Customer Meters and Regulators: Location
§ 192.353 Customer Meters and Regulators: Location#
(a)Each meter and service regulator, whether inside or outside a building, must be installed in a readily accessible location and be protected from corrosion and other damage, including, if installed outside a building, vehicular damage that may be anticipated.#
(b)Each service regulator installed within a building must be located as near as practical to the point of service line entrance.#
(c)Each meter installed within a building must be located in a ventilated place and not less than 3 feet (914 millimeters) from any source of ignition or any source of heat which might damage the meter.#
(d)Where feasible, meters and regulators previously installed inside of buildings will be relocated to outside of building when the regulator or meter is removed for any reason.#