NTSB safety recommendation P-73-034.
THE NTSB RECOMMENDS THAT THE EXXON PIPE LINE COMPANY: INITIATE A THOROUGH CATHODIC PROTECTION SURVEY OVER THIS SYSTEM, FROM HEARNE TO SATSUMA AS A MINIMUM, AND AT RANDOM INTERVALS UNCOVER AND PHYSICALLY INSPECT THE PIPE, WITH PARTICULAR EMPHASIS ON THE KNOWN "HOT SPOT" CORROSION AREAS.
Priority: CLASS II
Overall Status: Closed - Acceptable Alternate Action
Issued Date: 1973-08-10
Adopted Date: 1973-08-01
Overall Date Closed: 1976-07-20
Synopsis: ON MAY 14, 1972, A SHUTDOWN, CLOSED-IN 8-INCH PIPELINE OWNED BY THE EXXON PIPE LINE COMPANY RUPTURED NEAR HEARNE, TEXAS. THE CRUDE OIL FLOWED ALONG A SMALL STREAM AND WAS DAMMED UP 1 FOOT DEEP IN A STOCK POND 1,800 FEET FROM THE LEAK. VAPORS FROM THE CRUDE OIL, WHICH CONTINUED TO LEAK FROM THE RUPTURE, ENTERED A HOUSE AND WERE IGNITED. THE EXPLOSION KILLED ONE PERSON, SERIOUSLY BURNED TWO OTHERS, DESTROYED THE HOUSE, MELTED NEARBY COMMUNICATION LINES, AND SCORCHED AN 1,800-FOOT-LONG AREA.
Ntsbnumber: PLD72XR003
Report Number: PAR-73-02
Addressee Name: ExxonMobil Corporation
Addressee Status: Closed--No Longer Applicable
Addressee Date Closed: 1976-07-20
Addressee Organization Type: P-Private Industry
Communication Date: 1973-12-20
Communication Type: Official Correspondence
Communication Contents: LETTER FROM EXXON PIPE LINE COMPANY: AT PRESENT WE HAVE NO PLAN TO RETURN THE LINE TO SERVICE. IN THE EVENT WE SHOULD HAVE A NEED FOR THE LINE, WE WILL UNCOVER, INSPECT, AND REPAIR ALL AREAS WITH EXCESSIVE CORROSION, AND WILL PRESSURE TEST THE LINE BEFORE RETURNING IT TO SERVICE.