# Westpac Utilities — Pipeline Safety Interpretation

- **operation:** document
- **citation:** PI-93-054
- **title:** Westpac Utilities — Pipeline Safety Interpretation
- **source type:** guidance
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** guidance
- **official:** true
- **published on:** 1993-08-24
- **effective on:** Not available
- **summary:** PI-93-054 response to Westpac Utilities concerning 192.355.
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-93-054.json
- **markdown:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-93-054.md
- **app url:** https://regulus.evalyn.ai/document/phmsa-interpretation-pi-93-054
- **source url:** https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/legacy/interpretations/Interpretation%20Files/Pipeline/1993/PI93054.pdf
**body:**

<<<PAGE 1>>>

August 24, 1993
Ms. Anne Radomski
Westpac Utilities
P.O. Box 30028
Reno, Nevada 89520-3028
Dear Ms. Radomski:
Your letter of July 20, 1993, requests our interpretation of 49 CFR §§ 192.355(b) (2) and
192.357(d) regarding venting of customer regulators. In your first question, you ask if a
meter with a relieving regulator in an enclosed space is properly vented if an outside door
to the space has slats at the top and air space clearance at the bottom. Since the regulator
has an internal relief valve, it must be vented directly to the outside atmosphere through
piping. Slats and air space are not acceptable.
Your second question asks if venting to the outside atmosphere is necessary for a confined
space that contains a working regulator and a monitor regulator. Neither regulator has
external relief. In the absence of state or local requirements to the contrary, direct venting
is not necessary if the regulator is in a confined space, and has no internal relief valve.
Accordingly, venting is not required.
The third question regards a confined space that contains a regulator with an internal relief
valve. As in the first question, the relief valve must be vented directly to the outside
atmosphere through piping.
Sincerely,
Cesar De Leon
Director, Regulatory Programs
Office of Pipeline Safety
dal\192.355\93-08-24