# U.S. DOT/PHMSA - Decision

- **operation:** document
- **citation:** 0900006480e4a518
- **title:** U.S. DOT/PHMSA - Decision
- **source type:** rulemaking
- **agency:** Pipeline and Hazardous Materials Safety Administration
- **status:** current
- **official:** true
- **published on:** Not available
- **effective on:** Not available
- **summary:** This document is PHMSA's special permit (Docket PHMSA-2007-27842) for the Midcontinent Express Pipeline (MEP). It: (1) grants a waiver from 49 CFR §§ 192.111 and 192.201 for the specified ~500-mile pipeline allowing Class 1 operation using a design factor up to 0.80 and stress levels up to 80% SMYS resulting in MAOPs stated for pipeline segments; (2) allows pressure relief/limiting devices sized so pressure in Class 1 segments will not exceed 104% MAOP (or hoop stress of 83.2% SMYS) in an overpressure event; (3) defines the “special permit area” and ties the grant to the analysis in the Special Permit Analysis and Findings; and (4) lists detailed conditions and limitations (material, manufacturing, testing, inspection, monitoring, reporting, and PHMSA's authority to revoke). The permit includes numerous technical and operational requirements and explicit limitations on PHMSA authority. (
- **machine formats:** - **json:** https://regulus.evalyn.ai/document/regulations-gov-attachment-0900006480e4a518.json
- **markdown:** https://regulus.evalyn.ai/document/regulations-gov-attachment-0900006480e4a518.md
- **app url:** https://regulus.evalyn.ai/document/regulations-gov-attachment-0900006480e4a518
- **source url:** https://downloads.regulations.gov/PHMSA-2007-27842-0005/attachment_1.pdf
**body:**

<<<PAGE 1>>>

1
U.S. DEPARTMENT OF TRANSPORTATION
PIPELINE AND HAZARDOUS MATERIALS SAFETY ADMINISTRATION (PHMSA)
SPECIAL PERMIT
Docket Number:
PHMSA-2007-27842
Requested By:
Midcontinent Express Pipeline, LLC
Date Requested:
April 4, 2007
Code Sections:
49 CFR $§ 192.111 and 201
Grant of Special Permit:
The Pipeline and Hazardous Materials Safety Administration (PHMSA) grants this special
permit to the Midcontinent Express Pipeline, LLC (MEP), subject to the conditions and
limitations set forth below, waiving compliance from 49 CFR $§ 192.111 and 192.201 for a
proposed 500-mile interstate natural gas transmission pipeline to be operated by MEP, a jointly
owned subsidiary of Kinder Morgan Energy Partners, L.P. and Energy Transfer Partners L.P.
The new pipeline will consist of approximately 40 miles of 30-inch diameter and 257 miles of
42-inch diameter pipeline in "Zone 1" and approximately 197 miles of 36-inch diameter pipeline
in "Zone 2." The pipeline will originate in Bryan County, Oklahoma and run southeasterly
through Texas, Louisiana and Mississippi to existing facilities in Choctaw County, Alabama.
This special permit allows MEP to design, construct and operate the MEP pipeline in Class 1
locations only using a design factor in § 192.111 up to 0.80 and at stress levels up to 80% of the
specified minimum yield strength (SMYS). This would result in a maximum allowable operating
pressure (MAOP) of 1,480 pounds per square inch gauge (psig) for the 42-inch and 36-inch
segments and 1,440 psig for the 30-inch segment.
This special permit also allows MEP to design, install and operate pressure relief and limiting
devices on the MEP pipeline with a capacity that would ensure the pressure in Class 1 location
pipeline segments would not exceed 104% of the MAOP or the pressure that produces a hoop
stress of 83.2% SMYS in the event an overpressure situation develops. The pipeline overpressure
criteria in Class 2 and 3 locations must conform to existing regulations.

<<<PAGE 2>>>

2
For the purpose of this special permit, the "special permit area" means the area consisting of the
entire pipeline right-of-way for those segments of the pipeline that will operate above
72% SMYS in Class 1 locations.
PHMSA grants this special permit based on the findings set forth in the "Special Permit Analysis
and Findings" document, which can be read in its entirety in Docket No. PHMSA-2007-27842
in the Federal Docket Management System (FDMS) located on the Internet at
www.Regulations.gov.
Conditions
PHMSA grants this special permit subject to the following conditions:
1)
Steel Properties: The skelp/plate must be micro alloyed, fine grain, fully killed steel with
calcium treatment and continuous casting.
2) Manufacturing Standards: The pipe must be manufactured according to American
Petroleum Institute Specification 5L, Specification for Line Pipe (API 5L), product
specification level 2 (PSL 2), supplementary requirements (SR) for maximum operating
pressures and minimum operating temperatures. Pipe carbon equivalents must be at or
below 0.23% based on the material chemistry parameter (Pcm) formula.
Fracture Control: API 5L, the American Society of Mechanical Engineers B31.8 Standard
(ASME B31.8) and other specifications and standards address the steel pipe toughness
properties needed to resist crack initiation, crack propagation and to ensure crack arrest
during a pipeline failure caused by a fracture. MEP must institute an overall fracture
control plan addressing steel pipe properties necessary to resist crack initiation and crack
propagation and to arrest a fracture within 8 pipe joints with a 99% occurrence probability
or within 5 pipe joints with a 90% occurrence probability. The plan must include
acceptable Charpy Impact and Drop Weight Tear Test values, which are measures of a steel
pipeline's toughness and resistance to fracture. The fracture control plan, which must be
submitted to PHMSA headquarters, must be in accordance with API 5L, Appendix F and
must include the following tests:
a) SR 5A - Fracture Toughness Testing for Shear Area: Test results must indicate at least
85% minimum average shear area for all X- 70 heats and 80% minimum shear area for
all X- 80 heats with a minimum result of 80% shear area for any single test. The test

<<<PAGE 3>>>

3
results must also ensure a ductile fracture and arrest;
b) SR SB - Fracture Toughness Testing for Absorbed Energy; and
c) SR 6 - Fracture Toughness Testing by Drop Weight Tear Test: Test results must be at
least 80% of the average shear area for all heats with a minimum result of 60% of the
shear area for any single test. The test results must also ensure a ductile fracture and
arrest.
The above fracture initiation, propagation and arrest plan must account for the entire range
of pipeline operating temperatures, pressures and gas compositions planned for the pipeline
diameter, grade and operating stress levels, including maximum pressures and minimum
temperatures for shut-in conditions associated with the special permit area. Where the use
of stress factors, pipe grade, operating temperatures and gas composition make fracture
toughness calculations non-conservative, correction factors must be used. If the fracture
control plan for the pipe in the special permit area does not meet these specifications, MEP
must submit to PHMSA headquarters an alternative plan providing an acceptable method to
resist crack initiation, crack propagation and to arrest ductile fractures in the special permit
area.
4)
Steel Plate Quality Control: The steel mill and/or pipe rolling mill must incorporate a
comprehensive plate/coil mill and pipe mill inspection program to check for defects and
inclusions that could affect the pipe quality. This program must include a plate or rolled
pipe ultrasonic testing (UT) inspection program to check for imperfections such as
laminations. UT inspection must be conducted on all factory beveled pipe ends. In
addition, pipe body UT inspection must be conducted on a minimum of 100% of pipe joints
and all ends, with a minimum coverage of 35% of the pipe body for those joints inspected.
Any laminations identified by the UT inspection program must be evaluated in accordance
with the acceptance criteria defined in ASTM International Standard ASTM A578/A578M
"Standard Specification for Straight-Beam Ultrasonic Examination of Rolled Steel Plates
for Special Applications (ASTM A578), " Level B or API 5L Paragraph 7.8.10. An
inspection protocol for centerline segregation evaluation using a test method referred to as
slab macro-etching must be employed to check for inclusions that may form as the steel
plate cools after it has been cast. A minimum of one macro-etch or a suitable alternative
test must be performed from the first or second heat (manufacturing run) of each sequence

<<<PAGE 4>>>

4
(approximately 4 heats) and graded on the Mannesmann scale or equivalent. Test results
with a Mannesmann scale rating of one or two out of a possible four or five scale are
acceptable.
5)
Pipe Seam Quality Control: A quality assurance program must be instituted for pipe weld
seams. The pipe weld seam tests must meet the minimum requirements for tensile strength
in API 5L for the appropriate pipe grade properties. A pipe weld seam hardness test using
the Vickers hardness testing of a cross-section from the weld seam must be performed on
one length of pipe from each heat. The maximum weld seam and heat affected zone
hardness must be a maximum of 280 Vickers hardness (Hv10). The hardness tests must
include a minimum of 3 readings for each heat affected zone, 3 readings in the weld metal
and 2 readings in each section of pipe base metal for a total of 13 readings. The pipe weld
seam must be 100% UT inspected after expansion and hydrostatic testing per API 5L.
6) Mill Hydrostatic Test: The pipe must be subjected to a mill hydrostatic test to achieve a
minimum stress level of 95% SMYS in the pipe for a minimum duration of 10 seconds.
The 95% stress level may be achieved using a combination of internal test pressure and the
application of end loads imposed by the hydrostatic testing equipment as allowed by API
5L, Appendix K
7)
Pipe Coating: The application of a corrosion resistant coating to the steel pipe must be
subject to a coating application quality control program. The program must address pipe
surface cleanliness standards, blast cleaning, application temperature control, adhesion,
cathodic disbondment, moisture permeation, bending, minimum coating thickness, coating
imperfections and coating repair.
8)
Field Coating: A field girth weld joint coating application specification and quality
standards to ensure pipe surface cleanliness, application temperature control, adhesion
quality, cathodic disbondment, moisture permeation, bending, minimum coating thickness,
holiday detection and repair quality must be implemented in field conditions. Field joint
coatings must be non-shielding to cathodic protection (CP). Field coating applicators must
use valid coating procedures and be trained to use these procedures.
9) Coatings for Trenchless Installation: Coatings used for directional bore, slick bore and
other trenchless installation methods must resist abrasions and other damages that may
occur due to rocks and other obstructions encountered in this installation technique.

<<<PAGE 5>>>

10) Bends Quality: Certification records of factory induction bends and/or factory weld bends
must be obtained and retained. All bends, flanges and fittings must have carbon
equivalents (CE) below 0.42 or a pre-heat procedure must be applied prior to welding for
CE above 0.42.
I1) Fittings: All pressure rated fittings and components (including flanges, valves, gaskets,
pressure vessels and compressors) must be rated for a pressure rating commensurate with
the MAOP and class location of the pipeline. Designed fittings (including tees, elbows and
caps) must have the same design factor as the adjacent pipe.
12) Design Factor - Pipelines: Pipe installed under this special permit in Class 1 location may
use a design factor of 0.80.
13) Temperature Control: The compressor station discharge temperature must be limited to
120° Fahrenheit. A temperature above this maximum temperature of 120° Fahrenheit may
be approved if MEP technical coating operating tests show that the pipe coating will
properly withstand the higher operating temperature for long term operations. If the
temperature exceeds 120° Fahrenheit MEP must also institute a coating monitoring
program in these areas using ongoing Direct Current Voltage Gradient (DCVG) surveys or
Alternating Current Voltage Gradient (ACVG) surveys or other testing to demonstrate the
integrity of the coating. This program will be approved by and results provided to the
regional offices of PHMSA where the pipe is in service.
14) Overpressure Protection Control: Mainline pipeline overpressure protection must be
limited to a maximum of 104% MAOP.
15) Welding Procedures: For automatic or mechanized welding the 20th Edition, of API 1104,
"Welding of Pipelines and Related Facilities, " will be used for welding procedure
qualification, welder qualification and weld acceptance criteria. Operator must use the
19th Edition of API 1104 for all other welding processes. The appropriate PHMSA
regional office must be notified within 14 days of the beginning of welding procedure
qualification activities. Automated or manual welding procedure documentation must be
submitted to the same PHMSA regional office.
16) Depth of Cover: The soil cover must be a minimum depth of 36 inches in all areas. In
areas where threats from chisel plowing or other activities are threats to the pipeline, the
top of the pipeline must be installed at least one foot below the deepest penetration above

<<<PAGE 6>>>

the pipeline. If routine patrols or other observed conditions indicate the possible loss of
cover over the pipeline, MEP will perform a depth of cover study and replace cover as
necessary to meet the minimum depth of cover requirements specified herein.
17) Construction Quality: A construction quality assurance plan to ensure quality standards
and controls must be maintained throughout the construction phase with respect to:
inspection, pipe hauling and stringing, field bending, welding, non-destructive examination
(NDE) of girth welds, field joint coating, pipeline coating integrity tests, lowering of the
pipeline in the ditch, padding materials to protect the pipeline, backfilling, alternating
current (AC) interference mitigation and CP systems. All girth welds must be non-
destructively examined by radiography or alternative means. The NDE examiner must
have all required and current certifications.
18) Interference Currents Control: Control of induced AC from parallel electric transmission
lines and other interference issues that may affect the pipeline must be incorporated into the
design of the pipeline and addressed during the construction phase. Issues identified and
not originally addressed in the design phase must be brought to PHMSA's attention by
notifying the appropriate regional office. An induced AC program to protect the pipeline
from corrosion caused by stray currents must be in place within six months after placing
the pipeline in service.
19) Test Level: The pre-in service hydrostatic test must be to a pressure producing a hoop
stress of at least 100% SMYS and 1.25 X MAOP in areas to operate to 80% SMYS. Short
segments of pipe (up to one mile in length) having a design factor between 72% SMYS and
less than 80% SMYS may be tested with 80% SMYS pipe provided the test pressure
produces a hoop stress of at least 1.25 X MAOP for all pipe tested.
20) Assessment of Test Failures: Any pipe failure occurring during the pre-in service
hydrostatic test must undergo a root cause failure analysis to include a metallurgical
examination of the failed pipe. The results of this examination must preclude a systemic
pipeline material issue and the results must be reported to PHMSA headquarters and the
appropriate PHMSA regional office.
21) Supervisory Control and Data Acquisition (SCADA) System Capabilities: A SCADA
system to provide remote monitoring and control of the pipeline system must be employed.
22) SCADA Procedures: A detailed procedure for establishing and maintaining accurate

<<<PAGE 7>>>

7
SCADA set points must be established to ensure the pipeline operates within acceptable
design limits at all times.
23) Mainline Valve Control: Mainline valves located on either side of a pipeline segment
containing a High Consequence Area (HCA) where personnel response time to the valve
exceeds one hour must be remotely controlled via the SCADA system. The SCADA
system must be capable of closing these mainline valves and monitoring the valve position,
as well as upstream pressure and downstream pressure at the mainline valve. As an
alternative, a leak detection system for mainline valve control is acceptable.
24) Pipeline Inspection: The pipeline must be capable of passing in-line inspection (ILI) tools.
All headers and other segments covered under this special permit that do not allow the
passage of an ILI device must have a corrosion mitigation plan.
25) Gas Quality Monitoring: An acceptable gas quality monitoring and mitigation program
must be instituted to not exceed the following limits:
a) H¿S (1.0 grain per 100 standard cubic feet or 16 parts per million (ppm), maximum);
b) CO2 (3% maximum);
c) H2O (less than or equal to 7 pounds per million standard cubic feet and no free water);
and
d) Other deleterious constituents that may impact the integrity of the pipeline.
26) The pipeline must have an ongoing pigging and liquids sampling plan to identify, mitigate
and remove deleterious constituents where applicable.
27) If H¿S is above 8 ppm up to a maximum of 16 ppm, the gas stream constituents must be
reviewed for implementation of a quarterly pigging/inhibitor injection program, including
follow up sampling of liquids at receipt points.
28) Gas Quality Control: Separators or Filters/separators must be installed at locations where
gas is received into the pipeline where the incoming gas stream quality includes potentially
deleterious free liquids and/or particulates to minimize the entry of contaminants and to
protect the integrity of downstream pipeline segments.
29) Gas Quality Monitoring Equipment: Equipment, including moisture analyzer,
chromatograph and semi-annual H¿S sampling (quarterly sampling where H¿S is above
8 ppm), must be installed to permit the operator to manage and limit the introduction of
contaminants and free liquids into the pipeline.

<<<PAGE 8>>>

8
30) Cathodic Protection: The initial CP system must be operational within 12 months of
placing any pipeline segment in service.
31) Interference Current Surveys: Interference surveys must be performed within six months
of placing the pipeline in service to ensure compliance with applicable NACE International
Standard Recommended Practices 0169 and 0177 (NACE RP 0169 and NACE RP 0177)
for interference current levels. If interference currents are found, MEP will determine if
there have been any adverse affects to the pipeline and mitigate the affects as necessary.
MEP will report the results of any negative finding and the associated mitigative efforts to
the appropriate PHMSA regional office.
32) Corrosion Surveys: Corrosion surveys of the affected pipeline must be completed within
six months of placing the respective CP systems) in operation to ensure adequate external
corrosion protection per NACE RP 0169. The survey will also address the proper number
and location of CP test stations as well as AC interference mitigation and AC grounding
programs per NACE RP 0177.
33) Verification of Cathodic Protection: An interrupted close interval survey (CIS) must be
performed in concert and integrated with ILl in accordance with 49 CFR Part 192 Subpart
O reassessment intervals for all HCA pipeline mileage. At least one CP test station must be
located within each HCA with a maximum spacing between test stations of one-half mile
within an HCA. If any annual test station reading fails to meet 49 CFR Part 192, Subpart I
requirements, remedial actions must occur within six months. Remedial actions must
include a CIS on each side of the affected test station and all modifications to the CP
system necessary to ensure adequate external corrosion control.
34) Initial Close Interval Survey (CIS) - Initial: A CIS must be performed on the pipeline
within two years of the pipeline in-service date. The CIS results must be integrated with
the baseline ILI to determine whether further action is needed.
35)
Initial Coating Assessment - MEP must assess the integrity of the pipeline coating after
completion of padding and backfill during construction through use of coating indirect
assessment methods such as DCVG or ACV surveys or equivalent methods. MEP must
remediate any damaged coating found during these assessments that are classified as minor
and at or above 15% IR for DCVG or at or above 30 dBuV for ACVG, moderate or severe
based on NACE International Recommended Practice 0502-2002, Pipeline External

<<<PAGE 9>>>

9
Corrosion Direct Assessment Methodology, (NACE RP 0502-2002). A minimum of two
coating survey assessment classifications must be excavated, classified and/or remediated
per each survey crew and compressor station discharge pipeline section to verify survey
results.
36) Pipeline Markers: MEP must employ line-of-sight markings on the pipeline in the special
permit area except in agricultural areas or large water crossings such as lakes where line-
of-sight markers are not practical. The marking of pipelines is also subject to Federal
Energy Regulatory Commission orders or environmental permits and local restrictions.
37) Pipeline Patrolling: Pipeline patrolling must be conducted at least monthly (12 times per
calendar year), not to exceed 45 days, to inspect for excavation activities, ground
movement, wash-outs, leakage or other activities and conditions affecting the safe
operation of the pipeline.
38) Monitoring of Ground Movement: An effective monitoring/mitigation plan must be in
place to monitor for and mitigate issues of unstable soil and ground movement.
39) Initial ILI: MEP must perform a baseline ILI in association with the construction of the
pipeline using a high-resolution Magnetic Flux Leakage (MFL) tool to be completed within
three years of placing a pipeline segment in service. MEP must perform a baseline
geometry tool run after completion of the hydrostatic strength test and backfill of the
pipeline, (just prior to placing the pipeline in service) but no later than six months after
placing the pipeline in service in accordance with the conditions allowed by the special
permit.
40) Future ILI: A second high-resolution MFL inspection must be performed and completed
on the pipe subject to this special permit within the first reassessment interval required by
49 CFR Pat 192, Subpart O, regardless of HCA classification. Future ILI must be
performed on a frequency consistent with Subpart O for the entire pipeline covered by this
special permit.
41) Direct Assessment Plan: Headers, mainline valve bypasses and other sections in the
special permit area that cannot accommodate IL tools must be part of a Direct Assessment
(DA) plan or other acceptable integrity monitoring method using External and Internal
Corrosion Direct Assessment criteria (ECDA/ICDA).
42) Damage Prevention Program: The Common Ground Alliance's (CGA) damage prevention

<<<PAGE 10>>>

10
best practices applicable to pipelines must be incorporated into the MEP damage
prevention program.
43) Anomaly Evaluation and Repair: Anomaly evaluations and repairs in the special permit
area, regardless of HCA status, must be performed based upon the following:
a) Anomaly Response Time: Repair Immediately
- Any anomaly within a special permit area operating up to 80% SMYS with a
failure pressure ratio (FPR) equal to or less than 1.1 and/or an anomaly depth equal
to or greater than 80% wall thickness.
b) Anomaly Response Time: Repair Within One Year
- Any anomaly within a special permit area operating at up to 80% SMYS with a
FPR equal to or less than 1.25.
c) Anomaly Response Time: Monitored Conditions
- Anomalies not requiring immediate or one year repairs per paragraphs a and b
above must be reassessed according to 49 CFR Part 192, Subpart O reassessment
intervals.
- Each anomaly not repaired under the immediate repair requirements must have a
corrosion growth rate and ILI tool tolerance assigned per the Gas Integrity
Management Program (IMP) to determine the maximum re-inspection interval.
d) Anomaly Assessment Methods
- MEP must confirm the remaining strength (R-STRENG) effective area method,
0.85dL and ASME B31G assessment methods are valid for the pipe diameter, wall
thickness, grade, operating pressure, operating stress level and operating
temperature. MEP must also use the most conservative method until confirmation
of the proper method is made to PHMSA Headquarters.
- Dents in the pipe in the special permit area must be evaluated and repaired per
49 CFR § 192.309(b) for the baseline geometry tool run and per 49 CFR
§ 192.933(d) for future ILI.
44) Potential Impact Radius Calculation Updates: If the pipeline operating pressures and gas
quality are determined to be outside the parameters of the C-FER Study, a revised study
with the updated parameters must be incorporated into the IMP.
45) Reporting - Immediate: MEP must notify the appropriate PHMSA regional office within

<<<PAGE 11>>>

11
24 hours of any non-reportable leaks occurring in the special permit area.
46)
Reporting - 30 Day: At least thirty (30) days prior to the pipeline in- service date under
this special permit, MEP must report on its compliance with special permit conditions to
PHMSA headquarters and the appropriate regional offices.
a) Special Permit Conditions 1 through 25, 28, 29, 35, 36, 44 and 46 must be completed
and implemented with documentation available for PHMSA review prior to operating
at the Special Permit MAOP.
b) Special Permit Conditions 3, 13, 14, 16, 18, 21, 22 through 34, 36 through 43, 45 and
47 must be included in the operator's written operating and maintenance (O&M)
procedures manual concerning permit condition requirements with documentation
available for PHMSA review prior to operating at the Special Permit MAOP.
47) Annual Reporting: MEP must report the following to the appropriate PHMSA regional
offices annually:
a) The results of any ILl or direct assessment results performed within the special permit
area during the previous year;
b) Any new integrity threats identified within the special permit area during the previous
year;
c) The number of new residences, other structures intended for human occupancy and
public gathering areas built within the special permit area;
d) Any class or HCA changes in the special permit area during the previous year;
e) Any reportable incidents associated with the special permit area that occurred during
the previous year;
f Any leaks on the pipeline in the special permit area that occurred during the previous
year;
g) A list of all repairs on the pipeline in the special permit area made during the previous
year;
h) On-going damage prevention initiatives on the pipeline in the special permit area and a
discussion of their success or failure;
i) Any changes in procedures used to assess and/or monitor the pipeline operating under
'Annual reports must be received by PHMSA by the last day of the month in which the Special Permit is dated. For
March 31 each year beginning in 2009.
example, the annual report for a Special Permit dated March 4, 2008, must be received by PHMSA no later than

<<<PAGE 12>>>

12
this special permit; and
j) Any company mergers, acquisitions, transfers of assets, or other events affecting the
regulatory responsibility of the company operating the pipeline to which this special
permit applies.
Limitations:
PHMSA grants this special permit subject to the following limitations:
1) PHMSA has the sole authority to make all determinations on whether MEP has complied
with the specified conditions of this special permit.
2) Should MEP fail to comply with any of the specified conditions of this special permit,
PHMSA may revoke this special permit and require MEP to comply with the regulatory
requirements in 49 CFR §§ 192.111 and 192.201.
3) PHMSA may revoke, suspend or modify a special permit based on any finding listed in
49 CFR § 190.341(h)(1) and require MEP to comply with the regulatory requirements in
49 CFR §§ 192.111 and 192.201.
4) Should PHMSA revoke, suspend or modify a special permit based on any finding listed in
49 CFR § 190.341(h)(1), PHMSA will notify MEP in writing of the proposed action and
provide MEP an opportunity to show cause why the action should not be taken unless
PHMSA determines that taking such action is immediately necessary to avoid the risk of
significant harm to persons, property or the environment (see 49 CFR § 190.341(h)(2)).
5) The terms and conditions of any corrective action order, compliance order or other order
applicable to a pipeline facility covered by this special permit will take precedence over the
terms of this special permit in accordance with 49 CFR § 190.341(h) (4).
AUTHORITY: 49 U.S.C. 60118(c) and 49 CFR § 1.53.
Issued in Washington, DC on
DEC
5 2008
Bittese
Jeffrey D. Wiese,
Associate Administrator for Pipeline Safety

<<<PAGE 13>>>

of Transportation
U.S. Department
1200 New Jersey Avenue, SE
Materials Safety
Pipeline and Hazardous
DEC 5 2008
Washington, D.C. 20590
Administration
Mr. M. Dwayne Burton
Vice President, Gas Pipeline Operations and Engineering
Kinder Morgan, Inc.
One Allen Center
500 Dallas Street, Suite 1000
Houston, TX 77002
Docket No. PHMSA-2007-27842
Dear Mr. Burton:
On April 4, 2007, you wrote to the Pipeline and Hazardous Materials Safety Administration
(PHMSA) requesting a waiver of compliance from the Federal pipeline safety regulations in
49 CFR §§ 192.111 and 192.201 for approximately 500-miles of proposed interstate natural gas
transmission pipeline. This pipeline will be operated by Midcontinent Express Pipeline, LLC
(MEP), a jointly owned subsidiary of Kinder Morgan Energy Partners, L.P., and Energy
Transfer Partners L.P. The new pipeline will originate in Bryan County, Oklahoma, and run
southeasterly through Texas, Louisiana and Mississippi to existing facilities in Choctaw County,
Alabama.
On October 13, 2008, PHMSA published the final rule, Standards for Increasing the Maximum
Allowable Operating Pressure for Gas Transmission Pipelines, which becomes effective 30 days
after publication. The rule covers the requirements for any pipeline to operate at a design factor
of up to 0.80 in Class 1 areas. PHMSA is proceeding with issuing the Midcontinent Express
Pipeline special permit as a result of the thorough analysis contained in the Special Permit
Analysis and Findings document, prepared well in advance of the final rule. Moreover, since
the Midcontinent Express pipeline varies from certain provisions of the final rule, this special
permit is necessary to cover all requested variances from regulations and required conditions,
and is consistent with, or more stringent than, prior grants of special permit for existing
pipelines.
PHMSA is granting this waiver through the enclosed special permit, which allows MEP to
design, construct and operate the MEP pipeline in Class 1 locations, using a design factor in
§ 192.111 up to 0.80 and at stress levels up to 80% of the specified minimum yield strength
(SMYS). This would result in a maximum allowable operating pressure (MAOP) of 1,480 psig.
This special permit also allows MEP to design, install and operate pressure relief and limiting
devices on the MEP pipeline, with a capacity that would ensure the pressure in Class 1 location
pipeline segments would not exceed 104% of the MAOP, or the pressure that produces a hoop
stress of 83.2% SMYS in the event an overpressure situation develops. This special permit has
conditions and limitations and provides some relief from the Federal pipeline safety regulations
for the MEP pipeline, while ensuring that pipeline safety is not compromised.

<<<PAGE 14>>>

Page 2
Mr. M. Dwayne Burton
Docket No. PHMSA-2007-27842
My staff would be pleased to discuss this special permit or any other regulatory matter with
you. John Gale, Director of Regulations, (202-366-0434), may be contacted on regulatory
matters and Alan Mayberry, Director of Engineering and Emergency Support (202-366-5124),
may be contacted on matters specific to this special permit.
Sincerely,
Direse
Jeffrey D. Wiese
Associate Administrator for Pipeline Safety
Enclosure: Special Permit