# New Hampshire Public Utilities Commission — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-73-019
- **title:** New Hampshire Public Utilities Commission — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 1973-07-11
- **effective on:** Not available
- **summary:** PI-73-019 response to New Hampshire Public Utilities Commission concerning 192.187.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-73-019.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-73-019.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-73-019
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/1973/PI73019.pdf
**body:**

<<<PAGE 1>>>

Jul 11 1973
Mr. Bruce B. Ellsworth
Gas Safety Engineer
New Hampshire Public Utilities Commission
26 Pleasant Street
Concord, New Hampshire 03301
Dear Mr. Ellsworth:
In your letter of June 25, 1973, you asked about "...§192.187, Vaults: sealing, venting, and
ventilation. (a) When the internal volume exceeds 200 cubic feet - (1) The vault or pit must be
ventilated with two ducts, each having at least the ventilating diameter of a pipe 4" in diameter;..."
The intent of this regulation is to assure that there is adequate ventilation so that a hazardous
condition will be avoided. Therefore, if the 8-inch vent with a 4-inch vent inside will provide
adequate ventilation to avoid this hazardous condition, the requirements of this regulation will be
satisfied. If you have any further questions relative to this requirements, please contact me.
Sincerely,
Joseph C. Caldwell
Director
Office of Pipeline Safety
dal\192\187\73-07-11