# Corrosion Associates — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-76-016
- **title:** Corrosion Associates — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 1976-04-08
- **effective on:** Not available
- **summary:** PI-76-016 response to Corrosion Associates concerning 192.455, 192.457.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-76-016.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-76-016.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-76-016
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/1976/PI76016.pdf
**body:**

<<<PAGE 1>>>

April 8, 1976
Mr. Richard B. Bender
Corrosion Associates
P.O. Box 11302
Fort Worth, Texas 76110
Dear Mr. Bender:
In your letter of March 31, 1976, you ask whether the exemptions
contained in Section 192.455 apply to pipelines which are subject
to the requirements of Section 192.457. We presume the question
arises from the wording of Section 192.457 which provides that
certain pipelines must be cathodically protected "in accordance
with this subpart."
By its terms, Section 192.455 specifically applies to pipelines
installed after July 31, 1971. Likewise, Section 192.457
specifically applies to pipelines installed before August 1, 1971.
This distinction in the scope of the two sections indicates that
the exemptions under Section 192.455 are intended to apply only to
pipelines installed after July 31, 1971.
In Section 192.457, the phrase "in accordance with this subpart" is
not intended to reference the exemptions from the cathodic
protection requirement of Section 192.455. This is particularly
true in light of the analogous usage of the phrase in Section
192.455 where exemptions are otherwise set forth. Rather, in both
sections the phrase is grammatically used to describe the
requirement for cathodic protection. The phrase indicates that
other regulations in Subpart I, namely Section 192.463, govern the
protection which must be provided.
Sincerely,
\signed\
Cesar DeLeon
Acting Director
Office of Pipeline
Safety Operations
dal\195\260\76-04-08
1

<<<PAGE 2>>>

March 31, 1976
Mr. Cesar DeLeon
Acting Director
Office of Pipeline Safety
Department of Transportation
Washington, D.C. 20590
Dear Mr. DeLeon:
As an independent Corrosion Consultant, I need some assistance in
interpreting a situation that has been presented to me by the
regional Federal Housing Authority, Dallas, Texas.
The question concerns Section 192.455 and Section 192.457. They
feel that they can interpret these two sections which will allow
them exempt status from cathodic protection on an apartment project
that is 20 years old. Can they apply the section dealing with
systems installed after 1971 to a system that was installed prior
to 1971? As we interpreted the law to them, they cannot do this.
In the past when we asked for help, it was inferred that only the
owner or the operator can get answers. However, as a consultant
working with your rules and regulations; and dealing with apartment
project owners who can't even spell cathodic protection, we are
working with you and need your help.
I do not like to be placed in a position where we would have to
sign a document stating that cathodic protection is not needed on
an apartment project when in fact we have interpreted your
regulations that it be protected. Perhaps a letter or an answer in
the monthly news OPSO Advisory Bulletin would benefit everyone in
the industry, including H.U.D.
I am caught between two major Federal Bureaus (DOT and HUD.) I
know the horror of a gas explosion, and I know what can be done
with cathodic protection. I will not sign a document that is not
true. Please assist me in this matter.
Sincerely yours,
RICHARD B. BENDER CORROSION ASSOCIATES
\signed\
R.B. (pipe) Bender
NACE Certification No. 14
dal\195\260\76-04-08
2

<<<PAGE 3>>>

Mr. Richard B. Bender
Corrosion Associates
P.O. Box 11302
Fort Worth, Texas 76110
Dear Mr. Bender:
In your letter of March 31, 1976, you ask whether the exemptions
contained in Section 192.455 apply to pipelines which were
installed in an apartment project 20 years ago.
By its terms, Section 192.455 specifically applies to pipelines
installed after July 31, 1971. Likewise, Section 192.457
specifically applies to pipelines installed before August 1, 1971.
This distinction in the scope of the two sections indicates that
the exemptions under Section 192.455 are intended to apply only to
pipelines installed after July 31, 1971, and not to pipelines 20
years old.
We trust this satisfactorily responds to your inquiry.
Sincerely,
\signed\
Cesar DeLeon
Acting Director
Office of Pipeline
Safety Operations
dal\195\260\76-04-08
3

<<<PAGE 4>>>

July 14, 1975
Mr. Joseph Caldwell, Director
Office of Pipeline Safety
Department of Transportation
2100 2nd Street, SW
Washington, D.C. 20590
Dear Mr. Caldwell:
Thank you for your letter of July 7, 1975 relative to the
Control, Inc. Corrosion Control Program.
Based on the preamble to Subpart I and the broad meaning of
the word "impractical", we have interpreted 192.457(b) to mean that
an electrical survey is not mandatory and that operators could use
leak surveys and/or records to determine areas of active corrosion.
We have so advised the utilities in Tennessee as can be seen from
my letter dated July 26, 1974.
Electrical survey procedures are not specific an d results can
be indefinite and inconclusive, as is well stated in the enclosed
paragraph 8-02 or Air Force Manual 88-9, Chapter 4; and other than
in appendix D, Part 192 provides no specific criteria relative to
soil resistivity or bacteria. I discussed this at length with
Lance Heverly in 1972 and it is because of the above reasons we
subsequently deleted 192.455(b) in Tennessee. It has been our
opinion that leak surveys and/or records provide a more accurate
and concrete indication of active corrosion.
With the 1976 deadline approaching we need to know whether to
redirect our utilities or amend Part 192 in Tennessee to state
specifically that leak surveys and/or records can be used as a
method of determining areas of active corrosion, if such an
amendment would not weaken the regulation. Your advice will be
appreciated.
Sincerely,
\signed\
John Searcy, Engineer
Engineering Division
dal\195\260\76-04-08
4

<<<PAGE 5>>>

July 26, 1974
TO: ALL GAS UTILITIES
FROM:John Searcy
Engineering Division
The Tennessee Public Service Commission, Engineering Division, is
the authority enforcing the gas pipeline safety regulations for
transmission and distribution in Tennessee. These regulations are
susceptible to comments and interpretations by those other than
authorized representatives of the Commission, and such comments and
interpretations may be contrary to the intent of the regulations.
Particularly susceptible are the regulations relating to leak
surveys, corrosion control, and other operations which may involve
the services of outside contractors, consultants, and/or suppliers.
Erroneous or misleading interpretations of, or statements
concerning, regulations can cost you money unnecessarily in that
services may be performed over and above that required by the
regulations. Always contact me or the Gas Safety Inspector
assigned to your area when you have questions concerning, or are in
doubt about, the regulations. Do not abide by any statement
concerning the regulations other than those made by representatives
of the Commission unless you first verify with the Commission any
statement you have heard concerning the regulations.
Outlining briefly the leak survey and corrosion control
requirements, buried or submerged distribution pipelines installed
prior to August 1, 1971, require cathodic protection by August 1,
1976, unless it can be shown that a corrosive environment does not
exist. This may be shown, for example, by an analysis of corrosion
related leak history. Pipelines unprotected because of such a
showing must be re-evaluated every three (3) years to determine
whether or not the environment has changed.
Pipelines installed after July 31, 1971, must be coated, and within
one (1) year after construction, cathodically protected, regardless
of whether or not a corrosive environment exists.
Probably the most well know cathodic protection criterion is the
-.85 volt potential. However, there are other criteria in Appendix
D of the Federal Minimum Safety Standards. Any of the criterion
may be met.
There are also atmospheric corrosion control requirements for above
dal\195\260\76-04-08
5

<<<PAGE 6>>>

ground pipelines.
Concerning leak surveys, business districts require a survey every
year, and other areas require a survey every five (5) years.
8-02 FIELD TEST METHODS. It is important that corrosion field
survey work be performed by experienced personnel. There is no
other engineering field in which so many meaningless measurements
or misinterpretations of results are likely to occur than when
inexperienced personnel are called upon to do field survey work.
Corrosion testing is widely diversified involving many different
techniques, some of which are highly specialized. Tests may
require durations of a few minutes to a year or more, and
measurements may vary over wide limits. For example, potential
measurements can vary from a few millivolts to hundreds of volts,
and the currents involved may be a few milliamperes or hundreds of
amperes. The size of a structure bears no relation to the type of
test required. A small complex structure may involve many
intricate measurements. Often the available data are fragmentary,
and the conditions that cannot be measured are of greater
significance than those that are obtainable. Consequently,
judgment and experience in field-testing techniques are of great
value. Due to the many factors involved, a corrosion investigation
may include visual inspection, study of geographical areas, study
of records, chemical analyses, electrical measurements, and
sometimes biological studies. The proper combination of tests to
use depends largely upon the data available and local conditions.
Here again, the necessity for experienced personnel is evident.
Corrosion survey reports should indicate not only the results of
the tests, but also the reasons why particular tests were used or
why they were excluded. Brief descriptions of some of the standard
test practices are now presented.
a. Soil Resistivity Measurements . The voltage drop principle
is used to determine the resistivity of soils and water. The
electrolyte resistivity plays a big part in the rate of corrosion.
However, it must be pointed out that no single test can be taken
as an absolute determination of corrosivity. Variations in
electrolyte resistivity are often the critical factor. For the
design of cathodic protection systems, a knowledge of the soil
resistivity values in a given area . . . (The remainder of this
page did not print and the typist has no idea what was in that
area!)
SUBPART I- REQUIREMENTS FOR CORROSION CONTROL
?192.457(C) Active Corrosion
dal\195\260\76-04-08
6

<<<PAGE 7>>>

1. 2. What is a condition where you have continuing corrosion that
is not detrimental to public safety?
Does this mean that if you have corrosion way out in the
country in a place where no one lives, that no cathodic
protection is required if the pipe was installed before 1971?
3. How about in a city if a pipe is 300 yards from a place where
people would congregate or live.
?192.463(d)
1. a. Each operator shall take prompt remedial action to correct any
deficiencies indicated by monitoring.
What time period does the word prompt cover?
?192.455(f)
1. As far as enforcement of Part (f) of this regulation:
a. If an operator wants to install an insulated fitting
protected by alloyage, must this operator comply with
each part of (f) (1, 2, &3)? If not, is the operator
then in violation?
b. An operator can use these fittings according to item (1)
if he can show by tests, investigation, or experience
that adequate corrosion control is provided by alloyage.
1. Does this mean that an operator must be keeping
some type of record to prove that from past
experience the alloy used in the fitting has not
had a corrosion problem. In other words, have
records showing that brass or stainless steel after
being in service for a period of years and
experienced no corrosion problem.
2. Would the operator have to prove this for all soil
resistivities?
3. Would it be adequate for an operator with no
records of tests or investigations just to say they
have experienced no corrosion problem with the
dal\195\260\76-04-08
7

<<<PAGE 8>>>

2. c. d. alloyage used in the fitting, therefore, it is
meeting ?192.455(1)?
4. Who makes the final determination as to what types
of alloyage are adequate; the operator, OPSR, OOE,
the respective region?
Must an operator test the manufacturers's design to see
if corrosion pitting would cause fitting to leak? Could
he just review manufacturer's data?
Must an operator still keep track of the location of
metal alloy fittings if the operator claims that he has
adequately proven that there is no corrosion problem in
all soil resistivity with respect to the alloy being
used.
The small municipalities would have a hard time showing by
tests and investigations that an alloy is adequate. Is it OK
for these municipalities to depend on test results from other
gas companies with respect to alloys used in these fittings as
long as they keep track of where they are putting them?
dal\195\260\76-04-08
8

<<<PAGE 9>>>

October 16, 1979
Mr. R. E. Speckmann, Manager
Regulations and Maintenance Standards
Shell Pipe Line Corporation
P.O. Box 2648
Houston, TX 77001
Dear Mr. Speckmann:
Your letter of June 19, 1979, requesting a finding under 49 CFR
195.260(e) that valves are not justified at certain water crossings
in your planned installation of the 48-inch diameter LOCAP crude
oil pipeline between the Louisiana Offshore Oil Port (LOOP)
terminal at Clovelly, Louisiana, and the existing input terminal to
the Capline system at St. James, Louisiana.
In your letter, you stated that the LOCAP pipeline begins at LOOP's
Clovelly, Louisiana, underground storage dome in Section 32, T18S,
R22E, LaFourche Parish, and extends in a northerly direction across
marshes, numerous bayous, swamps, the Intracoastal Waterway, and
some farmland to the Capline Pipeline St. James Terminal located in
Section 56, T12S, R16E, St. James Parish, Louisiana. Conditions
along the LOCAP pipeline route are such that approximately 85
percent of the pipeline will be installed in marsh and swamp areas
using weight coating for stability. The pipeline will be welded
together and floated in a ditch excavated through these areas. The
pipeline will be submerged, and the floatation ditch will be
backfield to cover the pipeline. Brackish and fresh water will
exist at various times of the year over most of the length of the
new pipeline.
You indicated that precise compliance with ?195.260(e) would result
in the placement of what the Shell Pipe Line Corporation (SPLC)
considers to be an impractical number of valves. Instead you
proposed to place valves at initiating and delivery terminals, near
Highway 3199 and near Highway 20, and on each side of the
Intracoastal Waterway. The valves at the initiating and delivery
terminals and on each side of the Intracoastal Waterway will be
remotely operable from the Capline St. James Control Center.
Further, you also proposed to install two means to detect leaks, as
discussed hereafter.
In the evaluation of your request, this Office considered the
following factors as relevant to whether justification exists for
not installing valves as required:
1. Effectiveness of Proposed Leak Detection and Shutdown System
We found your plans for automated leak detection with alarms and
dal\195\260\76-04-08
9

<<<PAGE 10>>>

remotely controlled block valves and shutdown pumps at Clovelly
Station to be an effective, integrated set of alternative measures
which will assure a level of safety far exceeding that attainable
by literal adherence to ?195.260(e). Your first method, a dynamic
computer model of the pipeline, will provide rapid response to
suddenly occurring leaks. i believe this model will read
telemetered pressures and flow rates from Clovelly and St. James.
Utilizing hydraulic surge theory, the model will calculate and
compare calculated and telemetered hydraulic variables.
Computerized computations will ascertain the divergence between
real and calculated values and send appropriate alarms to the oil
movements controller if a leak is indicated.
The proposed second method of leak detection by comparison of input
and delivery volumes will be read into a computer line balance
program and compared at periodic intervals. If a discrepancy
exists between the adjusted input and output volumes exceeding a
preset limit, the proposed leak detection alarm will be signalled
to the oil movements controller, who will be able to shut down the
pumps at Clovelly Station and isolate the pipeline by means of
remotely controlled block valves at initiating and delivery
terminals and on each side of the Intracoastal Waterway. Your
proposed leak detection and shutdown appear to be safe and surpass
the safety provided if shutdown capabilities were limited to
manually controlled valves placed as required by ?195.260(e). Even
if these remotely controlled valves failed to close in the event of
a pipeline rupture, the response time required to manually close
them should be no greater than the response time necessary to close
any manually operated valves under ?195.260(e).
2. Crossings
Threat to the Integrity of the Pipeline at the Planned Water
The waterways to be crossed other than the Intracoastal Waterway
are all less than 10 feet deep and most are less than 7 feet deep.
Flow rates are so low that erosion of the pipeline cover is highly
unlikely. Marine traffic consists of light, shallow draft boats
and an occasional flat-bottomed barge, none of which can be
expected to damage the pipeline within its 5-foot, filled trench by
direct contact or dragging anchor. For these reasons, we conclude
that the probability of pipeline rupture at these water crossings
is not appreciably greater than that for the remainder of the
pipeline.
3. Drainage from Line after Shutdown
Placement of valves on either side of the water crossing is to
limit line drainage into the waterway after shutdown in the event
of rupture at a crossing. In your proposed valving plan locations,
Drawing No. SK-0146 showing pipeline water crossings, even though a
dal\195\260\76-04-08
10

<<<PAGE 11>>>

valve is not near a crossing, very little oil is expected to escape
from any line rupture that might occur at the crossing after
shutdown occurs and all dynamic effects cease. The maximum grade
elevation variation along the pipeline is limited to approximately
15 feet. The elevation at Clovelly Dome is 0 feet to -1 foot, and
at the St. James Terminal, the elevation is approximately +14 feet
at the delivery manifold. Eighty percent of the pipeline will be
installed in marsh and swamp areas using weight coating for
stability. It is reasonable to postulate for practical purposes
that the line will lie mostly beneath the water level and that
after shutdown, water pressure will confine most of the line fill
to the pipeline except for small amounts displaced by the
differential in density between oil and water.
Therefore, in consideration of the above information and
conclusions, the Materials Transportation Bureau finds that valves
and a leak detection system installed and operated as proposed in
your letter of June 19, 1979, will provide an acceptable level of
public safety and that placement of valves on each side of every
water crossing, other than the Intracoastal Waterway, along the
LOCAP pipeline is not justified.
Sincerely,
\signed\
Cesar DeLeon
Associate Director for
Pipeline Safety Regulation
Materials Transportation Bureau
dal\195\260\76-04-08
11

<<<PAGE 12>>>

Shell Pipe Line Corporation
June 19, 1979
Mr. Cesar De Leon, Associate Director
for Pipeline Safety Regulation
Materials Transportation Bureau
Department of Transportation
Washington, D.C. 20590
Dear Mr. De Leon:
Shell Pipe Line will construct LOCAP Pipeline, a 48-inch diameter
crude oil pipeline between the Louisiana Offshore Oil Port (LOOP)
terminal at Clovelly, Louisiana, and the existing input terminal to
the Capline system at St. James, Louisiana, Capline, in turn,
delivers crude oil into the American mid-continent area.
The LOCAP pipeline segment was originally a part of the LOOP permit
applications and approvals. Recently the owners of LOCAP Pipeline
(Texaco, Inc., Marathon Pipe Line Company, Ashland Oil, Inc., and
Shell Pipe Line Corporation) selected Shell Pipe Line Corporation
to construct and operate it.
As shown on the attached sketch, the LOCAP line begins at LOOPS's
Clovelly, Louisiana, underground storage dome in Section 32, T18S,
R22E, LaFourche Parish, and extends in a northerly direction across
marshes, numerous bayous, swamps, the Intracoastal Canal, and some
farmland to the Capline Pipeline St. James Terminal located in
Section 56, T12S, R16E, St. James Parish, Louisiana.
Conditions along the LOCAP pipeline route are such that
approximately 85 percent of the pipeline will be installed in marsh
and swamp areas using weight coating for stability. The pipeline
will be welded together and floated in a ditch excavated through
these areas. The pipeline will be submerged, and the floatation
ditch will be backfilled to cover the pipeline. Brackish and fresh
water will exist at various times of the year over most of the
length of the new pipeline.
As in the case of LOOP Pipe Line System, extensive wetlands exist
along most of the LOCAP pipeline route. Since approximately 18
bayous and submerged land areas will be crossed where the width of
dal\195\260\76-04-08
12

<<<PAGE 13>>>

the crossing exceeds 100 feet (reference attached SK-046 (sic) for
crossing locations), we believe, as in the case of LOOP pipeline,
strict adherence to 49 CFR 195.206(c), "Transportation of Liquids
by Pipeline", is neither practicable nor justifiable in this
particular case. Due to the existence of a combination of water
and marsh or swamp along the proposed 48-inch pipeline, block
valves at all locations required by DOT regulations would not
improve line safety nor appreciably reduce pollution should a
failure occur.
Accordingly, we propose to install block valves at both sides of
the Intracoastal Waterway, near Louisiana Highway 3199, near
Highway 20, and at the initiating and delivery terminals. As shown
on the attached sketch, valves located at terminals and the
Intracoastal Waterway will be remotely operable from the Capline
St. James Control Center. Maximum valve spacing will be
approximately 16? miles. The recommended locations are accessible
and serve a useful purpose should damage occur to the new pipeline.
Installation of valves in the above manner takes into consideration
numerous related pipeline control factors including the following:
A. Leak Detection and Shutdown System
Line integrity features will be included in the
supervisory control system to monitor the pipeline for
leaks and provide rapid shutdown of the pipeline by the
oil movements controller in the event a leak is
detected. Two methods of monitoring for leaks will be
included in the line integrity features. The first
method, a dynamic computer model of the pipeline, will
provide rapid response to suddenly occurring leaks. The
model will read telemetered pressures and flow rates
from Clovelly and St. James. Utilizing hydraulic surge
theory, the model will calculate and compare calculated
and telemetered hydraulic variables. Shell Pipe Line's
computer program will ascertain the divergence between
real and calculated values and send appropriate alarms
to the oil movements controller if a leak is indicated.
The second method of leak detection functions by
comparison of input and delivery volumes. Input and
delivery volumes from custody transfer quality meters at
Clovelly and St. James will be gathered each supervisory
scan and will be read into a computer line balance
program and compared at periodic intervals. At each
comparison, line fill between the measurement points
will be calculated by the computer and compared with the
line fill calculation at the previous interval. Any
change in line fill between the two intervals will be
dal\195\260\76-04-08
13

<<<PAGE 14>>>

B. included in the line balance comparison. When a
discrepancy exists between the adjusted input and output
volumes exceeding a preset limit, a leak detection alarm
will be presented to the oil movements controller.
Upon indication of a leak detection alarm, the oi l
movements controller will be able to shut down the pumps
at Clovelly Station and isolate the pipeline by means of
remotely controlled block valves at initiating and
delivery terminals and on each side of the Intracoastal
Canal - Clovelly Station to East Bank of Intracoastal
Canal, East Bank to West Bank of Intracoastal Canal, and
West Bank of Intracoastal Canal to St. James Terminal.
Pressure transmitters will allow monitoring of the
pressure in each of the three line sections for
indications of leakage.
Pipeline Integrity at Planned Water Crossings (Excluding
C. the Intracoastal Waterway)
The waterways to be crossed are all less than 10 feet
deep. The waterway flow rates are such that erosion of
the pipeline cover is highly unlikely. Marine traffic
consists of light, shallow draft boats and an occasional
flat-bottomed barge, none of which can be expected to
damage the pipeline within its 5-foot backfilled trench
by direct contact or dragging anchor. A significant
degree of protection from exterior mechanical damage
will be provided by the steel reinforced concrete weight
coating approximately five inches thick and surrounding
the pipe. It may, therefore, be concluded that the
probability of pipeline rupture at these water crossings
is not greater than that for the remainder of the
pipeline.
Drainage from Line after Shutdown
Under the proposed valving plan, even though a valve may
not be near a point of rupture, very little oil is
expected to escape from any rupture after shutdown
occurs and all dynamic effects cease. Because the
maximum grade elevation variation along the pipeline is
limited to approximately 15 feet (Clovelly Dome is 0
feet to -1 feet, St. James Terminal is approximately +14
feet at the delivery manifold) and because much of the
line lies beneath the water level, the line fill should
be confined to the pipeline by water pressure except for
small amounts displaced by the differential in density
between oil and water.
In consideration of the above, your concurrence with
dal\195\260\76-04-08
14

<<<PAGE 15>>>

LOCAP pipeline valve placement at water and road crossings as
recommended is requested in lieu of requirements established under
the provisions of 195.260(e) Part 195, Transportation of Liquids by
Pipeline, DOT - Pipeline Safety Regulations.
Very truly yours,
\signed\
R. E. Speckmann, Manager
Regulations and Maintenance Standards
Attachments:
1. Sketch No. SD-13712 showing line location.
2. Drawing SK-0146 showing pipeline, water crossing, and
proposed valve locations.
dal\195\260\76-04-08
15
- **truncated:** false
- **body characters:** 26707
