# Peoples Natural Gas — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-72-008
- **title:** Peoples Natural Gas — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 1972-02-24
- **effective on:** Not available
- **summary:** PI-72-008 response to Peoples Natural Gas concerning 192.199.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-72-008.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-72-008.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-72-008
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/1972/PI72008.pdf
**body:**

<<<PAGE 1>>>

February 24, 1972
Mr. Joseph A. Wager
Measurement Superintendent
Peoples Natural Gas
2223 Dodge Street
Omaha, Nebraska, 68102
Dear Mr. Wager:
This is in further reply to your letter of October 1, 1971, to Mr. Barry Sweedler of the National
Transportation Safety Board, that was referred to this office for reply.
With regard to your first question regarding Subparagraph 192.197(a)(1), which states:
"A regulator capable of reducing distribution
line pressure to pressures recommended for
household appliances."
Your interpretation is correct. This refers to a pressure regulator capable of reducing distribution
line pressure (pounds per square inch) to pressures recommended for household appliances
(inches of water column).
With regard to your second question regarding Paragraph 192.199(g), which states:
"Where installed at a district regulator station
to protect a pipeline system from overpressuring, be
designed and installed to prevent any single incident
such as an explosion in a vault or damage by vehicle
from affecting the operation of both the overpressure district regulator."
protective device and
You indicated that you are interested in knowing whether a modified regulator being used for
commercial and industrial loads and delivering pressures of 5 to 25 pounds can be equipped with
a monitor or a shut-off device in the same body. You interpret that a combination regulator and
monitor in the same body will not meet the DOT specifications.
Your interpretation is correct that the regulator you described would not meet our requirements if
it were used as a district regulator. This would not exclude such a regulator from being used as a
service regulator to an industrial or commercial customer as long as you comply with the
requirements in Section 192.197.
dal\192\199\72-02-24
1

<<<PAGE 2>>>

With regard to your series of questions regarding Section 192.623 which states:
"No person may operate a low pressure distribution
system at a pressure lower than the minimum pressure
at which the safe and continuing operation of any
connected and properly adjusted low pressure gas
burning equipment can be assured."
Your questions were:
(1) Does this mean that devices must be installed where feeding gas into a low pressure
distribution system so that the system cannot continue to operate if the pressure falls below a
given amount?
(2) Would this indicate that a low pressure distribution system being fed from one regulator
station must have a station which protects against overpressure as well as underpressure?
(3) Could one place the regulators in series using one as a monitor, or could one interpret this as
meaning that another regulator or two regulators must be placed in parallel to protect against
underpressure?
All the methods that you described would be appropriate under certain operating conditions. It is
the operator's responsibility to assure that whatever method that is selected will meet the
requirements of Section 192.623 for the operating conditions of the particular system.
We trust that this will answer your particular questions. If you need further assistance, please let
me know.
Sincerely,
/signed/
Joseph C. Caldwell
Acting Director
Office of Pipeline Safety
dal\192\199\72-02-24