P-82-034
P-82-034
NTSB safety recommendation P-82-034.
THE NTSB RECOMMENDS THAT THE MISSOURI POWER AND LIGHT COMPANY: REVIEW ITS MAPS AND RECORDS OF DISTRICT REGULATOR STATION PIPING TO DETERMINE THEIR ACCURACY AND COMPLETENESS AND TAKE APPROPRIATE ACTION WHERE NECESSARY TO CORRECT THESE DOCUMENTS.
Priority: CLASS II
Overall Status: Closed - Acceptable Action
Issued Date: 1982-09-08
Adopted Date: 1982-08-24
Overall Date Closed: 1983-02-16
Synopsis: ON JANUARY 28, 1982, AT CENTRALIA, MISSOURI, NATURAL GAS AT 47 PSIG ENTERED A LOW PRESSURE DISTRIBUTION SYSTEM WHICH NORMALLY OPERATED AT 11 INCHES WATER COLUMN (0.40 PSIG) AFTER A BACKHOE BUCKET SNAGGED, RUPTURED, AND SEPARATED THE 3/4-INCH-DIAMETER STEEL PRESSURE REGULATOR CONTROL LINE AT THE MISSOURI POWER AND LIGHT COMPANY'S DISTRICT REGULATOR STATION NO. 1. THE BACKHOE, WHICH WAS OWNED AND OPERATED BY THE CITY OF CENTRALIA, WAS BEING USED TO CLEAN A DITCH LOCATED ADJACENT TO THE PRESSURE REGULATOR STATION. THE HIGH PRESSURE GAS ENTERING CUSTOMER PIPING SYSTEMS IN SOME CASES RESULTED IN HIGH PILOT LIGHT FLAMES WHICH INITIATED FIRES IN BUILDINGS; WHILE IN OTHER CASES, THE PILOT LIGHT FLAMES WERE BLOWN OUT, ALLOWING GAS TO ESCAPE WITHIN THE BUILDINGS. OF THE 167 BUILDINGS AFFECTED BY THE OVER PRESSURE, 12 WERE DESTROYED AND 32 SUSTAINED MODERATE TO HEAVY DAMAGES. FIVE PERSONS RECEIVED MINOR INJURIES.
Probable Cause: None
Ntsbnumber: DCA82MP010
Report Number: PAR-82-03
Addressee Name: Missouri Power and Light Company
Addressee Status: Closed--No Longer Applicable
Addressee Date Closed: 1983-02-16
Addressee Organization Type: P-Private Industry
Communication Date: 1982-10-07
Communication Type: Official Correspondence
Communication Contents: MISSOURI POWER AND LIGHT COMPANY LETTER: WE HAVE PERFORMED THIS RECOMMENDATION IN CONNECTION WITH THE PREVIOUS ONE. WE HAVE REVIEWED CONTROL LINE LOCATIONS BY INSPECTION OF RECORDS AND BY EXCAVATION. ALTERATIONS WERE MADE WHERE NECESSARY.
Addressee Organization Type: P-Private Industry
Communication Date: 1983-02-16
Communication Type: Official Correspondence
Communication Contents: The actions you have described concerning appropriate inspections and reviews with associated corrective actions are satisfactory in fulfilling these recommendations. We have placed P-82-33 and -34 in a “Closed--Acceptable Action” status.