# Judge Baughman — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-10-0011
- **title:** Judge Baughman — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 2010-08-04
- **effective on:** Not available
- **summary:** PI-10-0011 concerning 192.723.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-10-0011.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-10-0011.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-10-0011
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/2010/PI-10-0011.pdf
**body:**

<<<PAGE 1>>>

)
U.S. Department
of Transportation
Pipeline and Hazardous
Materials Safety
Administration
12CO New Jersey Avenue, SE
Washington, D C. 20590
AUG - 4 '20m
The Honorable William H. Baughman, Jr.
801 West Superior Avenue
Cleveland,OH 44113-1846
Dear Judge Baughman:
Thank you for your letter of June 11,2010, regarding Federal regulations pertaining to gas
distribution pipeline leakage surveys and whether they are required inside of residences. As
overseers of the Nation's 2.1 million miles of pipelines, the Pipeline and Hazardous Materials
Safety Administration (PHMSA) is committed to ensuring safety and protecting the
environment. Leakage surveys, as required under 49 CFR § 192.723, help ensure the safety of
people who live and work in proximity to pipelines.
As you note in your letter, § 192.723 requires operators of a distribution pipeline system to
conduct periodic leakage surveys. Pipelines not located in business districts must be surveyed at
least once every five years. For cathodically unprotected distribution lines on which electrical
surveys for corrosion are impractical, a leakage survey must be conducted at least once every
three years.
Also, please reference 49 CFR § 192.3, which defines a service line as a distribution pipeline that
transports gas from a common source of supply, such as a main, to one or more individual
customers. A service line ends at the outlet of a customer's meter or at the connection to the
customer's piping, whichever is farther downstream. If there is no customer meter, the service
line ends at the connection to the customer's piping.
Under these provisions, an operator must conduct a leakage survey with leak detector equipment
up to the end of the service lines. If the customer's meter or connection to the customer's piping
is located inside a personal residence, the leakage survey must include that portion of the service
line inside the residence.
Ohio is one of many states certified under 49 U.S.C. § 60105(a) to regulate intrastate natural gas
pipelines, such as those discussed in this letter. Ohio regulates such pipelines through the Public
Utilities Commission of Ohio (PUCO).
The Pipeline and Hazardous Materials Safety Administration. Office of Pipeline Safety, provides written clarifications of the Regulations (49
CFR Parts 190-199) in the form of interpretation letters. These letters reflect the agency's current application of the regulations to the specific
facts presented by the person requestmg the clarification. Interpretations do not create legally-enforceable rights or obligations and are provided
to help the public understand how to comply with the regulations.

<<<PAGE 2>>>

2
I hope this letter answers your questions and addresses your concerns. If we can be of further
assistance, please do not hesitate to contact Elizabeth Komiskey (elizabeth.komiskey@dot.gov,
phone: 202-288-1818), Harold Winnie (harold.winnie@dot.gov, phone: 816-329-3800) at our
Central Region Community Assistance and Technical Services team in Kansas City, or me at
202-366-4595.
Sincerely,
~f~'
Deputy Associate Administrator
For Field Operations
cc: Mr. Neil Eisner, Assistant General Counsel for Regulation and Enforcement, DOT
Mr. Alan R. Schriber, Chairman, Public Utilities Commission of Ohio
The Pipeline and Hazardous Materials Safety Administration, Office of Pipeline Safety. provides written clarifications of the Regulations (49
CFR Parts 190-199) in the form of interpretation letters. These letters reflect the agency's current application of the regulations to the specific
facts presented by the person requesting the clarification. Interpretations do not create legally-enforceable rights or obligations and are provided
to help the public understand how to comply with the regulations.

<<<PAGE 3>>>

ttbe ~onorablt 'William~ .• aullbman, Jr.
Wntteb 6tate. ~ourtbou.e
~ourtroom 10~
801l»e~ 6upertor m,enue
QClebelanb, c!)Jp 44113 ·1846
216/351·1220
.:Ifax: 216/351·1224
June 11,2010
Mr. Neil Eisner
Assistant General Counsel for
Regulation and Enforcement
United States Department of Transportation
1200 New Jersey Avenue S.B.
Washington, DC 20590
, .
Re: Demand ~fDominion'EastOhio for Leakage Survey of Inside Gas
Meter ,and Piping 'Under U.S~ Department of Transportation
. Regulation .
Account No. 4500014919225
Service Address: 31541 Edgewood Road, Pepper Pike, OH 44124
Meter No.' i8252265 ' . ,
Dear Mr~ 'Eisner: '
I have received a demand from my natural gas service provider, Dominion East Ohio,
for a leakage survey of my inside gas meter and piping. A copy of the demand letter is
enclosed. This demand is purportedly made under a regulation of your Department.
Through research, I have found 49 C.F.R. § 192.723, Distribution systems: Leakage
surveys. A copy of that regulation is enclosed. Although the regulation refers to leakage
surveys, I cannot determine from the regulation if it applies to the gas meter and piping inside
my residence. . . .
My efforts to 'get Il?-0re information on this leakage survey and the authority therefor
from Dominion East Ohio have been unsuccessful. The most helpful service representative
advised that the inspe'ction is required by federal regulation. She checked the records for my
residence and said that such an inspection had not been performed since 2002. This predates

<<<PAGE 4>>>

Mr. Neil Eisner
Assistant General Counsel for
Regulation and Enforcement
United States Department of Transportation
June 11,2010
Page 2
my ownership of the home. I had been a customer of Dominion East Ohio in two other
Cleveland suburbs since 1976 and have never had such a survey performed at any of my
residences.
When asked for an explanation, the customer service representative for Dominion East
Ohio stated that the company has probably been in violation of the regulation for some time
and is now undertaking these surveys under pressure from your Department. Frankly, this
all sounds pretextual to me.
I see that 49 C.F.R. § 192.723 has been in effect since 1970. I find it incredible that
Dominion East Ohio has been in default as to my properties since 1976, if indeed this
regulation applies to the interior of residential properties.
Dominion East Ohio has continued to insist on this survey, with a reminder that it can
terminate my service even if my account with them is current. I have tentatively scheduled
the survey for June 24, 2010. Accommodating Dominion East Ohio in this manner will
require me, however, to take at least one-half day from my duties as a federal magistrate
judge at the federal district court in Cleveland.
If, in fact, your Department does not have a regulation requiring this surveyor is not
insisting that surveys be conducted, I would appreciate receiving that information. I have
made inquiry with the Public Utilities Commission of Ohio, whose representative has advised
that it has no knowledge of this leakage survey program.
Sincerely,
~7f.~~la;(.
William H. Baughman, Jr. ()
gsg
Enclosures

<<<PAGE 5>>>

Justia :: 49 C.P.R. § 192.723 Distribution systems: Leakag.e surveys. Page 1 of 1
Supreme Court Center I us Laws I Blawgs.FM I BlawgSearch.com I ~
L........... ______ --.JEJ_
Justia> Law> United States> Code of Federal Regulations> Tttle 49 - Transportation> CHAPTER I--PIPELINE AND HAZARDOUS MATERIALS SAFETY
ADMINISTRATION DEPARTMENT OF TRANSPORTATION> PART 192--TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM
FEDERAL SAFETY STANDARDS> § 192.723 Distribution systems: Leakage surveys.
49 C.F.R. § 192.723 Distribution systems: Leakage surveys.
Title 49 - Transportation
Title 49: Transportation
Subpart M=Maintenance
PART 192- TRANSPORTATION OF NATURAL AND OTHER GAS BY PIPELINE: MINIMUM FEDERAL SAFETY STANDARDS
Browse Previous I Browse Next
§ 192.723 Distribution systems: Leakage surveys.
(a) Each operator of a distribution system shall conduct periodic leakage surveys in accordance with this section.
(b) The type and scope of the leakage control program must be determined by the nature of the operations and the local conditions, but it
must meet the following minimum requirements:
(1) A leakage survey with leak detector equipment must be conducted in business districts, including tests of the atmosphere in gas,
electric, telephone, sewer, and water system manholes, at cracks in pavement and sidewalks, and at other locations providing an
opportunity for finding gas leaks, at intervals not exceeding 15 months, but at least once each calendar year.
(2) A leakage survey with leak detector equipment must be conducted outside business districts as frequently as necessary, but at least
once every 5 calendar years at intervals not exceeding 63 months. However, for cathodically unprotected distribution lines subject to
§192.465(e) on which electrical surveys for corrosion are impractical, a leakage survey must be conducted at least once every 3 calendar
years at intervals not exceeding 39 months.
[35 FR 13257, Aug. 19, 1970, as amended by Amdt. 192-43,47 FR 46851, Oct. 21, 1982; Amdt. 192-70, 58 FR 54528,54529, Oct. 22,
1993; Amdt. 192-71, 59 FR 6585, Feb. 11, 1994; Amdt. 192-94,69 FR 32895, June 14, 2004; Amdt. 192-94,69 FR 54592, Sept. 9, 2004]
Browse Previous I Browse Next
Copyright © Justia - No copyright claim is made to any of the government data on these pages.
Company:: Terms of Service :: Privacy Policy:: Contact Us :: Have a Happy Day!
http://law.justia.com/us/cfr/title49/49-3.1.1.1.3.13.9.13.html 05/2812010

<<<PAGE 6>>>

P.O. Box 26666
Richmond, VA 23261-6666
May 21, 2010
Dominion®
1191 1 AV 0.335 T#00000
********* AUTO**5-DIGIT 4412
WILLIAM H BAUGHMAN
ACCOUNT NO:
31541 EDGEWOOD RD
4500014919225
PEPPER PIKE OH 44124-5117
SERVICE ADDRESS:
31541 EDGEWOOD RD
PEPPER PIKE OH 44124-5117
METER NO: 18252265
Subject: We Need To Check the Inside Service Line
It's been some time since we read or inspected the inside gas meter and piping. The U.S.
Department of Transportation (DOT) requires us to perform a leakage survey up to and
including the gas meter at least once every three years.
Please call (800)362-7557 Monday through Friday from 7:00 a.m. through 7:00 p.m. to
schedule an appointment.
Your cooperation will help us make sure the meter is safe and accurate. Thank you.
Sincerely,
Customer Service Center
Dominion East Ohio
Imr039
SEQ#: 1191 OMA-SW1: 3

<<<PAGE 7>>>

Magistrate Judge William I. Baughman, Jr.
United States District Court for the
27. 3001:2022
*92 L
Northern District of Chio
801 West Superior Avenue 10A
Cleveland, O7 44113-1846
Mr. Neil Eisner
Assistant General Counsel for
Regulation and Enforcement
United States Department of Transportation
1200 New Jersey Avenue S.E.
Washington, DC 20590
- **truncated:** false