P-70-020
P-70-020
NTSB safety recommendation P-70-020.
THE NTSB RECOMMENDS THAT THE UNITED STATES OF AMERICA STANDARDS INSTITUTE B31.8 COMMITTEE TAKE THE FOLLOWING ACTION: INCLUDE IN ITS STANDARDS A REQUIREMENT THAT SURVEYS BE MADE OF EXISTING SYSTEMS TO DETERMINE THE EXTENT OF CORROSION DAMAGE AND TO REPLACE OR FURTHER CATHODICALLY PROTECT THOSE FACILITIES FOUND CORRODED BEYOND A SPECIFIED MINIMUM, AND FURTHER, USE THE NATIONAL ASSOCIATION OF CORROSION ENGINEERS STANDARDS AS A GUIDELINE.
Priority: CLASS II
Overall Status: Closed - Acceptable Action
Issued Date: 1969-12-04
Adopted Date: 1969-12-04
Overall Date Closed: 1976-07-20
Synopsis: ON JUNE 3, 1969, A SERIES OF EXPLOSIONS AND FIRES OCCURRED IN THE NATURAL GAS DISTRIBUTION SYSTEM IN THE WESTERN HALF OF THE GLEN PARK RESIDENTIAL SUBDIVISION OF GARY, INDIANA. THERE WERE NO FATALITIES, BUT NINE RESIDENTS AND FIVE FIREMEN WERE INJURED. SEVEN HOUSES WERE DESTROYED, AND 45 OTHERS INCURRED DAMAGE EXTENDING FROM MINOR TO VIRTUAL DESTRUCTION. TOTAL PROPERTY DAMAGE WAS ABOUT $350,000.
Probable Cause: The Board finds that the probable cause of this accident was a combination of personnel error and system inadequacy. Involved were the inadvertent opening of a separation valve by a gas company employee allowing gas at 20 p.s.i.g. to flow into a 1/4 p.s,i,g. system and a system which could not control adequately such an increase in pressure owing to the lack of overpressure protection devices. Thereafter, the increase in pressure caused the failure of a regulator diaphragm which allowed an 80-fold overpressure in the low-pressure system to become continuous for 30 - 45 minutes. Significant contributing causal factors were: 1. The inaccessibility of the shutoff valve for the regulator which failed. 2. The lack of systematic review of the hazards in the conversion operation which could have revealed the hazardous condition in which one human error could produce catastrophe, coupled with the lack of a written plan for conversion. 3. The absence in Code B31.8 of any specification of safeguards to be employed at separation (isolation) valves during pressure conversions. 4. The lack of complete leakage surveys, before and during the pressure increase in the eastern area, which would have probably disclosed and leaking condition of the pipe and avoided the major leaks which occurred on June 3, 1969.
Ntsbnumber: DCA69FP004
Report Number: PAR-UNNUMBERED
Addressee Name: American Society of Mechanical Engineers
Addressee Status: Closed--No Longer Applicable
Addressee Date Closed: 1976-07-20
Addressee Acronym: ASME
Addressee Organization Type: A-Associations
Communication Date: 1970-06-26
Communication Type: Official Correspondence
Communication Contents: LETTER FROM THE CHAIRMAN OF THE COMMITTEE: THE CODE COMMITTEE INDICATES THAT A NEW CORROSION CONTROL CHAPTER HAS BEEN DEVELOPED AND WILL BE INCLUDED IN THE CODE THIS YEAR. THIS NEW CHAPTER TAKES INTO ACCOUNT PROVISIONS OF THE NACE STANDARD WHICH ARE SPECIFICALLY APPLICABLE TO GAS PIPING SYSTEM. THE CHAPTER INCLUDES REQUIREMENTS TO EVALUATE EXISTING SYSTEMS TO DETERMINE THE EXTENT OF CORROSION. UNSATISFACTORY CONDITIONS WOULD HAVE TO BE CORRECTED. 12/15/70 - THE "GUIDE FOR GAS TRANSMISSION & DISTRIBUTION PIPING SYSTEMS", ISSUED BY THE ASME GAS PIPING STANDARDS COMMITTEE (FORMERLY B31.8) INCLUDES NEW CHAPTER IN CORROSION CONTROL WHICH GENERALLY COMPLIES WITH THE RECOMMENDATION. CORRESPONDENCE DOCUMENTATION INCOMPLETE.
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.