{"operation":"document","citation":"PHMSA Report 20250046","title":"ENERGY TRANSFER COMPANY — Hazardous liquid gravity and reporting-regulated-only — incident on 2025-04-21","source_type":"incident","agency":"Pipeline and Hazardous Materials Safety Administration","status":"historical","official":true,"published_on":"2025-05-20","effective_on":"2025-04-21","summary":"Hazardous liquid gravity and reporting-regulated-only incident in NOT WITHIN A MUNICIPALITY, GLASSCOCK County, TX. Reported cause: EQUIPMENT FAILURE. Reported consequences: 0 fatalities, 0 injuries, 25 CRUDE OIL released, $8,000 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.","machine_formats":{"json":"https://regulus.evalyn.ai/document/phmsa-incident-1cc422aedffd6f3b2273c8a7.json","markdown":"https://regulus.evalyn.ai/document/phmsa-incident-1cc422aedffd6f3b2273c8a7.md"},"app_url":"https://regulus.evalyn.ai/document/phmsa-incident-1cc422aedffd6f3b2273c8a7","source_url":"https://data.transportation.gov/api/views/27nc-rsge/files/28f0a80f-a155-4294-8d1e-1d46f1237896?download=true&filename=Hazardous%20Liquid%20Gravity%20%26%20Reporting-Regulated-Only%20Jul%202020_present.zip","body":"Hazardous liquid gravity and reporting-regulated-only incident in NOT WITHIN A MUNICIPALITY, GLASSCOCK County, TX. Reported cause: EQUIPMENT FAILURE. Reported consequences: 0 fatalities, 0 injuries, 25 CRUDE OIL released, $8,000 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.\n\nReport number: 20250046.\n\nOperator ID: 32099.\n\nReported incident date: 4/21/2025 5:44.\n\nCause detail: PUMP OR PUMP-RELATED EQUIPMENT\n\nCause detail: ON 04/21/25 AT APPROXIMATELY 05:44, LOCAL ET EMPLOYEE NOTIFIED THE CONTROL CENTER THAT THE LACT SEAL HAD FAILED AND PRODUCT WAS ON THE PUMP PAD. THE CONTROLLER IMMEDIATELY PULLED PERMISSIVE ON 2365 - END WTH 20-8 6INCH GATHERING LINE (INTRASTATE - TAC 8.110(A)(3)). IT WAS DETERMINED THAT THE BEARING ON THE LACT PUMP FAILED CAUSING THE PUMP TO HEAT TO A DEGREE THAT CAUSED THE MECHANICAL SEAL TO FAIL AND CAUSED PRODUCT TO BE RELEASED. APPROXIMATELY 25 BARRELS OF CRUDE OIL WAS RELEASED. CLEAN-UP CONTRACTORS RECOVERED PRODUCT AND REMOVED CONTAMINATED SOIL. THE LEAK WAS REPAIRED BY REPLACING THE SEAL. THE ACCIDENT IS STILL UNDER INVESTIGATION. A SUPPLEMENTAL REPORT WILL BE SUBMITTED ONCE THE ROOT CAUSE FAILURE ANALYSIS IS COMPLETED. SUPPLEMENTAL & FINAL: THE CAUSE OF THE ACCIDENT WAS DUE TO A PUMP-RELATED EQUIPMENT FAILURE. NORMAL WEAR OF THE PUMP BEARINGS CAUSED PUMP TO OVERHEAT LEADING THE SEAL TO FAIL, WHICH ALLOWED PRODUCT TO BE RELEASED. TO PREVENT REOCCURRENCE, A PREVENTIVE MAINTENANCE SCHEDULE FOR THIS PUMP WILL BE ESTABLISHED, AND PROVIDE TRAINING TO PERSONNEL ON PROPER LUBE OIL LEVEL VERIFICATION.","truncated":false,"body_characters":1692}