# MIDWAY SUNSET COGENERATION CO — Notice of Amendment

- **operation:** document
- **citation:** CPF 520090025M
- **title:** MIDWAY SUNSET COGENERATION CO — Notice of Amendment
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2009-11-09
- **effective on:** Not available
- **summary:** CLOSED notice of amendment citing 192.805(b), 192.805(c), 192.805(i).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-520090025m.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-520090025m.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-520090025m
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/520090025M
**body:**

Notice of Amendment involving MIDWAY SUNSET COGENERATION CO. PHMSA's enforcement data identifies the cited regulations as 192.805(b),  192.805(c),  192.805(i). The case was opened on 2009-11-09 and is reported as closed as of 2010-01-12. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

520090025M_notice of amendment_11092009.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520090025M/520090025M_notice%20of%20amendment_11092009.pdf

520090025M_notice of amendment_11092009_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520090025M/520090025M_notice%20of%20amendment_11092009_text.pdf

520090025M_operator_response_12012009.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520090025M/520090025M_operator_response_12012009.pdf

520090025M_notice of amendment_11092009_text.pdf

NOTICE OF AMENDMENT
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
November 9, 2009
Mr. Greg Jans
Plant Manager
Midway Sunset Cogeneration Company
3466 West Crocker Spring Road
Fellows, CA 93224-0457
CPF 5-2009-0025M
Dear Mr. Jans:
On June 1-3, 2009, a representative of the Pipeline and Hazardous Materials Safety
Administration (PHMSA), pursuant to Chapter 601 of 49 United States Code, inspected
Midway Sunset Cogeneration Company’s (MSCC) Operator Qualification (OQ) program in
Fellows, California.
As a result of the inspection, it appears that you have committed probable violations of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations. The items inspected and
the probable violations are:



1. §192.805 Qualification program
Each operator shall have and follow a written qualification program. The
program shall include provisions to:
(b) Ensure through evaluation that individuals performing covered tasks are
qualified.
MSCC requires its contractors to submit proof of qualification with the MSCC OQ
plan before performing any OQ-covered tasks. However, MSCC’s OQ plan does not
require sub-contractors to do the same. MSCC needs to expand the OQ provision for
outside contractors performing covered tasks on its behalf to include sub-contractors
as well.
2. §192.805 Qualification program
Each operator shall have and follow a written qualification program. The
program shall include provisions to:
(c) Allow individuals that are not qualified pursuant to this subpart to perform
a covered task if directed and observed by an individual that is qualified.
2a. MSCC’s OQ program needs to be modified so that a non-qualified individual
performing an OQ-covered task is both directed and observed rather than just
observed.
2b. There are certain critical OQ-covered tasks such as hot tapping, stoppling, and
welding that need to be performed by a qualified individual only. MSCC’s OQ
manual needs to be revised so that only qualified individuals from perform critical
OQ covered tasks.
3. §192.805 Qualification program
Each operator shall have and follow a written qualification program. The
program shall include provisions to:
(i) After December 16, 2004, notify the Administrator or a state agency
participating under 49 U.S.C. Chapter 601 if the operator significantly modifies
the program after the Administrator or state agency has verified that it
complies with this section.
MSCC has no provision in its OQ program to notify PHMSA or the appropriate
regulatory agency of significant modifications that are made to its OQ program.
2



Response to this Notice
This Notice is provided pursuant to 49 U.S.C. § 60108(a) and 49 C.F.R. § 190.237.
Enclosed as part of this Notice is a document entitled Response Options for Pipeline
Operators in Compliance Proceedings. Please refer to this document and note the response
options. Be advised that all material you submit in response to this enforcement action is
subject to being made publicly available. If you believe that any portion of your responsive
material qualifies for confidential treatment under 5 U.S.C. 552(b), along with the complete
original document you must provide a second copy of the document with the portions you
believe qualify for confidential treatment redacted and an explanation of why you believe
the redacted information qualifies for confidential treatment under 5 U.S.C. 552(b). If you
do not respond within 30 days of receipt of this Notice, this constitutes a waiver of your
right to contest the allegations in this Notice and authorizes the Associate Administrator for
Pipeline Safety to find facts as alleged in this Notice without further notice to you and to
issue a Final Order.
If, after opportunity for a hearing, your plans or procedures are found inadequate as alleged
in this Notice, you may be ordered to amend your plans or procedures to correct the
inadequacies (49 C.F.R. § 190.237). If you are not contesting this Notice, we propose that
you submit your amended procedures to my office within 30 days of receipt of this Notice.
This period may be extended by written request for good cause. Once the inadequacies
identified herein have been addressed in your amended procedures, this enforcement action
will be closed.
In correspondence concerning this matter, please refer to CPF 5-2009-0025M and, for each
document you submit, please provide a copy in electronic format whenever possible.
Sincerely,
Chris Hoidal
Director, Western Region
Pipeline and Hazardous Materials Safety Administration
Enclosures: Response Options for Pipeline Operators in Compliance Proceeding
cc: PHP-60 Compliance Registry
PHP-500 H. Monfared (#125306)