# Venart Industries Limited — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-80-017
- **title:** Venart Industries Limited — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 1980-09-26
- **effective on:** Not available
- **summary:** PI-80-017 response to Venart Industries Limited concerning 192.111.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-80-017.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-80-017.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-80-017
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/1980/PI80017.pdf
**body:**

<<<PAGE 1>>>

September 26, 1980
Mr. J. K. Campbell, P.E.
Venart Industries Limited
215 - 52nd Street
Delta, British Columbia, Canada V4M 2Y3
Dear Mr. Campbell:
This refers to your letter dated August 11, 1980, in which you requested an interpretation of 49
CFR Part 192, Subpart C--Part Design, as it relates to compressor station main piping.
Question: You ask whether strict compliance with 49 CFR is mandatory or not.
Response: All pipelines subject to the Natural Gas Pipeline Safety Act (NGPSA) must comply
with the prescribed requirements of 49 CFR Part 192, "Transportation of Natural and Other Gas
by Pipeline," (copy enclosed). These requirements are considered as minimums that must be met.
Under section 11(a) of the NGPSA, operators of pipelines found not in compliance with 49 CFR
Part 192 are subject to a civil penalty not to exceed $1,000 for each violation for each day the
violation persists up to a maximum of $200,000 for any related series of violations.
Question: You ask if we agree with your interpretation of the maximum stress levels allowable
under 49 CFR Part 192.
Response: No. It appears that you have not considered the performance requirements contained
in §192.103, General, which states: "Pipe must be designed with sufficient wall thickness, or
must be installed with adequate protection, to withstand anticipated external pressures and loads
that will be imposed on the pipe after installation." The purpose of this performance requirements
if to take care of those stresses which are not relieved after construction and proof testing that
become additive to operating stresses. Some of the stresses which are of concern specifically with
compressor station deign are those caused during blowdowns and repressurization of discharge
lines, by effects of soil settlement, by major temperature changes, by mechanical and sonic
vibration, and pulsation.
We wish to emphasize that the design factor (F) contained in §192.111 is required to be used only
in determining the pressure containment abilities of the pipe. However, a person responsible for
designing a pipeline, including compressor station piping, must use appropriate design factors
and/or provide protection against the accumulative effects of all relevant stresses. Part 192 does
not specify the design factors to be used in considering stresses other than those produced by
internal pressure although the design factor (F) contained in §192.111 would be considered
appropriate.
dal\192\111\80-09-26
1

<<<PAGE 2>>>

Thank you for your very helpful analysis and discussion of MOHR circle diagrams explaining the
complexity involved in analyzing combined stresses in compressor station piping.
Sincerely,
Melvin A. Judah