# Georgia Fire Protection — Hazardous Materials Safety Interpretation

- **operation:** document
- **citation:** 12-0176
- **title:** Georgia Fire Protection — Hazardous Materials Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 2012-12-12
- **effective on:** Not available
- **summary:** 12-0176 response to Georgia Fire Protection concerning 180.205.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-12-0176.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-12-0176.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-12-0176
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretations/2012/120176.pdf
**body:**

<<<PAGE 1>>>

U.S. Department
of Transportation
Pipeline and Hazardous
Materials Safety
Administration
1200 New Jersey Avenue, SE
Washington, D.C. 20590
DEC 1 2 2012
Mr. W .A. Andrews
Vice President
Georgia Fire Protection
2090 Tucker Industrial Road, Suite A-6
Tucker, Georgia 30084
Ref. No. 12-0176
Dear Mr. Andrews:
This responds to your July 30, 2012letter and September 11, 2012 email requesting further
clarification of your May 25, 2012letter of clarification under Ref. No. 12-0129 on
requalification of cylinders under the Hazardous Materials Regulations (HMR; 49 CFR
Parts 171-180). Specifically, you request clarification of when a cylinder may be retested
under § 180.205(g)(5) due to equipment failure that results in a failed outcome. In your
email and May 25 letter, you describe two types of failure scenarios that led to your
request: 1) during a test of a 3AA cylinder, the test equipment failed to transfer volume
from the jacket to the weight indicating device leading to the device showing minimal or
no increase in weight, which results in either an aborted test or a failure at 100%
expansion; and 2) during a test of a 3AL cylinder, the test adapter to the cylinder had an 0-
ring failure resulting in a greater than 10% permanent expansion reading. During both of
these scenarios your technician became aware of the test equipment failure that you believe
accounted for an erroneous permanent expansion reading.
You explain further that your company uses computerized test equipment that performs
and records the test and results. Moreover, you provide information from the manufacturer
of this equipment that corroborates your conclusion of equipment failure. Finally, you also
provide the cylinder test result reports associated with these scenarios for our reference.
In accordance with§ 180.205(g)(3) of the HMR, the retester must confirm test equipment
is properly functioning before the onset of any retesting. This accuracy check of the
testing system, as well as adherence to any manufacturer maintenance recommendations, is
designed to make a retester aware of any testing system problem(s) prior to the onset of
pressure testing. Also, in accordance with§ 180.205(g)(5), a retester may perform a
system check at or below 90% of the test pressure prior to a retest to look at the testing
system and cylinder for any leaks. However, we understand that test equipment can and

<<<PAGE 2>>>

will occasionally fail during performance of a cylinder pressure test. Your questions are
paraphrased and answered as follows:
Ql. Does § 180.205(i)(1)(iv) require condemnation of the 3AA cylinder in
scenario 1 or does the test equipment failure invalidate the first attempt results and
allow a retest under § 180.205(g)(5)?
Al. As previously stated in our response under Ref. No. 12-0129, in the case of a
malfunction of the test equipment during a full retest (above 90% of the test
pressure), performance of a repeat test is authorized in accordance with
§ 180.205(g)(5). However, a cylinder required to be condemned under
§ 180.205(i) is not authorized for retesting. Section 180.205(i)(1 )(iv) refers to
condemnation of a DOT specification cylinder experiencing permanent expansion
exceeding 10% of total expansion under proper test conditions. The cylinder does
not have to be condemned if it can be substantiated that the test equipment failure
led to a false reading. Note that the reason for this repeat test must be included on
the test record in accordance with § 180.215(b )(2). The repeat test must be
performed at a pressure increased by 10% or 100 psig, whichever is less. Because
of the unique circumstance of the equipment malfunction, we recommend
recalibrating the test equipment before conducting the repeat test. Also, we
recommend performance of a system check at or below 90% of test pressure prior
to the repeat test to ensure the system is functioning properly. Finally, we caution
that at no time should a cylinder retest exceed 110% of the minimum test pressure.
If a cylinder is pressurized to more than 110% of the minimum test pressure, it may
cause embrittlement of the cylinder's sidewall which could result in failure of the
cylinder in service.
Q2. Does § 180.205(i)(1)(iv) require the condemnation of the 3AL cylinder in
scenario 2 or does the test equipment failure invalidate the first attempt results and
allow a retest under § 180.205(g)(5)?
A2. See Al.
I hope this answers your inquiry and clarifies our previous response. If you need
additional assistance, please contact this office at (202) 366-8553.
Sincerely,
7#-ZJ'h-
Robert Benedict
Chief, Standards Development Branch
Standards and Rulemaking Division

<<<PAGE 3>>>

-eoathe-
& /?.>0. 2D5
Fire Protection
~I ir1cfer~
{')_- /) !1&
July 30, 2012
US DOT
PHMSA Office of Hazardous Materials Standards
Attn: Robert Benedict, Chief, Standards Development Branch
Standards and Remarking Division
1200 New Jersey Ave. SE
Washlngton, DC 20590 0001
RefNo. 12-0129
Dear Mr. Benedict:
I find myself in the unenviable position of requesting a clarification of your clarification
letter dated July 19, 2012. Your clarification letter would appear to say that a retest is
allowed and is in order. The South East Region's interpretation appears to say that under
180.205(i)(iv), we are not allowed to retest the cylinders because the first test results
showed a permanent expansion of greater than 10%.
I will try to ask the question as specifically as possible.
On both Example 1 and 2, the pressure test was performed by an automated, computer
directed test method. The computer records the test results as an aborted, failed or passed
indication. In Exan1ple 1, the computer aborted the test but recorded a 1 00% permanent
expansion reading. In Example 2, the computer failed the test and recorded a greater than
1 0% permanent expansion reading.
During both of the tests our technician became aware of a test equipment failure that
accounted for the erroneous permanent expansion readings that were recorded.
Your letter appears to agree that the observed test equipment failure would allow a retest
under 180.205(g)(5).
However under 180.205(i), both of these cylinders recorded a permanent expansion
reading of greater than 1 0% during the first defective test attempt.
The question is: Does 180.205(i)(iv) require the condemnation of both cylinders or does
the test equipment failure invalidate the first attempt results and allow a prescribed retest
under 180.205(g)(5)?
Vice- President
2090 Tucker Industrial Road * Suite A-6 * Tucker, Georgia 30084
(770) 934-4449 * (770) 934-9974 *Fax (770) 934-4860
A DeKalb Fire Protection Service, Inc. Company

<<<PAGE 4>>>

Drakeford, Carolyn (PHMSA)
From:
Sent:
To:
Cc:
Subject:
Attachments:
Billings, Delmer (PHMSA)
Tuesday, September 11,2012 2:01PM
Drakeford, Carolyn (PHMSA)
Betts, Charles (PHMSA)
FW: Retesting restrictions
Attachment A pdf; Attachment B. pdf; Attachment C. pdf
Der k;ndereYJ
1 ~ • .Go5 lin d-ec.s
/2.-{)205
Carolyn,
Please log into Filemaker and assign for response.
Thanks.
Del
From: Betts, Charles (PHMSA)
Sent: Tuesday, September 11, 2012 1:33PM
To: Billings, Delmer (PHMSA)
Subject: Fw: Retesting restrictions
Fyi
From: Woody Andrews [mailto:wandrews@georgiafire.net]
Sent: Tuesday, September 11, 2012 09:42 AM
To: Betts, Charles (PHMSA)
Subject: Retesting restrictions
United States Department of Transportation
Standards Development
Attn: Charles Betts
Mr Betts,
We would like to request a clarification as to when a cylinder may be retested under 180.205(g)(5) due to equipment
failure that results in a recorded failed outcome. Does equipment failure invalidate the results of the initial test or is the
retest prohibited under 180.205(i)(1 )(iv) (specifically, permanent expansion greater than 1 0%) due to the recorded results
of the inititial test?
We have performed retests on cylinders that on the first test attempt have been pressurized to more than 90% of test
pressure and we have experienced equipment failure. The question is does the first recorded permanent expansion
reading of greater than 10% prevent us from performing the retest?
Background.
We operate a Galiso REC4 computerized test machine that performs and records the test function and results
automatically.
There have been two types of failures that created this delima.
Example #1: On a 3AA 1800 cylinder at an achieved pressure of 3019 psi, during the test the test equipment fails to
transfer volume from the jacket to the weight indicating device, the weight indicating device does not show or shows a
minimal increase in weight, at the end of the test the weight indicating device shows the same weight. The test is either
aborted by the test equipment or fails at 100% permanent expansion.
Attachment A sample of results of test and data. (items #8 and 9)
Attachment B. letter from manufacturer confirming test equipment failure.
Example #2: A cylinder reaches 90%+ of test pressure during an initial test but has a test adapter to cylinder o ring failure
during the test resulting in a greater than 1 0% permanent expansion reading, is a retest allowed on this cylinder when the
o-ring defect is apparent or does 180.205(i)preclude the retest.
1

<<<PAGE 5>>>

Attachment C. sample of results of test and data. (items #29 and 30)
Our reasoning is:
The results of the first test are invalid because of the equipment failure and the greater than 10% results qo not preclude a
retest.
Under the first example it is obvious to us that a cylinder cannot fail at 1 00% expansion and then pass a retest at 2.9%
without the first set of results being invalid.
Under the second example the leakage inside the jacket prevented a correct reading of the volume returned to the jacket.
The retest results show a total expansion number and permanent expansion results expected of a 3AA cylinder.
Thank you for your consideration,
Woody Andrews
Georgia Fire Protection
Office (770) 934-4449
Fax(770)934-4860
2