# various — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-78-017
- **title:** various — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 1978-06-20
- **effective on:** Not available
- **summary:** PI-78-017 response to various concerning 192.453.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-78-017.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-78-017.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-78-017
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/1978/PI78017.pdf
**body:**

<<<PAGE 1>>>

June 20, 1978
Mr. Robert Steffan, Chairman Mr. M.J. Schiff, Director
Southern California Cathodic Los Angeles Section
Protection Committee National Association of
National Association of Corrosion Engineers
Corrosion Engineers P.O. Box 1499
P.O. Box 1499 Houston, Texas 77001
Houston, Texas 77001
Gentlemen:
This responds to your letter of April 19, 1978, regarding your assertion that some of the
corrosion contractors are not qualified and are doing substandard corrosion work for master
meter system operators trying to comply with the Federal pipeline safety standards.
You ask what enforcement is available from Federal and State agencies. You further inquire if it
is practical to require persons designing and/or installing corrosion control systems to accept
some legal responsibility for their work.
The Federal standard (192.453) require the operator to "...establish procedures to implement the
requirements of this subpart" and that "...the design, installation, and maintenance of cathodic
protection systems must be carried out, by or under the direction of a person qualified by
experience and training in pipeline corrosion control methods." This Office has jurisdictional
authority over operators of natural gas pipeline systems under the Natural Gas Pipeline Safety Act
of 1968 and, therefore, our surveillance and enforcement program is directed toward operators to
assure that they comply with the Federal gas pipeline safety standards. Since our authority does
not extend to corrosion contractors designing and installing cathodic protection for such
operators, we cannot place requirements on such contractors. This is not to say that operators
and corrosion contractors cannot enter into contractual relationships that place a legal
responsibility on the contractor for the adequacy of his corrosion work. Such contractual
relationships would not alter the legal relationship between this Office and the operator, but it
could establish the basis for legal actions between the operator and contractor.
The Office of Operations and Enforcement has a Regional Office in Burlingame, California, that is
responsible for inspecting operators and assuring compliance with the regulations. Because of the
limited staff, their primary inspection efforts are aimed
at distribution systems and, to a lesser degree, master meter systems.
Thank you for your interest in matters of pipeline safety.
dal\192\453\78-06-20
1

<<<PAGE 2>>>

Sincerely,
\signed\
Robert L. Paullin
Associate Director for
Operations & Enforcement
Materials Transportation Bureau
dal\192\453\78-06-20
2

<<<PAGE 3>>>

LOS ANGELES SECTION
April 19, 1978
U.S. Department of Transportation
Materials Transportation Bureau
Washington, D.C. 20590
Attention: Cesar DeLeon, Acting Director
Office of Pipeline Safety Operation
Reference: Cathodic Protection of Pipelines
Gentlemen:
As officers of the Los Angeles Section of the National Association of Corrosion Engineers and of
the Southern California Cathodic Protection Committee, we have been requested to obtain
information from you regarding substandard work in the application of cathodic protection to
control corrosion on underground gas lines.
The Federal Pipeline Safety Act of 1968 required that cathodic protection be applied to
underground gas lines subject to active corrosion which might pose a hazard to the public safety.
Interpretation of this act to include master meter operations, such as mobile home parks, has
resulted in many new companies being formed to design and install cathodic protection for such
applications.
The federal law states that such work must be done "by, or under the direction of a person
qualified by experience and training in pipeline corrosion control methods". The attached
quotations from cathodic protection survey reports and photograph of an anode installation
demonstrate that some of the contractors are not qualified to do this work, and, in fact, are
actually increasing the safety hazards. It is apparent that Federal and State laws are being broken.
dal\192\453\78-06-20
3

<<<PAGE 4>>>

We recognize that code violations can be reported to contractors' licensing boards. This,
however, does not prevent incompetent contractors from operating. We would like to know if
and what enforcement is available from Federal and State Agencies. How and from whom should
it be obtained?
Is it practical to require that the person qualified to design and/or install systems sign reports and
accept some legal responsibility for their work.
Very truly yours,
\signed\ \signed\ _
Robert Steffan, Chairman M.J. Schiff, Director
Southern California Los Angeles Section
Cathodic Protection Committee National Association of Corrosion
Engineers
Attachment
Company B
INTRODUCTION
Underground gas leaks may be undetectable when the odor is filtered out by the soil.
Underground gas leaks often migrate and collect in or under structures creating an explosive
hazard. Underground gas leaks are primarily caused by corrosion. Our gas leak survey and
corrosion test was performed to determine whether pipes are now leaking and whether the pipes
are in a corrosive environment and thus likely to develop future leaks.
The Pipeline Safety Act requires among other things, that gas distributors survey to locate
and classify gas leaks according to hazard. It further requires that gas distributors either establish
that there is no corrosion or install equipment which will minimize corrosion.
dal\192\453\78-06-20
4

<<<PAGE 5>>>

Because pipes may be corroding at one location and not corroding a few feet away, it is
economically impractical to dig enough trenches and holes to visually examine all areas and
determine they are not corroding. Thus corrosion engineers use electrical tests to determine (a)
whether soil conditions are of the type which promote corrosion and (b) whether corrosive
electrical currents may be flowing in the underground piping.
personnel surveyed your mobile home park and performed tests which usually
yield an accurate estimate of the size and type of corrosion control installation needed to protect
underground piping.
Our leak report, describing the leaks found is included here as Appendix I. Appendix II
reports our measurements of soil resistivity and pipe-to-soil potentials at various points within the
park.
In the pages which follow we report our survey findings and conclusion. We also
recommend action for you to take in order to lengthen your pipe life and satisfy Federal safety
regulations.
FINDINGS
LEAKS
Leaks are detailed, listed and graded in Appendix I. Grade 1 leaks are hazardous and
must be cleared immediately (You have already been notified, if you have any). Grade 2 leaks are
potentially hazardous and should be repaired within 1 year according to the Department of
Transportation requirements. Grade 3 leaks are non-hazardous and must either be repaired or
monitored annually.
Smith & Dension surveyors found:
dal\192\453\78-06-20
5

<<<PAGE 6>>>

0 Grade 1 Leaks
0 Grade 2 Leaks
0 Grade 3 Leaks
CATHODIC PROTECTION
Our survey showed that voltages measured between gas pipes and surrounding soil varied
at various points in the park (see Appendix II). The maximum voltage variation measured was
.150 volts. This is one indicator of the flow of corrosion currents. The highest voltage measured
was only .600 volts. This value is absolutely smaller than the 0.850 volts needed to provide
protection.
SOIL RESISTIVITY
Soil resistivity was measured. The measured resistivity was 5000 ohm/cm3. Resistivities
below 3000 ohm/cm3 coupled with significant variations in pipe-to-pipe potentials indicate a hot
soil; that is, a soil which promotes rapid corrosion. With higher values of resistivity, corrosion
proceeds more slowly.
ISOLATION
Our tests indicate that your pipeline system is not electrically insulated from the gas utility
distribution system.
dal\192\453\78-06-20
6

<<<PAGE 7>>>

CONCLUSION & RECOMMENDATIONS
PIPELINE CONDITIONS
Low and variable pipe-to-soil potentials and a relatively low soil resistivity indicate that
the soil is corrosive, that actual corrosion currents are flowing from the pipes into the ground, and
that a cathodic protection installation is required to inhibit active corrosion.
NEED FOR PROTECTION
Installing a cathodic protection system will increase the life of your pipe and reduce the
leaks and the cost of repairs in future years. Further, it will bring your gas distribution system
within full compliance of the Pipeline Safety Act of 1968 and should thus reduce your liability in
the case of an accident. At the same time, you can also protect your metal water pipes. Water
system electrolysis though less dangerous than gas line corrosion and not required by law, is
equally costly to repair. Further, protecting both sets of pipes at the same time avoids the costly
effort of inserting an insulating coupling in the riser at each coach and digging up the gas water
pipes and separating them wherever they are in contact.
We have calculated that the amount of power required to protect both your gas piping and
your water is about 100 watts. This power can most economically be obtained from small
rectifiers connected to your powerline.
dal\192\453\78-06-20
7

<<<PAGE 8>>>

PROPOSAL
INSTALLATION
The cathodic protection installation will comprise 6 large graphite anodes buried in the
ground and 1 transformer rectifiers power supplies connected so as to maintain your pipes at a
negative potential higher than .850 volts. This potential will cause current to flow from the anode
bed to your pipe, thereby inhibiting the ion corrosion now occurring. will excavate, back
fill, resurface, install and wire the system required to cathodically protect your pipes and restore
your property to its original condition.
The transformer/rectifier will be mounted on an appropriate wall or post and wired to your
AC power line. All components of the system are designed for a life of 20 years. Maintenance
and monitoring instrumentation is built into the rectifier unit.
WARRANTEE
installations are completely guaranteed for a period of 1 year against defects in
materials and workmanship. Follow up tests will be made at our expense within 1 year from date
of installation completion to assure adequate performance.
REPORTS
We will prepare and submit in a manual the following plans needed for operating your
distribution system in full compliance with the Pipeline Safety Act of 1968:
1) Operating plan
2) Maintenance plan
3) Emergency plan
PRICE
The total price is $4,747.00 subject to the following conditions:
1) Sewer pipe is non-metallic.
2) No other underground metallic structures interfere influenced by the current flowing from the anode bed.
with, or are
dal\192\453\78-06-20
8

<<<PAGE 9>>>

3) Rock, if any, lies deeper than 8 feet below the where anodes are to be buried.
4) Screwed pipe joints if any, are not so rusted that soil surface in areas
they fail
TERMS
30% with authorization to proceed.
70% when installation and test are complete.
SCHEDULE
We will schedule your project within 30 days after you authorize us to proceed. Normal
installation time is five working days: Two days for excavating installation and refill and three
days for test and adjustment. In subsequent weeks we will revisit the park as often as necessary
for inspection and minor adjustments to compensate for gradual polarization which modifies
system drains as the voltages and currents equalize through the system. We will also notify you of
any pre-existing corrosion we discover as they are revealed by corrosion scale loosening.
This proposal is valid for 30 days. To authorize us to proceed please sign below and
return with an advance payment of 30%.
For: For:
Contractor's License:
Signed: _
_
_
President
Date: Signed: _
Date: _
Attachment
dal\192\453\78-06-20
9

<<<PAGE 10>>>

COMPLETE CORROSION DATA
pipe-to-soil potential reading
location reading (dc volts)
22 .53
7 .45
12 .55
1 .51
25 .6
29 .52
Soils resistivity Measured in ohm/cm3
depth reading (ohm/cm3)
8 ft. 5000
dal\192\453\78-06-20
10