# EL PASO NATURAL GAS CO — Warning Letter

- **operation:** document
- **citation:** CPF 520191002W
- **title:** EL PASO NATURAL GAS CO — Warning Letter
- **source type:** enforcement
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** historical
- **official:** true
- **published on:** 2019-01-17
- **effective on:** Not available
- **summary:** CLOSED warning letter citing 192.479(a), 192.481(a), 192.605(a), 192.615(c)(1), 192.705(b), 192.709(c), 192.736(c).
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-enforcement-520191002w.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-enforcement-520191002w.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-enforcement-520191002w
- **source url:** https://primis.phmsa.dot.gov/enforcement-data/case/520191002W
**body:**

Warning Letter involving EL PASO NATURAL GAS CO. PHMSA's enforcement data identifies the cited regulations as 192.479(a),  192.481(a),  192.605(a),  192.615(c)(1),  192.705(b),  192.709(c),  192.736(c). The case was opened on 2019-01-17 and is reported as closed as of 2019-01-17. Open the official case record for notices, responses, orders, and the latest status.

Official case documents:

520191002W_Operator Response to Notice_04172019.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520191002W/520191002W_Operator%20Response%20to%20Notice_04172019.pdf

520191002W_Warning Letter_01172019.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520191002W/520191002W_Warning%20Letter_01172019.pdf

520191002W_Warning Letter_01172019_text.pdf: https://primis.phmsa.dot.gov/enforcement-documents/520191002W/520191002W_Warning%20Letter_01172019_text.pdf

520191002W_Warning Letter_01172019_text.pdf

WARNING LETTER
CERTIFIED MAIL - RETURN RECEIPT REQUESTED
January 17, 2019
Mr. Tom Martin
President, Natural Gas Pipelines
Kinder Morgan
1001 Louisiana Street, Suite 1000
Houston, TX 77002-5089
CPF 5-2019-1002W
Dear Mr. Martin:
During the weeks of April 17 through 24, April 24 through 28, June 5 through 9, and June 12
through 16, 2017, representatives of the Pipeline and Hazardous Materials Safety Administration
(PHMSA), pursuant to Chapter 601 of 49 United States Code (U.S.C.), inspected your El Paso
Natural Gas Pipeline, Deming East Complex Facilities, located in New Mexico and Texas.
Based on our inspection findings, PHMSA determined that you have committed probable
violations of the Pipeline Safety Regulations, Title 49, Code of Federal Regulations (CFR), Part
192. The deficiencies noted and the probable violations are:



1. §192.605 Procedural manual for operations, maintenance, and emergencies.
(a) General. Each operator shall prepare and follow for each pipeline, a manual of
written procedures and conducting operations and maintenance activities and for
emergency response. For transmission lines, the manual must also include
procedures for handling abnormal operations. This manual must be reviewed and
updated by the operator at intervals not exceeding 15 months, but at least once each
calendar year. This manual must be prepared before operations of pipeline system
commence. Appropriate parts of the manual must be kept at locations where
operations and maintenance activities are conducted.
Kinder Morgan was unable to provide documentation that a review or update of the emergency
manual occurred in calendar years 2014 and 2015, for the Deming East Complex.
2. §192.615 Emergency Plans.
(c) Each operator shall establish and maintain liaison with appropriate fire, police,
and other public officials to:
(1) Learn the responsibility and resources of each government organization that
may respond to a gas pipeline emergency;
While reviewing records for calendar years 2014 through 2016 for the City of Deming and Luna
County, it was determined that the operator failed to establish and maintain liaisons with public
officials. Only records demonstrating liaison with emergency responders were provided during
the inspection.
3. §192.736 Compressor stations: Gas detection.
(c) Each gas detection and alarm system required by this section must be
maintained to function properly. The maintenance must include performance tests.
Kinder Morgan (KM) personnel did not adequately inspect their gas detection and alarm system
at one of their compressor stations to ensure that they are being maintained to function properly.
Kinder Morgan specified an inspecting and testing interval for these systems in their Operations
and Maintenance (O&M) manual as required by 192.605(a). KM maintenance records indicate
that they have not followed their procedure in accordance with their O&M Manual, specifically
the mandated testing activities for their gas detection system.
Kinder Morgan's Procedure 550, Testing of Gas and Fire Detection Systems, requires that
interval testing of the gas detection system be conducted at least four (4) times each calendar
year, not to exceed 4.5 months. Prior to 2014, the gas detection frequency was established to be
conducted annually.
A review of the gas detection testing records indicated that Kinder Morgan personnel did not
conduct the performance tests at the revised frequency, as established by Procedure 550.
Examples of non-compliance were found at the following locations:
2



• Lordsburg Compressor Station: Plant A - 6 gas detectors, Plant B - 3 gas detectors, Plant
C - 3 gas detectors.
Calendar Year 2014: Only one inspection occurred during this year, on 7/17/2014.
Calendar Year 2015: Plant C - Records failed to demonstrate that all three gas detectors
were inspected during each quarter (March/June/September/December).
Calendar Year 2016: Plant C - Records failed to demonstrate that all three gas detectors
were inspected during each quarter (April/July/September/December).
4. §192.709 Transmission lines: Record keeping.
Each operator shall maintain the following records for transmission lines for the
periods specified:
(c) A record of each patrol, survey, inspection, and test required by subparts Land
M of this part must be retained for at least 5 years or until the next patrol, survey,
inspection, or test is completed, whichever is longer.
Kinder Morgan was unable to provide records that demonstrated compliance for continuing
surveillance in calendar year 2014, in accordance with their procedure O&M Manual, Procedure
#218- Continuing Surveillance, and §192.613(a).
5. §192.605 Procedural manual for operations, maintenance, and emergencies.
(a) General. Each operator shall prepare and follow for each pipeline, a manual of
written procedures and conducting operations and maintenance activities and for
emergency response. For transmission lines, the manual must also include
procedures for handling abnormal operations. This manual must be reviewed and
updated by the operator at intervals not exceeding 15 months, but at least once each
calendar year. This manual must be prepared before operations of pipeline system
commence. Appropriate parts of the manual must be kept at locations where
operations and maintenance activities are conducted.
Kinder Morgan's annual review and update of their procedural manual appears inadequate. The
procedural manual is required by 192.605(e) to include procedures that address Continuing
Surveillance, as prescribed in 192.613(a). Kinder Morgan records provided during the inspection
could not substantiate that all activities in Procedure #218 for Continuing Surveillance were
included in the annual review for calendar years 2015 and 2016.
6. §192.705 Transmission lines: Patrolling.
(b) The frequency of patrols is determined by the size of the line, the operating
pressures, the class location, terrain, weather, and other relevant factors, but
intervals between patrols may not be longer than prescribed in the following table:
3



Maximum interval between patrols
Class
location
ofline
1, 2 At highway and railroad
crossings 7½ mop.ths; but at least twice
each calendar year
At all other places
15 months; but at least once
each calendar year.
3 4½ months; but at least four
times each calendar year
7½ months; but at least twice
each calendar year.
4 4½ months; but at least four
times each calendar year
4½ months; but at least four
times each calendar year.
Patrolling records for 2013 did not demonstrate that Kinder Morgan patrolled Line 1005 (East
Zone District Division Line - Florida Station to Gage Station) twice in the calendar year. Only
one patrol occurred on July 22, 2013.
7. §192.479 Atmospheric corrosion control: General
(a) Each operator must clean and coat each pipeline or portion of pipeline that is
exposed to the atmosphere, except pipelines under paragraph (c) of this section.
Kinder Morgan did not clean and coat pipelines or portions of pipelines that were exposed to the
atmosphere at the following location:
• Line 1005 (Old Station #4) had no coating on aboveground piping.
8. §192.481 Atmospheric corrosion control: Monitoring
(a) Each operator must inspect each pipeline or portion of pipeline that is exposed to
the atmosphere for evidence of atmospheric corrosion, as follows:
If the pipeline is
located: Then the frequency of inspection is:
Onshore At least once every 3 calendar years, but with
intervals not exceeding 39 months
Offshore At least once each calendar year, but with intervals
not exceeding 15 months
4



Kinder Morgan was not conducting atmospheric inspections that could adequately assess the
level of atmospheric corrosion. During the field inspection of Block Valve #41 ¼ on Line 1600,
the valve was observed to be housed in a below grade pit type structure. The valve was exposed
to the atmosphere within the pit area. When asked about performing atmospheric corrosion
inspections on the entire exposed area (360°), field staff stated they do not go into the pit to
check for evidence of corrosion, they only observe from above.
Kinder Morgan was not performing adequate atmospheric corrosion inspection on each pipeline
or portion of pipeline that is exposed to the atmosphere. The inspection must be conducted so
any evidence of atmospheric corrosion can be evaluated.
Under 49 U.S.C. § 60122 and 49 CFR § 190.223, you are subject to a civil penalty not to exceed
$209,002 per violation per day the violation persists, up to a maximum of $2,090,022 for a
related series of violations. For violations occurring prior to November 2, 2015, the maximum
penalty may not exceed $200,000 per violation per day, with a maximum penalty not to exceed
$2,000,000 for a related series of violations. We have reviewed the circumstances and supporting
documents involved in this case, and have decided not to conduct additional enforcement action
or penalty assessment proceedings at this time. We advise you to correct the item(s) identified in
this letter. Failure to do so will result in Kinder Morgan being subject to additional enforcement
action.
No reply to this letter is required. If you choose to reply, in your correspondence please refer to
CPF 5-2019-1002W. Be advised that all material you submit in response to this enforcement
action is subject to being made publicly available. If you believe that any portion of your
responsive material qualifies for confidential treatment under 5 U.S.C. 552(b), along with the
complete original document you must provide a second copy of the document with the portions
you believe qualify for confidential treatment redacted and an explanation of why you believe
the redacted information qualifies for confidential treatment under 5 U.S.C. 552(b).
Sincerely
Chris Hoidal
Acting Director, Western Region
Pipeline and Hazardous Materials Safety Administration
cc: PHP-60 Compliance Registry
PHP-500 D.Fehling (#155199)
5