NTSB safety recommendation P-77-025.
INSTRUCT ITS CREWS TO ASCERTAIN POSITIVELY BY ALL POSSIBLE MEANS THE TYPE AND SIZE OF EXISTING GAS LINE FACILITIES BEFORE WORKING ON THEM.
Priority: CLASS II
Overall Status: Closed - Acceptable Action
Issued Date: 1977-09-27
Adopted Date: 1977-09-16
Overall Date Closed: 1978-11-21
Synopsis: ON MAY 25, 1977, AN EXPLOSION AND FIRE DESTROYED A BUILDING AT 65-67 ARCH STREET IN GREENWICH, CONNECTICUT. TWO ADJACENT BUILDINGS WERE ALSO DESTROYED AND ANOTHER BUILDING WAS HEAVILY DAMAGED. FIREMEN EVACUATED RESIDENTS FROM A TWO-BLOCK AREA 30 MINUTES AFTER THE EXPLOSION. TEN PERSONS REQUIRED MEDICAL TREATMENT FOR INJURIES CAUSED BY THE ACCIDENT.
Ntsbnumber: DCA77FP024
Report Number: None
Addressee Name: Connecticut Natural Gas Corporation
Addressee Status: Closed--No Longer Applicable
Addressee Date Closed: 1978-11-21
Addressee Acronym: CNG
Addressee Organization Type: S-State Government
Communication Date: 1977-10-13
Communication Type: Official Correspondence
Communication Contents: CONNECTICUT NATURAL GAS CORP. LTR: THE CNG CORP. SUSPENDED ALL HOT LINE INSULATION FITTING INSTALLATIONS UNTIL EVENTS SURROUNDING THE ACCIDENT COULD BE EVALUATED. CNG CORP. HAS IMPLEMENTED REVISED WRITTEN PROCEDURES TO REQUIRE A COMPLETE REVIEW OF EXISTING RECORDS PRIOR TO COMMENCING WORK. IT ALSO REQUIRES A TEST TAP TO DETERMINE THAT A PIPE IS A GAS CARRIER AND NOT A SLEEVE BEFORE ACTUAL HOT TAP IS PERFORMED. 2/1/78 - CNG LTR TRANSMITTING MATERIAL REQUESTED BY NTSB IN LETTER OF 1/24/77: CNG GUIDELINES FOR INSTALLATION OF HOT TAP INSULATOR FITTINGS, AND PROCEDURE TO INSTALL HOT TAP INSULATOR FITTINGS.
Addressee Acronym: CNG
Addressee Organization Type: S-State Government
Communication Date: 1978-01-24
Communication Type: Official Correspondence