192.375
Service Lines: Plastic
§ 192.375 Service Lines: Plastic#
(a)Each plastic service line outside a building must be installed below ground level, except that it may terminate above the ground and outside the building, if:#
(1)The above ground part of the plastic service line is protected against deterioration and external damage; and#
(2)It may terminate above ground level and outside the building, if -#
(i)The above ground level part of the plastic service line is protected against deterioration and external damage;#
(ii)The plastic service line is not used to support external loads; and#
(iii)The riser portion of the service line meets the design requirements of §192.204. Each plastic service line inside a building must be protected from external damage.#