# Alabama Public Service Commission — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-74-0102
- **title:** Alabama Public Service Commission — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 1974-01-25
- **effective on:** Not available
- **summary:** PI-74-0102 response to Alabama Public Service Commission concerning 192.123.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-74-0102.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-74-0102.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-74-0102
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/1974/g74-01-25_Waldrop_192.123%20-%20lmxs.pdf
**body:**

<<<PAGE 1>>>

PI-74-0102
January 25, 1974
Mr. Larry E. Wladrop
Alabama Public Service Commission
P.O. Box 991
Montgomery, AL 36102
Dear Mr. Waldrop:
Your letter to Mr. Frank Fulton dated January 7, 1974, asked if certain service risers made for use with plastic service
piping would meet Office of Pipeline Saftety’s regulations. You specifically named items made by Perfection
Coprporation and Kerotest Manufacturing Corporation, both of which consist of a metal sheath used as a protective
shield over a plastic service riser assembly. From the information provided it appears that if these risers are installed so
that all the below ground gas containing materials are plastic, no cathodic protection is required. The metallic sheath is
not considered part of a pipeline as that term is defined in Section 192.3 of the Federal safety standards. However, the
installation must still comply with the requirements of Section 192.375, Service lines: plastic, and the limitations of
Section 192.123, Design limitations for plastic pipe, are applicable.
Thank you for your interest. We trust this answers your question satisfactorily.
Sincerely,
CESAR DE LEON
Joseph C. Caldwell
Director
Office of Pipeline Safety

<<<PAGE 2>>>

State of Alabama
Alabama Public Service Commission
P.O. Box 991
Montgomery, Alabama 36102
January 7, 1974
Mr. Frank Fulton, Chief Engineer
Office of Pipeline Safety
Department of Transportation
Washington, D. C.
Dear Mr. Fulton:
As per our conversation this date on whether or not the riser put out by the Perfection Corporation would meet
OPS's regulations, enclosed is the material that I have on this riser. I am also enclosing a riser put out by Kerotest
Manufacturing Company.
We would like your opinion at your earliest convenience as to whether either, both, or none of these risers
would meet OPS's regulations. Your prompt reply would be appreciated.
Yours very truly,
Larry E. Waldrop
Utilities Engineer

<<<PAGE 3>>>

Power, Water & Gas Department
Post Office Box 580
Sheffield, Alabama 35660
December 20, 1973
Mr. Larry E. Waldrop
Utilities Engineer
Alabama Public Service Commission
P. 0. Box 991
Montgomery, Alabama 36102
Dear Larry:
You will recall some discussions that we have had recently regarding service risers and some of the questions that have
been raised regarding pressurized risers, plastic insertion, temperature rise, etc. Jerald Mitchell has been interested in
this subject and has had considerable discussion with us during recent visits and phone conversations.
One item that we have all been particularly interested in is a prefabricated riser produced by Perfection Corporation and
distributed by Mike Deason with Empire Pipe and Supply Company, Inc. of Birmingham, Alabama.
Mike is an excellent salesman, and I think had convinced us that the Perfection riser answered all of our problems,
including the need for cathodic protection on the riser.
I felt that this item might indeed solve some of the problems involved with plastic services and understood from Mike
that the item does meet all of the Department of Transportation requirements. However, to be on perfectly safe
ground, I asked that Perfection Corporation provide us with evidence from DOT that this riser is approved by them.
I enclose a copy of a letter in response to my inquiry, and my reaction to the letter is that I am highly disappointed
because it indicates to me no approval by DOT whatever.
I should appreciate very much having comments from you and Jerald regarding your interpretation of the content of the
letter and what your reaction to the use of this item would be.
Very truly yours,
R. A. Azbell , General Manager

<<<PAGE 4>>>

Perfection Corporation
Madison, Ohio 44057
December 14, 1973
City of Sheffield, Alabama
Power, Water and Gas Department
Sheffield, Alabama 35660
Attention: Mr. R. A. Azbelle
General Manager
Dear Mr. Azbelle:
We have been asked by our representative, Mr. Mike Deason of Empire Pipe and Supply, Birmingham, Alabama, to
relate to you why our Perfection service line riser does not need to be cathodically protected.
It is in our estimation, the steel in this service line riser acts as no more than a protective shield for the plastic contained
therein, and it is not considered a part of the pipe line as that term is defined in Section 192.3 of the Federal safety
standards. Of course, that particular portion of the service line riser that carries gas is above ground, and there are no
D.O.T. requirements that we know of that require to cathodically protect a gas carrier, be it steel or any other material,
that is above ground.
We hope this has answered your inquiry satisfactorily, and we thank you for your continued interest in Perfection
Corporation products. If there are any more questions, feel free to call us at any time.
Sincerely,
Perfection Corporation
J. Edward Matz
General Sales manager
THE RIZER-FLEX OFFERS THESE ADVANTAGES:
I. Installation:
1. Adjusts to trench depth.
2. Plastic pipe can be slipped through RIZER-FLEX while straight and then bent without kinking.
3. The union nut permits a fast connection under varied field conditions.
4. Particularly adaptable to service insert renewals.
II. Safety:
1. RIZER-FLEX adjusts to soil movement and other secondary loads.
2. Flexibility relieves strain on meter set.
3. No underground transition fitting.