Page 1Official PDFS TI WASHINGTON, D.C. ISSUED: October 2, 1980 Mr. Peter F. Lepanto City Manager City Hall P.O. Box 569 Cordele, Georgia 31015 / } SAFETY RECOMMENDAT ION (s) P-80-73 i A t 11:lO a.m., e.s.t., on February 21, 1980, an explosion and fire destroyed four stores in a shopping complex, severely damaged an adjoining restaurant, and damaged eight cars in Cordele, Georgia. Gas leaking from a 1-inch service line at 22 psig pressure migrated under a concrete block wall, into a service line trench, under a concrete slab floor, and into a jewelry store where it was ignited by an unknown source. Of the eight persons who were injured, three died later as a result of injuries received in the accident. Buildings and nearby automobiles were damaged extensively; no estimate of the dollar loss was made. The gas department construction crew responded promptly to the accident and shut off gas to the affected section of the shopping complex by digging up and closing the tap tee on the gas main. G a s shutoff was completed 40 minutes after the explosion. lJ On February 18, 1980, a crew from the city of Cordele Gas Department discontinued service and removed the gas meter from a gasoline service station that was being torn down. Since no maps, records, or measurements were available, the crew used a pipe locator to locate the service line and a backhoe and shovel to dig for it. While digging for the service line, the backhoe snagged and broke it a t a threaded coupling and pulled it laterally more than 1 2 inches out of line. The crew removed the remains of the threaded coupling, installed a 1-inch threaded cutoff valve, closed the valve and put a plug in the open end, backfilled the excavation, and left the scene. No further excavation was done to check for possible additional line damage, and no gas leak survey was conducted to check for escaping gas. - 1/ For more detailed information. read "PiDeline Accident ReDort--MuniciDal Gas Department of Cordele, Georgia, Explosion and Fire, Cordele, Georgia, Febriary 21, 1980" (NTSB-PAR-80-5). 2944-A#
Page 2-2- During t h e investigation, a survey revealed heavy concentrations of gas in the south end of the shopping complex, in the parking areas, and around a 6-inch gas main adjacent to the jewelry store. Further investigation revealed that the service line had been pulled from a compression coupling, located approximately 1 4 feet upstream of the closed valve, when the backhoe snagged it. Natural gas at 22 psig leaked from the broken coupling. No gas leak complaints had been received by the gas department before the accident. The gas department's records showed that only 195 gallons of odorant had been injected into the gas distribution system between March and November 1979. Records showing the daily average odorant level were not maintained, as required by 49 CFR 192.625, Odorization of Gas. However, t h e use of only 195 gallons of odorant in this system over a 9-month period would not be consistent with maintenance of an adequate level of odorization as prescribed by the regulation. Well-odorized gas, leaking at 22 psig pressure from the open end of a 1-inch service line for 3 days before the explosion, should have been easily detected. Title 49 CFR 192.615, Emergency Plans, requires that: "(d) Each operator shall establish a continuing educational program to enable customers, the public, appropriate government organizations, and persons engaged in excavation-related activities to recognize a gas pipeline emergency for the purpose of reporting it to the operator or the appropriate public officials. The program and the media used must be as comprehensive as necessary to reach all areas in which the operator transports gas. The program must be conducted in English and in other languages commonly understood by R significant number and concentration of the non- English speaking population in the operator's area." Interviews conducted by the Safety Board with some injured persons and other witnesses in the accident area revealed that they were not aware of how natural gas should smell. Also, they were not aware of any public education program, initiated by t h e city of Cordele, which explained t h e characteristics of natural gas or what to do in case of gas odor detection. The city manager and the superintendent stated that Cordele had not yet established a gas education program. Between 1972 and 1980, the Safety Board investigated 17 pipeline accidents which occurred on municipal gas systems and which caused 25 fatalities and several million dollars in damage. Most of the accidents, like this one, could have been prevented by the application of proper practices and procedures and by adherence to the prescribed regulations.#
Page 3-3- As a result of this accident, the National Transportation Safety Board recommends that the city of Cordele Gas Department: Immediately initiate a program, as required by 49 CFR 192.615(d), to enable its customers and the general public to recognize the odor of natural gas and to know the proper action to take when it is detected (Class I, Urgent Action) (P-80-73) KING, Chairman, McADAMS, GQLDMAN, and BURSI.EY, memberGconcurred in this recommendation. DRIVER, Vice Chairman, did not participate.#
This is an NTSB safety recommendation letter. NTSB recommendations are advisory and do not themselves create binding regulatory requirements.