{"operation":"document","citation":"PHMSA Report 20150248","title":"SUNOCO PIPELINE L.P. — Hazardous liquid — incident on 2015-06-14","source_type":"incident","agency":"Pipeline and Hazardous Materials Safety Administration","status":"historical","official":true,"published_on":"2015-07-13","effective_on":"2015-06-14","summary":"Hazardous liquid incident in OREGON, LUCAS County, OH. Reported cause: EQUIPMENT FAILURE. Reported consequences: 0 fatalities, 0 injuries, 0.4 HVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBIENT CONDITIONS released, $20 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings. PHMSA trend classification: not significant, not serious.","machine_formats":{"json":"https://regulus.evalyn.ai/document/phmsa-incident-df92a9914ab64cec1699495b.json","markdown":"https://regulus.evalyn.ai/document/phmsa-incident-df92a9914ab64cec1699495b.md"},"app_url":"https://regulus.evalyn.ai/document/phmsa-incident-df92a9914ab64cec1699495b","source_url":"https://data.transportation.gov/api/views/27nc-rsge/files/1d547e17-2be1-4a32-9958-a1d5a946ade9?download=true&filename=Hazardous%20Liquid%20Accident%20Data%20-%20January%202010%20to%20present.zip","body":"Hazardous liquid incident in OREGON, LUCAS County, OH. Reported cause: EQUIPMENT FAILURE. Reported consequences: 0 fatalities, 0 injuries, 0.4 HVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBIENT CONDITIONS released, $20 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.\n\nReport number: 20150248.\n\nOperator ID: 18718.\n\nReported incident date: 6/14/2015 22:09.\n\nLocation detail: 0+00\n\nCause detail: DEFECTIVE OR LOOSE TUBING OR FITTING\n\nCause detail: AT 22:09 ON 6/14/2015, A FACILITY LOCKOUT ALARM CAME IN VIA SCADA FOR THE TOLEDO PUMP STATION (TOL5). THE TOL 5 PUMP WAS SHUT DOWN AND THE TOL5 PUMP STATION WAS ISOLATED FROM THE PIPELINE. THE CONTROLLER RESPONDED TO THE ALARM AND MONITORED FOR FURTHER INFORMATION. THE CONTROLLER NOTIFIED THE FIELD SUPERVISOR AND TECHNICIAN TO INVESTIGATE THE LOCKOUT CONDITIONS. UPON ARRIVAL AT TOL5, THE TECHNICIAN OBSERVED A VAPOR RELEASE AT THE AREA NEAR THE TOP OF THE PUMP. EMERGENCY RESPONSE WAS INITIATED. ETHANE/VAPORS WERE SAFELY CLEARED AND A TRANSITION TO MAINTENANCE/REPAIR STATUS WAS MADE ON 6/15/2015. IT WAS LATER CONFIRMED THAT A SWAGELOCK FITTING WAS THE SOURCE OF THE LEAK. THE FAILED FITTING WAS PART OF THE SEAL PRESSURE/COOLING MEDIUM SYSTEM. IT WAS DETERMINED THAT THE FITTING LEAKED BECAUSE IT WAS OVER-TIGHTENED WHEN INSTALLED.\n\nPHMSA trend classification: not significant, not serious.\n\nPHMSA standardized cause: EQUIPMENT FAILURE — DEFECTIVE OR LOOSE TUBING/FITTING.\n\nPHMSA indexed costs: $2,540 reported total cost, $1,274.234 in 1984 dollars, $3,138.046 in current-year dollars.\n\nPHMSA trend flags, standardized causes, and indexed costs are analytical fields added to operator-reported incident data. They do not represent final agency causal findings.","truncated":false,"body_characters":1874}