# Global Fire and Safety, Inc. — Hazardous Materials Safety Interpretation

- **operation:** document
- **citation:** 06-0133
- **title:** Global Fire and Safety, Inc. — Hazardous Materials Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 2006-06-30
- **effective on:** Not available
- **summary:** 06-0133 response to Global Fire and Safety, Inc. concerning 180.209.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-06-0133.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-06-0133.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-06-0133
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/2006/060133.pdf
**body:**

<<<PAGE 1>>>

.S. Departmer
f Transportatio
Washirigton, D.C. 20590
400 Seventh Street, S.W.
Pipeline and
Hazardous Materials Safety
Administration
JUN 30 2006
Mr. Bill McDonald
Ref. No. 06-0133
2601 Adeline Suite 150
Global Fire and Safety, Inc.
Oakland, CA 94607
/
Dear Mr. McDonald:
This is in response to your June 6, 2006 letter requesting clarification regarding the
applicability of the Hazardous Materials Regulations (HMR; 49 CFR Parts 171-180) to
your exemption cylinder. In your scenario, you have an exemption cylinder marked DO
accordance with § 180.209(g), which allows for external visual inspections of cylinders
used exclusively for certain named gases.
The answer is yes. Upon review by the Office of Hazardous Materials Special Permits
requalified in accordance with § 180.209(g).
and Approvals, it has been determined that the cylinder specified in your request may be
I hope this information is helpful.
Hattie L. Mitchell, Chief
Regulatory Review and Reinvention
Office of Hazardous Materials Standards
180.209 (9)
060133

<<<PAGE 2>>>

Satterthwarte
$180.209(9)
Cylinders
06-0133
THE PROFESSIONALS IN WORLOWIDE SERVICE
Director, Office of Hazardous Materials Standards
400 7th Street S.W.
U.S. DOT/PHMSA (PHH-10
June 6, 2006
Washington, D.C. 20590-0001
Mr. Edward T. Mazzullo,
Ref: E-8795
We have a cylinder marked DOT E-8795 500ET with an original mfg. date of 2-85. The
Cyliner i cha fre with urined ayload a mixtures therco that are:
The exemption letter, eighth edition, states applicable regulations to a DOT specification
is service qualifies for the modified external visual cylinder re-qualification as po
B240ET with note exceptions. There is no clarification indicating that this cylinder i
CFR-49 section 180.209(g).
It is my understanding that the intent of section 180.209(g) was to allow external visual
re-qualification in order to minimize the unnecessary discharge of Halon 1301 and other
environmentally harmful agents.
Can this cylinder be re-qualified as per section 180.209(g)?
Please review this inquiry and provide a written response to indicating your decision.
espectfully
Satan Conald
Bill McDonald
2601 Adeline Suite 150
Global Fire and Safety, Inc.
510-834-2323
Oakland, Calif. 94607
•
cc: Dave Rubino
- **truncated:** false