# Central Plastics Company — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-77-023
- **title:** Central Plastics Company — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 1977-10-18
- **effective on:** Not available
- **summary:** PI-77-023 response to Central Plastics Company concerning 192.455.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-77-023.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-77-023.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-77-023
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/1977/PI77023.pdf
**body:**

<<<PAGE 1>>>

October 18, 1977
Mr. Bob Pourchot
Product Engineer
Central Plastics Company
P.O. Box 762
Shawnee, OK 74801
Dear Mr. Pourchot:
Your letter to Mr. Paul Cory requests that we review the design of the anodeless service riser
manufactured by Central Plastics Company and determine if it violates the requirements of the
Federal gas pipeline safety regulations, 49 CFR Part 192.
The Office of Pipeline Safety Operations (OPSO) does not approve, endorse, or make the
requested determination on proprietary items. We can, however, discuss the design and indicate
the requirements that would be applicable.
You previously supplied Mr. Cory with drawings of the service riser in question that show the
transition from plastic to metal pipe occurring belowground. This transition is enclosed in a
metallic casing that extends belowground over the plastic pipe and upward over the steel gas pipe
to a point below the threaded upper end of the service riser. The steel gas pipe and the transition
fitting are insulated from the casing by a combination of polyethylene tubing and epoxy materials.
These plastic materials fill the void between the steel gas carrying pipe and the casing and since
the plastic is not carrying gas, it is not subject to the temperature limits of Section 192.123.
Also, according to the design provided to OPSO, the steel gas carrying pipe that extends from
belowground to the head of the service riser is enclosed in a covering of plastic material which in
turn is covered by the steel casing. Plastic material fills the void between the casing and carrier
pipes and is intended to insulate the carrier pipe from the casing. If it can be shown under Section
192.455(b) that the steel gas pipe is in a location where a corrosive environment does not exist,
then cathodic protection would not be required.
dal\192\455\77-10-18
1

<<<PAGE 2>>>

Thank you for your interest in pipeline safety. If you have additional questions, please advise.
Sincerely,
\signed\
Cesar DeLeon
Acting Director
Office of Pipeline
Safety Operations
dal\192\455\77-10-18
2

<<<PAGE 3>>>

CENTRAL PLASTICS COMPANY
September 12, 1977
D.O.T., Office of Pipeline Safety
Attn: Paul Cory
Trans Point Bldg.
2100 Second Street, S.W.
Washington, D.C. 20590
Dear Paul,
We certainly appreciate your efforts to answer P.G.& E.'s questions concerning our anodeless
service riser. We are sorry for the mix-up.
As I was not entirely sure that Tom Timen was the engineer at P.G.& E. who originally inquired,
I feel it necessary to go and talk with them again. In order to prevent any further embarrassment,
I was hoping you could send me a letter. If you would review our design again and merely say if
it violates the code or not, we would be most grateful. We would then clear up the matter with
P.G.& E. and P & F ourselves.
Thanks again for your concern.
Regards,
\signed\
Bob Pourchot
Product Engineer
dal\192\455\77-10-18
3

<<<PAGE 4>>>

February 2, 1974
Mr. Richard B. Bender
Richard B. Bender Corrosion
Associates
P.O. Box 11302
Fort Worth, TX 76110
Dear Mr. Bender:
In your letter of January 17, 1974, you asked about corrosion control requirements for steel risers
on plastic service lines.
Steel risers on plastic services must be coated and cathodically protected as required by Section
192.455 of Subpart I of the Federal regulations. So as to facilitate cathodic protection, each
service riser must be electrically insulated from other house piping such as at the regulator, shut-
off valve or meter as required by Section 192.467(b). The level of protection must meet one or
more of the criteria contained in Section 192.463.
Also, the frequency for monitoring the cathodic protection applied to service risers is covered by
Section 192.465.
We trust this clarifies the requirements for corrosion control measures applicable to steel risers on
plastic services. If you desire any further information, please advise.
Sincerely,
\signed\
Joseph C. Caldwell
Director
Office of Pipeline Safety
dal\192\455\77-10-18
4