# Kansas Corporation Commission — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-09-0022
- **title:** Kansas Corporation Commission — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 2010-03-08
- **effective on:** Not available
- **summary:** PI-09-0022 response to Kansas Corporation Commission concerning 192.3.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-09-0022.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-09-0022.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-09-0022
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/2009/PI-09-0022.pdf
**body:**

<<<PAGE 1>>>

U.S. Department
of Transportation
Pipeline and Hazardous
Materials Safety
Administration
1200 New Jersey Avenue, SE
Washington, D.C. 20590
MAR - 8 2010
Mr. Leo M. Haynos
Chief of Gas Operations & Pipeline Safety
Kansas Corporation Commission
1500 SW Arrowhead Road
Topeka, KS 66604
Dear Mr. Haynos:
In a letter to the Pipeline and Hazardous Materials Safety Administration (PHMSA) dated
November 10,2009, you requested PHMSA's views on an interpretation you drafted in response
to a written request from Gardner Energy dated September 4,2009, for reconsideration of a
determination by the Kansas Corporation Commission (KCC) that the 1.2 mile high pressure gas
pipeline it operated was a regulated transmission line.
In its letter, Gardner Energy, the electric utility serving the City of Gardner, stated that the 1.2
mile high pressure gas line connects a Southern Star high pressure natural gas transmission line
to two combustion turbine generators. The line is a 6" diameter steel coated pipe. The metering
point is at the tap. The turbines, which are in standby mode 365 days each year, are the sole load
connected to the line; therefore, the only time that gas flows in the pipe is during operation of the
turbines. Gardner Energy stated that the turbines were used solely for "peaking" and as a result,
their operation was very limited and amounted to only 2,375.5 million cubic feet (MMCF) in
2008 and 13,133 MMCF in 2009. Based on this limited operation, Gardner contended that the
pipeline should be considered to be an unregulated service line.
Under 49 CFR § 192.3, a transmission line is defined as:
"a pipeline, other than a gathering line, that: (1) transports gas from a gathering
line or storage facility to a distribution center, storage facility, or large volume
customer that is not down-stream from a distribution center; (2) operates at a hoop
stress of 20 percent or more of SMYS; or (3) transports gas within a storage
field. "
Based on the information provided by Gardner Energy, the line is a transmission line. We
recognize that the frequency of operation of the turbines has only been occasional to date, but
The Pipeline and Hazardous Materials Safety Administration, Office of Pipeline Safety provides written
clarifications of the Regulations (49 CFR Parts 190-199) in the form of interpretation letters. These letters reflect
the agency's current application of the regulations to the specific facts presented by the person requesting the
clarification. Interpretations do not create legally-enforceable rights or obligations and are provided to help the
public understand how to comply with the regulations.

<<<PAGE 2>>>

2
this does not change the pipeline classification. Since the definition of a transmission line is met
if anyone of the three conditions in the definition is satisfied, the line meets the definition of a
transmission line for the reasons stated in KCC's draft response to Gardner. We agree with KCC
that the turbine power plant is a large volume customer for purposes of the transmission line
definition despite the limited use of the turbines to date. A power plant can potentially be used
year around and the maintenance and operating requirements for a pipeline supplying a power
plant are consistent with other transmission pipelines, not service lines in a distribution system.
Accordingly, we agree with KCC that the above-described 1.2 mile pipeline meets the definition
of a regulated transmission line.
I hope that this information is helpful to you. If I can be of further assistance, please contact me
at (202) 366-4046.
Sincerely,
o
Director, Office of Regulations
The Pipeline and Hazardous Materials Safety Administration, Office of Pipeline Safety provides written
clarifications of the Regulations (49 CFR Parts 190-199) in the form of interpretation letters. These letters reflect
the agency's current application of the regulations to the specific facts presented by the person requesting the
clarification. Interpretations do not create legally-enforceable rights or obligations and are provided to help the
public understand how to comply with the regulations.

<<<PAGE 3>>>

Gardner Energy
1150 E. Santa Fe I Gardner, KS 66030
(913) 856-7256
November 20, 2009
Mr. John Gale
U.S. Department of Transportation
Pipeline & Hazardous Materials Safety Administration
East Building, 2nd Floor
1200 New Jersey Avenue, SE
Washington, DC 20590
Dear Mr. Gale,
I represent Gardner Energy (GE) in Gardner, Kansas. About twenty years ago GE
constructed a high pressure natural gas line which serves two combustion turbine
generators that are typically used only in the summer months for "peaking". Over the
years GE maintained and operated this line without incident. Earlier this year, we were
notified by the Kansas Corporation Commission (KCC) that the line fits into the definition
of TRANSMISSION. As a result, GE has begun the effort and expense of becoming
compliant with this new classification.
On September 4, 2009, I appealed to the KCC (see attached) and requested the line be
reclassified to a service. I recently received the attached response from Leo Haynos,
Chief of Gas Operations and Pipeline Safety. My request was denied. However, Mr.
Haynos indicated in the letter that he was copying you with his correspondence and
requesting your interpretation of our gas pipeline installation and scenario. The purpose
of my letter is to provide all of the necessary backgroul1d information to assist with your
decision.
Gardner Energy certainly wants to continue to utilize this line safely and without incident
to generate electricity and meet the needs of thisjcommunity. We have been very
successful in these efforts for over twenty years: My cqncern is whether the significant
expense and effort now required by the new TRANSMISSION classification are really
necessary and how they could improve on a flawless record of operation.
WU~T~
W.C. (Bill) Krawczyk, P.E.
Electric Director

<<<PAGE 4>>>

CORPORATION COMMISSION
Mark Parkinson, Governor
Thomas E. Wright, Chairman
Michael C. Moffet, Commissioner
Joseph F. Harkins, Commissioner
November 10, 2009
Bill Krawczyk
Electric Director
Gardner Energy Center
1105 Santa Fe
Gardner KS 66030
Re: Jurisdictional Status of High Pressure Gas Line Serving the Combustion Turbine Generators
at the Gardner Energy Center
Dear Mr. Krawczyk:
I received your letter dated September 4, 2009 requesting an interpretation on the function of the
gas pipeline that serves your combustion generator facility. In your letter, you suggested the
pipeline should be considered as a long service line instead of a transmission pipeline. In my
opinion, the subject pipeline meets the definition of a transmission pipeline because it serves a
large volume customer not located downstream of a distribution center. As such, the KCC Staff
expects the City of Gardner tobe in full compliance with the Kansas pipeline safety regulations
for transmission pipelines found in K.A.R. 82-11-4.
herefore, the gas pipeline regulations in Part 192 are applicable from the transmission line tap to
the point where the lateral pipeline enters plant grounds
In your letter, you noted the pipeline in question is typically at operating pressure but gas is not
flowing through the line except when the standby generators are activated.
Analysis
Pipeline safety regulations prescribe minimum safety requirements for pipeline facilities used for
the transportation of gas. In your case, the transportation of gas can be defined generally as
movement of natural gas from the Southern Star sales point to the city property on which the
generators are located, (e.g., land associated with plant processes, usually indicated by a security
fence) and to any facilities on the plant grounds that are necessary to control the pressure or
safety of the pipeline. As pointed out in your letter, the classification of the function of the
piping determines which portion of the regulations will apply to your pipeline facilities used for
the transportation of gas. Please note that a service line ends where the pipeline connects to a
meter or to the end-user's, (ie customer's) piping. The definition implies the endpoint of a
service line is at some point where the transportation of gas has ended. Because the piping in
question is a pipeline used for the transportation of gas, I believe the definition of service line
1500 SW Arrowhead Road, Topeka, KS 66604-4027 • (785) 271-3100 • Fax: (785) 271-3354 • http://kcc.ks.gov/

<<<PAGE 5>>>

would not apply. The next iteration in the analysis would be to determine if the pipeline in
question is performing the function of distribution or transmission.
The definitions of distribution line, service line and transmission line are as follows:
Distribution Line means a pipeline other than a gathering or transmission line.
Service line means a distribution line that transports gas from a common source of supply to
an individual customer. .. A service line ends at the outlet of the customer meter or at the
connection to a customer's piping, whichever is further downstream, or at the connection to
customer piping if there is no meter.
Transmission line means a pipeline, other than a gathering line, that:
(a) Transports gas from a gathering line or storage facility to a distribution center,
storage facility, or large volume customer that is not down-stream from a distribution
center;
(b) operates at a hoop stress of 20 percent or more of SMYS; or
(c) transports gas within a storage field.
Note: A large volume customer may receive similar volumes of gas as a distribution center,
and includes factories, power plants, and institutional users of gas.
In order to prove the line is a distribution line, the analysis must prove the subject line is not a
transmission line. Therefore, the next step in the analysis is to test the applicability of the
definition of a transmission line. From the note attached to the federal definition of a
transmission line, it is clear that a power plant is considered to be a large volume customer. Once
that fact is established, the analysis must decide if the large volume customer is downstream of a
distribution center. Pipeline safety regulations do not define this term. However, a past
interpretation by the U.S. Department of Transportation provides the opinion that a distribution
center is that point where gas enters piping used primarily to deliver gas to customers who
purchase it for consumption as opposed to customers who purchase it for resale. It is my
understanding that Gardner's pipeline is connected directly to Southern Star transmission line.
Although Gardner purchases the gas for consumption, the tie-in point at Southern Star is not
connected to piping that primarily supplies gas for consumption. For example, if the Gardner
pipeline was connected to piping operated by the local distribution company, the pipeline would
be considered an extension of q distribution main. Hpwever, in the case at hand, the function of
the Gardner piping is an extension of the transmission function supplied by Southern Star.
Therefore, in my opinion, the piping in question is not downstream of a distribution center.
Because the City of Gardner is a large volume customer by definition, and the pipeline
supplying the city is not downstream of a distribution center, the pipeline serving Gardner from
the Southern Star tap to the combustion turbines is a transmission pipeline regardless of the
annual volumetric throughput or the operating pressure of the line.

<<<PAGE 6>>>

· '
Please note the above is my opinion. For a second and definitive answer to your question, I am
copying this letter to Mr. John Gale with the U.S. Department of Transportation and requesting
his interpretation of this scenario.
SinCere y {? -11,
Leo M. Hay, s
Chief of Gas Operations & Pipeline Safety

<<<PAGE 7>>>

_______________________________________________________________________
GARDNER
Connecting TheComnnmlty
Gardner Energy Center
1150 E. Santa Fe I Gardner, KS 166030
September4, 2009 XiJR1UCSJ
Mr. Leo Haynos SEP S DUE
Kansas Corporation Commission
1500 SWArrowhead Road 111 flIEs DIi'
Topeka, Kansas 66604-4027
Dear Leo,
Gardner Energy, the electric utility serving the City of Gardner, was recently audited by
a memberof your staff. Jim Gorman, an inspector in the Pipeline Safety Division, met
with me and members of my staff regarding a gas line owned and operated by the City.
In 1990 the City constructed approximately 1.2 miles of high pressure gas line in
conjunction with the installation of two combustion turbine generators. The line, which
is located in a 20' wide easement, is a 6" steel coated pipe. It connects to a Southern
Star high pressure natural gas transmission line on the southeast corner of the City.
The metering point is at the tap. The turbines, which are in standby mode 365 days
each year, are the sole load connected to the line. Therefore, the only time that gas
flows in the pipe, is during operation of the turbines.
For many years, the City performed routine maintenance on the line, but otherwise gave
very little thought and/or attention to it. Weassumed that this pipeline was nothing
more than a long "service" line. However, the Kansas Corporation Commission's
Pipeline Safety Division has recently changed that priority. We have been informed the
facility meets the definition of a "transmission" line and is therefore subject to
Department of Transportation DOTregulations. I have reviewed the formal definitions
of a "distribution" line, "service" line and "transmission" line as provided in the Kansas
Pipeline Safety Regulations. I would contend that our pipeline does not meet the
criteria for a "transmission" line. Criterion aof the definition refers to a large volume
customer. Based on the usage pattern of this equipment, Gardner Energy is not a large
volume customer.
Since our turbines are used solely for "peaking", their operation is very limited. The
turbines, which are only operated a few times a year, are connected to the end of a long
"service" line that is metered at the source of supply. In 2008, the turbines were
operated only one day for a total of 13 hours. The total gas usage for that day was
2,375.5 MCF. In 2009, the turbines were operated seven days for a total of 62 hours.
The total gas usage for those hours was 13,133 MCF. Therefore, on average Gardner
Energy only used 7,754.25 MCF of natural gas per year or 646.19 MCF per month.

<<<PAGE 8>>>

I respecifully request that the KCC Pipeline Safety Division reconsider Gardner
Energy's pipeline classification. I believe the above information supports my position
and clearly demonstrates that our pipeline meets the definition of a "service" line.
Sincerely,
oeeK
Bill Krawczyk
Electric Director
913-856-7256