420(a); and
Section 17.1 Testing Requirements, parrots the code and fails to discuss pressure testing in
enough detail to satisfy §195.302(b).
Talos must amend its process and procedures to adequately describe the requirements for the
procedures listed above and to ensure compliance with §195.402(c)(3).
Response to this Notice
This Notice is provided pursuant to 49 U.S.C. § 60108(a) and 49 C.F.R. § 190.206. Enclosed as
part of this Notice is a document entitled Response Options for Pipeline Operators in Compliance
Proceedings. Please refer to this document and note the response options. Be advised that all
material you submit in response to this enforcement action is subject to being made publicly
available. If you believe that any portion of your responsive material qualifies for confidential
treatment under 5 U.S.C. 552(b), along with the complete original document you must provide a
second copy of the document with the portions you believe qualify for confidential treatment
redacted and an explanation of why you believe the redacted information qualifies for confidential
treatment under 5 U.S.C. 552(b).
3



Following the receipt of this Notice, you have 30 days to submit written comments, revised
procedures, or a request for a hearing under §190.211. If you do not respond within 30 days of
receipt of this Notice, this constitutes a waiver of your right to contest the allegations in this Notice
and authorizes the Associate Administrator for Pipeline Safety to find facts as alleged in this Notice
without further notice to you and to issue an Order Directing Amendment. If your plans or
procedures are found inadequate as alleged in this Notice, you may be ordered to amend your plans
or procedures to correct the inadequacies (49 C.F.R. § 190.206). If you are not contesting this
Notice, we propose that you submit your amended procedures to my office within 90 days of
receipt of this Notice. This period may be extended by written request for good cause. Once the
inadequacies identified herein have been addressed in your amended procedures, this enforcement
action will be closed.
It is requested (not mandated) that Talos Energy, LLC maintain documentation of the safety
improvement costs associated with fulfilling this Notice of Amendment (preparation/revision of
plans, procedures) and submit the total to Mary McDaniel, Director, Southwest Region, Pipeline
and Hazardous Materials Safety Administration. In correspondence concerning this matter, please
refer to CPF-4-2019-5009M and, for each document you submit, please provide a copy in
electronic format whenever possible.
Sincerely,
Mary L. McDaniel, P.E.
Director, Southwest Region
Pipeline and Hazardous Materials Safety Administration
Enclosure: Response Options for Pipeline Operators in Compliance Proceedings
4

420195009M_Closure Letter_02282020_text.pdf

CERTIFIED MAIL - RETURN RECEIPT REQUESTED
February 28, 2020
Melissa Logan
Regulatory Manager
Talos Energy, LLC
500 Dallas Street
Houston, Texas 77002
CPF 4-2019-5009M
Dear Ms. Logan:
From July 31, 2017 through October 16, 2017, a representative from the Pipeline and Hazardous
Materials Safety Administration (PHMSA), pursuant to Chapter 601 of 49 United States Code,
conducted an on-site pipeline safety inspection of Talos Energy, LLC (Talos) procedures in
Houston, Texas. As a result of the inspection, Talos was issued a Notice of Amendment on July
24, 2018, which proposed amendment of your procedures.
Talos submitted its amended procedures on August 24, 2018 and January 7, 2019. My staff
reviewed the amended procedures, and it appears that the inadequacies outlined in this Notice of
Amendment have been corrected.
This letter is to inform you no further action is necessary and this case is now closed. Thank you
for your cooperation.
Sincerely,
Mary L. McDaniel, P.E.
Director, Southwest Region
Office of Pipeline Safety