{"operation":"document","citation":"PHMSA Report 20220030","title":"ENERGY TRANSFER COMPANY — Hazardous liquid gravity and reporting-regulated-only — incident on 2022-03-29","source_type":"incident","agency":"Pipeline and Hazardous Materials Safety Administration","status":"historical","official":true,"published_on":"2022-04-28","effective_on":"2022-03-29","summary":"Hazardous liquid gravity and reporting-regulated-only incident in TARZAN, MARTIN County, TX. Reported cause: EQUIPMENT FAILURE. Reported consequences: 0 fatalities, 0 injuries, 10 CRUDE OIL released, $1,000 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.","machine_formats":{"json":"https://regulus.evalyn.ai/document/phmsa-incident-3521ea99de6f98d249b11547.json","markdown":"https://regulus.evalyn.ai/document/phmsa-incident-3521ea99de6f98d249b11547.md"},"app_url":"https://regulus.evalyn.ai/document/phmsa-incident-3521ea99de6f98d249b11547","source_url":"https://data.transportation.gov/api/views/27nc-rsge/files/28f0a80f-a155-4294-8d1e-1d46f1237896?download=true&filename=Hazardous%20Liquid%20Gravity%20%26%20Reporting-Regulated-Only%20Jul%202020_present.zip","body":"Hazardous liquid gravity and reporting-regulated-only incident in TARZAN, MARTIN County, TX. Reported cause: EQUIPMENT FAILURE. Reported consequences: 0 fatalities, 0 injuries, 10 CRUDE OIL released, $1,000 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.\n\nReport number: 20220030.\n\nOperator ID: 32099.\n\nReported incident date: 3/29/2022 7:30.\n\nCause detail: NON-THREADED CONNECTION FAILURE\n\nCause detail: AT APPROXIMATELY 7:03AM ON MARCH 29TH 2022, AN ENERGY TRANSFER EMPLOYEE OBSERVED CRUDE OIL ESCAPING FROM STAINLESS STEEL TUBING ASSOCIATED WITH AN INJECTION PUMP. THE EMPLOYEE IMMEDIATELY CONTACTED THE CONTROL CENTER AND HAD THE PUMP SHUTDOWN. UPON INVESTIGATION THE STAINLESS-STEEL TUBING HAD BROKEN AT THE CONNECTION FITTING DUE TO VIBRATION FROM THE INJECTION PUMP. CLEAN UP CREW WAS DISPATCHED TO COLLECT ALL FREE PRODUCT AND CONTAMINATED SOIL. LOCAL MECHANICS WERE CALLED OUT AND THE TUBING WAS REPLACED THE SAME DAY. TO PREVENT RECURRENCE, THE TUBING WAS REPLACED WITH A FLEXIBLE STAINLESS TYPE TUBING TO ABSORB ANY EXCESSIVE VIBRATION.","truncated":false,"body_characters":1195}