P-84-033
P-84-033
NTSB safety recommendation P-84-033.
THE NTSB RECOMMENDS THAT THE WASHINGTON GAS LIGHT COMPANY: REQUIRE THAT A SUPERVISOR TRAINED IN THE COMPANY PROCEDURES FOR THE WORK BEING CONDUCTED BE PRESENT TO DIRECT ALL OPERATIONS WHICH, THROUGH EMPLOYEE ERROR, WOULD POSE SUBSTANTIAL THREATS TO THE SAFETY OF EMPLOYEES OR THE PUBLIC.
Priority: CLASS II
Overall Status: Closed - Acceptable Alternate Action
Issued Date: 1984-08-23
Adopted Date: 1984-08-09
Overall Date Closed: 1985-05-03
Synopsis: ON OCTOBER 13, 1983, SEVEN EMPLOYEES OF THE WASHINGTON GAS LIGHT COMPANY WERE ASSIGNED TO PERFORM REQUIRED ANNUAL OPERATING AND MAINTENANCE INSPECTIONS ON A FLOW CONTROL VALVE AND A PRESSURE CONTROL VALVE AT ITS HERNDON GATE STATION IN FAIRFAX COUNTY, VIRGINIA. AS PART OF THE WORK TO BE DONE, THE EMPLOYEES DISCONNECTED THE GAS CONTROL SIGNAL LINE AND REMOVED THE BOLTS OF THE FLOW CONTROL VALVE BONNET BEFORE INSPECTING THE PIPE SEGMENT CONTAINING THE CONTROL VALVES TO INSURE THAT IT HAD BEEN ISOLATED AND VENTED PROPERLY. AT 10:13 A.M., WHILE TRYING TO REMOVE THE VALVE BONNET, NATURAL GAS AT ABOUT 150 PSIG BLEW THE BONNET UPWARD, AND GAS FILLED THE ENCLOSED PORTION OF THE BUILDING IN WHICH THE EMPLOYEES WERE WORKING. THE EMPLOYEES WITHIN THE STATION FLED OUTSIDE TO SAFETY; HOWEVER, THE FOREMAN REENTERED THE BUILDING. MOMENTS LATER, AT 10:18 A.M., GAS WAS IGNITED AND EXPLOSION AND FIRE, FOLLOWED DEMOLISHING THE BUILDING. THE FOREMAN WAS KILLED AND TWO EMPLOYEES RECEIVED MINOR INJURIES. THE CIRCUMSTANCES OF THIS ACCIDENT, AS WELL AS THOSE INVOLVED IN THE OCTOBER 29, 1982, ACCIDENT AT BURKE, VIRGINIA, INDICATE THE NEED FOR BETTER TRAINING OF WGL EMPLOYEES TO SUPPORT THEIR UNDERSTANDING OF PROCEDURES AND TO BE ALERT TO THE POTENTIAL CONSEQUENCES WHEN SUCH PROCEDURES ARE NOT CARRIED OUT EXPLICITLY. WHILE THE SAFETY BOARD IS PLEASED THAT WGL HAS INTENSIFIED TRAINING GIVEN TO ITS TRANSMISSION AND DISTRIBUTION DEPARTMENT EMPLOYEES, AN EQUALLY INTENSIVE EFFORT APPEARS NEEDED FOR ALL EMPLOYEES WHOSE RESPONSIBILITIES INVOLVE OPERATIONS WHEREIN A FAILURE TO UNDERSTAND OR TO FOLLOW REQUIRED SAFETY PROCEDURES MAY RESULT IN INJURIES OR DEATH TO EMPLOYEES OR THE PUBLIC.
Probable Cause: None
Ntsbnumber: DCA84MP001
Report Number: PAR-84-03
Addressee Name: Washington Gas
Addressee Status: Closed - Acceptable Alternate Action
Addressee Date Closed: 1985-05-03
Addressee Organization Type: P-Private Industry
Communication Date: 1985-01-11
Communication Type: Official Correspondence
Communication Contents: WGL CO. LTR: COMPANY PROCEDURES REQUIRE THAT A PERSON WITH SUPERVISORY RESPONSIBILITY, TRAINED IN THE COMPANY PROCEDURES FOR THE WORK BEING CONDUCTED BE PRESENT TO DIRECT ALL OPERATIONS WHICH, THROUGH EMPLOYEE ERROR, WOULD JEOPARDIZE CONTINUED SAFE OPERATION OF A GAS SYSTEM AND POSE SUBSTANTIAL THREATS TO THE SAFETY OF EMPLOYEES AND THE PUBLIC. THEREFORE, THE COMPANY, EXERCISING PRUDENT JUDGEMENT, WILL DETERMINE WHICH OF THESE TASKS CONSTITUTE SUBSTANTIAL THREATS AS USED HEREIN AND ACT ACCORDINGLY.
Addressee Organization Type: P-Private Industry
Communication Date: 1985-05-03
Communication Type: Official Correspondence
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.