# GAS TRANSMISSION NORTHWEST LLC — Warning Letter

- **operation:** document
- **citation:** CPF 520121004W
- **title:** GAS TRANSMISSION NORTHWEST LLC — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2012-02-21
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.173.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-520121004w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-520121004w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-520121004w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/520121004W
**body:**

Warning Letter involving GAS TRANSMISSION NORTHWEST LLC. PHMSA's enforcement data identifies the cited regulation as 192.173. The case was opened on 2012-02-21 and is reported as closed as of 2013-08-16. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

520121004W_Operator Response_08142012.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520121004W/520121004W_Operator%20Response_08142012.pdf

520121004W_warning letter_02212012.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520121004W/520121004W_warning%20letter_02212012.pdf

520121004W_warning letter_02212012_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520121004W/520121004W_warning%20letter_02212012_text.pdf

520121004W_withdrawal of notice letter_08162013.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520121004W/520121004W_withdrawal%20of%20notice%20letter_08162013.pdf

520121004W_withdrawal of notice letter_08162013_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520121004W/520121004W_withdrawal%20of%20notice%20letter_08162013_text.pdf

520121004W_warning letter_02212012_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
February 21, 2012
Mr. Vern Meier
VP, US Pipelines, Field Operations
TransCanada Corporation
717 Texas Avenue
Houston, TX 77002
CPF 5-2012-1004W
Dear Mr. Meier:
On October 17 to 21, 2011 a representative of the Pipeline and Hazardous Materials Safety
Administration (PHMSA) pursuant to Chapter 601 of 49 United States Code inspected your Gas
Transmission Northwest Corporation facilities in Redmond, Oregon.
As a result of the inspection, it appears that you have committed a probable violation of the
Pipeline Safety Regulations, Title 49, Code of Federal Regulations. The item inspected and the
probable violation is:
1. §192.173 Compressor stations: Ventilation.
Each compressor station building must be ventilated to ensure that employees are
not endangered by the accumulation of gas in rooms, sumps, attics, pits, or other
enclosed places.
At the time of the inspection the dry gas seal vents did not extend above the roof lines at
Compressor Stations #11 and #14. The vents need to be extended above the roof line to preclude
possible gas accumulations in the compressor stations.



Under 49 United States Code, § 60122, you are subject to a civil penalty not to exceed $100,000
for each violation for each day the violation persists up to a maximum of $1,000,000 for any
related series of violations. We have reviewed the circumstances and supporting documents
involved in this case, and have decided not to conduct additional enforcement action or penalty
assessment proceedings at this time. We advise you to correct the item(s) identified in this letter.
Failure to do so will result in TransCanada / Gas Transmission Northwest Corporation being
subject to additional enforcement action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer to
CPF 5-2012-1004W. Be advised that all material you submit in response to this enforcement
action is subject to being made publicly available. If you believe that any portion of your
responsive material qualifies for confidential treatment under 5 U.S.C. 552(b), along with the
complete original document you must provide a second copy of the document with the portions
you believe qualify for confidential treatment redacted and an explanation of why you believe
the redacted information qualifies for confidential treatment under 5 U.S.C. 552(b).
Sincerely,
Chris Hoidal
Director, Western Region
Pipeline and Hazardous Materials Safety Administration
cc: PHP-60 Compliance Registry
PHP-500 J. Haddow (#132926)
2

520121004W_withdrawal of notice letter_08162013_text.pdf

WITHDRAWAL of NOTICE LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
August 16, 2013
Mr. Vern Meier
Vice President, US Pipelines, Field Operations
TransCanada Corporation
717 Texas Avenue
Houston, TX 77002
CPF 5-2012-1004W
Dear Mr. Meier:
On February 21, 2012 TransCanada Corporation was issued a Warning Letter for the case
number referenced above. This Warning Letter cited TransCanada Corporation for not providing
ventilation in accordance with 49 CFR, Part 192.173. At the time of the inspection the dry gas
seal vents did not extend above the roof lines at Compressor Stations #11 and #14. PHMSA
believed that the vents needed to be extended above the roof line to preclude possible gas
accumulations in the compressor stations.
However, in your letter dated August 14, 2012, TransCanada provided information regarding the
exhaust system noting that gas detectors are present. These detectors shut down the compressors
if a level of 25% LEL is exceeded and the fact that the vents from the building are powered by
fans with intakes below lower than the vent exhaust, TransCanada contends this system complies
with §192.173.



This letter is to inform you that PHMSA hereby withdraws the Warning Letter and that the case
is now closed.
Sincerely,
Chris Hoidal
Director, Western Region
Pipeline and Hazardous Materials Safety Administration
cc: PHP-60 Compliance Registry
PHP-500 J. Haddow