{"operation":"document","citation":"PHMSA Report 20150250","title":"ENTERPRISE PRODUCTS OPERATING LLC — Hazardous liquid — incident on 2013-08-16","source_type":"incident","agency":"Pipeline and Hazardous Materials Safety Administration","status":"historical","official":true,"published_on":"2015-07-13","effective_on":"2013-08-16","summary":"Hazardous liquid incident in NEEDVILLE, FORT BEND County, TX. Reported cause: INCORRECT OPERATION. Reported consequences: 0 fatalities, 0 injuries, 0 HVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBIENT CONDITIONS released, $0 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings. PHMSA trend classification: significant incident, not serious.","machine_formats":{"json":"https://regulus.evalyn.ai/document/phmsa-incident-827518e43eb6a55366f0c78b.json","markdown":"https://regulus.evalyn.ai/document/phmsa-incident-827518e43eb6a55366f0c78b.md"},"app_url":"https://regulus.evalyn.ai/document/phmsa-incident-827518e43eb6a55366f0c78b","source_url":"https://data.transportation.gov/api/views/27nc-rsge/files/1d547e17-2be1-4a32-9958-a1d5a946ade9?download=true&filename=Hazardous%20Liquid%20Accident%20Data%20-%20January%202010%20to%20present.zip","body":"Hazardous liquid incident in NEEDVILLE, FORT BEND County, TX. Reported cause: INCORRECT OPERATION. Reported consequences: 0 fatalities, 0 injuries, 0 HVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBIENT CONDITIONS released, $0 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.\n\nReport number: 20150250.\n\nOperator ID: 31618.\n\nReported incident date: 8/16/2013 4:55.\n\nLocation detail: NEEDVILLE\n\nCause detail: OTHER INCORRECT OPERATION\n\nCause detail: IN REFERENCE TO PARTS A(6), F,AND I, THIS REPORT IS BEING MADE AS PART OF A COMPREHENSIVE REVIEW AND ANALYSIS OF PRIOR INCIDENTS OR NEAR MISSES INVOLVING FLASH FIRE OR IGNITION OF FLAMMABLE VAPORS, PURSUANT TO A COMPLIANCE ORDER ISSUED BY PHMSA (CPF NO. 4-2014-5017). A FLASH FIRE OCCURRED AT A RECENTLY COMPLETED WELD WHEN AIR MOVERS WERE BEING RELOCATED. A VALVE (HV-3) UPSTREAM OF THE WELD LOCATION WAS NOT SEALING RESULTING IN LEAKING HYDROCARBONS. AIR MOVERS WERE UTILIZED TO PULL THE HYDROCARBON VAPORS AWAY FROM THE WELDING LOCATION. PRIOR TO THE START OF WELDING, LEL LEVELS WERE CHECKED INITIALLY, DOCUMENTED ON THE PERMIT AND PERIODICALLY THROUGHOUT THE WELDING JOB. THESE CHECKS INDICATED A 0% LEL READING WHILE THE AIR MOVERS WERE IN OPERATIONS. WHEN THE AIR MOVERS WERE SHUTDOWN TO ACCOMMODATE MOVING ONE OF THE AIR MOVERS, HYDROCARBON VAPORS CAME IN CONTACT WITH HOT METAL (POST WELDING) AT THE WELD LOCATION AND IGNITED. POST INCIDENT, CONTINUOUS GAS MONITORING PERFORMED IN THE WORK AREA INDICATED A 0% LEL READINGS WHILE THE AIR MOVERS WERE IN OPERATIONS.\n\nPHMSA trend classification: significant incident, not serious.\n\nPHMSA standardized cause: INCORRECT OPERATION — OTHER INCORRECT OPERATION.\n\nPHMSA indexed costs: $0 reported total cost, $0 in 1984 dollars, $0 in current-year dollars.\n\nPHMSA trend flags, standardized causes, and indexed costs are analytical fields added to operator-reported incident data. They do not represent final agency causal findings.","truncated":false,"body_characters":2087}