PHMSA FIR, Enbridge Pipelines, LLC, 2013-05-17
PHMSA FIR, Enbridge Pipelines, LLC, 2013-05-17
Page 1Official PDFDOT U.S. Department of Transportation PHMSA Pipelines and Hazardous Materials Safety Administration OPS Office of Pipeline Safety Southwest Region Principal Investigator Molly Atkins Region Director R.M. Seeley Date of Report 2/24/2014 Subject Failure Investigation Report – Enbridge Pipelines, LLC, Tank 3013 24- inch Fill Line failure in Cushing, OK Operator, Location, & Consequences Date of Failure 5/17/20131 Commodity Released West Texas Intermediate Crude Oil City/County & State Cushing, Lincoln County, OK OpID & Operator Name 31947, Enbridge Pipelines, LLC Unit # & Unit Name 22464, Cushing Tank Farm SMART Activity # 143591 Milepost/Location Cushing, OK, Tank Farm Type of Failure Internal Corrosion, Microbiologically Influenced (MIC) Fatalities 0 Injuries 0 Description of area impacted No off-site impacts; however, there were on-site impacts to vegetation, containment ponds, and small animals/reptiles Property Damage $13,844,274 (Final Report)2 1 Event occurred on May 17, 2013, but was not discovered or reported until May 18, 2013. 2 Enbridge Pipelines, LLC. (Revision: 12/18/2013). 7000.1 Report 20130208.#
Page 2Failure Investigation Report – Enbridge Cushing Tank Farm May 17-18, 2013 Executive Summary On the afternoon of May 18, 2013, Enbridge Pipelines, LLC (Enbridge), reported a release of approximately 2,500 barrels of crude oil from its Tank 3013 fill line into on-site containment ponds. The leak originated on the Tank 3013 fill line located outside of tank containment dike areas in a drainage swale on the morning of Friday, May 17, 2013. The leak—which was not visible at the surface due to vegetation in the drainage swale—was not identified until an odor was detected by operations personnel, prompting further investigation into line balance calculations and site conditions. The leak was observed and confirmed at 1:00 p.m. CT on Saturday, May 18, 2013. Tank 3013 and its fill line were deinventoried and isolated, a unified command response center was set up, and clean-up began. The Tank 3013 fill line was excavated to investigate the source of the leak, which was found on the bottom of the pipe at the low point of the fill line. The failed pipe section was removed and transported to a metallurgical laboratory for examination and testing. The Tank 3013 fill line was replaced in its entirety. In December 2013, after the new line was tested, Tank 3013 and the fill line were returned to service. There were no injuries, fatalities, fires, explosions, or off-site impacts as a result of this leak. On-site impacts were limited to vegetation, soil, and retainment pond areas. Approximately 2,246 barrels of crude oil were released and 2,071 barrels were recovered. Forensic metallurgical analysis determined that the immediate cause of failure was internal corrosion. System Details The Cushing Tank Farm is operated by Enbridge, which has a terminal located in Cushing, Oklahoma. The Enbridge terminal is 2 miles long and comprised of three operating areas: the North, Central, and South Terminals. The South Terminal is located in Lincoln County, Oklahoma, while the Central and North Terminals are in Payne County, Oklahoma. The Enbridge terminal currently has 89 breakout tanks, as well as several tanks in various stages of inspection or demolition and additional tanks currently under construction. The tally of 89 tanks was taken at the time of the most recent inspection and included 28 breakout tanks in the South Terminal, 34 breakout tanks in the Central Terminal, and 27 breakout tanks in the North Terminal. The terminal is operated by a local control room that is manned 24 hours, seven days per week. Events Leading up to the Failure Tank 3013 and the connecting tank fill lines were purchased by Enbridge from Skelly Oil Company in 1980. The tank has operated in crude oil service from the time of purchase to the present. Tank 3013 was out of service for an American Petroleum Institute (API) 653 internal inspection from May 2011 through May 8, 2013, when the tank roof was floated by injection of 50,000 barrels of oil. On May 10, 2013, the tank level radar gage was recalibrated, causing the calculated tank volume to increase by 1,879 barrels although no additional oil was added to the tank. Tank 3013 was refilled on May 14, 2013, after which point no additional withdrawals or injections were made and the tank valves remained in their normal open position for “ready for service” mode until the time of the release. Page 2 of 8#
Page 3Failure Investigation Report – Enbridge Cushing Tank Farm May 17-18, 2013 On Friday, May 17, 2013, maintenance pigging was performed on a line that is part of the Basin Pipeline System, owned by Plains All American Pipeline, L.P. Coordination of activities related to the interface of that pipeline within the Enbridge Cushing Terminal was monitored by the controller on duty during the day shift. Enbridge outside technicians worked with the Plains All American Pipeline personnel who were performing the pigging and line-fill activities in the North Terminal area. On Friday, May 17, 2013, a product movement alarm was acknowledged for Tank 3013 at 14:39:09 supervisory control and data acquisition (SCADA) time. The alarm noted a volume of (b) (7)(F) . Despite the controller’s acknowledgment of the alarm, it was not cleared at that time. No further product movement alarms were received for Tank 3013. Because there was not a second alarm during that shift, and because the controller thought the first movement alarm was related to weather and had cleared itself, the alarm remained in the stack and was not discussed in the shift hand-off (SHO). The SHO from night shift to day shift on Saturday, May 18, 2013, did not mention anything about Tank 3013. The daily balance performed at about 7:30 a.m. Central Time (CT) noted an imbalance of approximately the same value as the tank bottom adjustment for Tank 3013; the coincidental similarity was attributed to the accounting entry rather than a possible leak because the controller did not have any indication of abnormal conditions in Tank 3013. The subsequent balance check performed Saturday morning caused the controller to make a mental note of the imbalance, which he decided to investigate further if it did not return to normal after lunch. Around 1:00 p.m. CT on Saturday, May 18, 2013, an outside technician was returning to the control room with lunch when he detected an odor. The outside technician communicated this information to the controller, who instructed the outside technician to investigate the Tank 3013 area while he began further review of the balance information and trending data. The outside technician reported to the controller that there were no visible signs of a leak in the vicinity of Tank 3013. However, the controller asked the outside technician to continue looking and indicated that the issue might be related to Tank 3013. By this time the product was just becoming visible on the surface of the dirt bank and the containment pond, into which it was flowing. The following aerial view depicts the site layout: Page 3 of 8#
Page 4Failure Investigation Report – Enbridge Cushing Tank Farm May 17-18, 2013 Tank 3013 Site Layout Shortly after 1:00 p.m. CT, operations personnel confirmed that oil was leaking from the 24-inch- diameter line connected to Tank 3013 at a low point in the line where it crossed below a drainage ditch. Oil was found to have migrated from the drainage ditch into a nearby containment pond and then into a second, larger containment pond via a connecting drainage creek. Upon confirmation of the leak, all connecting tank and manifold valves were closed to stop the outflow of oil. The outside technician closed the Tank 3013 isolation valve and provided the controller with leak confirmation on the Tank 3013 fill line. The controller initiated spill response notifications and set up the incident command at the Cushing Terminal office location. Emergency Response Operator Response The operator identified the release shortly after 1:00 p.m. CT on May 18, 2013, after which the operator initiated its spill response plan and recovered approximately 2,071 barrels of the 2,246 barrels released. All product was contained onsite and within planned containment areas. The clean-up operations were carried out in extremely severe weather, yet did not result in injury or further release of product. The operator reported the release to the National Response Center (NRC) Office 1047579 at 2:33 p.m. CT on May 18, 2013. The original release volume was estimated at 1,500 barrels (Appendix B). PHMSA Response PHMSA dispatched an accident investigator to the site. The accident investigator arrived on Sunday, May 19, 2013, and remained onsite until Wednesday, May 22, 2013. Investigation Details PHMSA’s investigation included a detailed review of the events and associated procedures related to internal corrosion prevention, alarm response, and terminal balancing activities, as well as the numerous control room processes related to leak detection and suspected leak investigation. Page 4 of 8#
Page 5Failure Investigation Report – Enbridge Cushing Tank Farm May 17-18, 2013 Terminal piping leak detection is managed by monitoring flow rates, pressures, and tank volumes, as supplemented by the SCADA alarm system. In addition, a tank volume balance procedure is used to identify imbalances in tank levels that could indicate product loss either directly from a tank or from the associated piping. The SCADA system was designed and is managed by the Enbridge Pipeline Control Systems and Leak Detection group in Edmonton, Canada; however, various inputs to the system are set by operations technicians in Cushing, Oklahoma. (b) (7)(F) —which is set when no tank movement is anticipated and will trigger an alarm if the calculated tank movement exceeds the set value. (b) (7)(F) (b) (7)(F) . This volume was chosen due to the size of the tank (capacity greater than 100,000 barrels) and to avoid nuisance alarms during weather events due to shifting of floating roofs and product movement inside the tank, which can generate barrel movement volume ranging from 200 to 300 barrels. Fluctuation of the floating roof during weather events can be an inch or more. If the volume is not set high enough to account for such movements the tank movement alarms would not be meaningful during adverse weather events. In addition to tank balancing, other leak detection methods include visual checks and surveillance by camera. These methods are intended to work in concert with the tank alarms as a comprehensive set of actions designed to detect leaks as early as possible. Terminal monitoring by outside technician personnel includes a drive-through of the facility on a two- hour cycle, use of the Commodity Movement Tracking System for volumetric measurements on both a two-hour and a daily basis, and surveillance cameras installed inside the tank areas. Metallurgical Examination Following initial clean-up, an 8.5-foot section of the failed pipe was sent to Det Norske Veritas Germanischer Lloyd (DNVGL) in Columbus, Ohio, for metallurgical analysis. A summary of DNVGL’s findings may be found later in this section, and the complete metallurgical report is provided in Appendix D. DNVGL’s report indicated that the leak in the 24-inch pipe originated from a hole 1.4 inches long and 0.8 inches wide (circumference) that was located beneath black deposits in an area of discrete internal corrosion on the bottom of the pipe. In total, there were four corrosion pits found in the pipe. The leak hole was 100 percent through the pipe wall, while the remaining three pits were between 35 percent and 53 percent through the pipe wall. There was no evidence of general Page 5 of 8#
Page 6Failure Investigation Report – Enbridge Cushing Tank Farm May 17-18, 2013 corrosion or pitting on the external surface of the pipe, and the pipe coating was well adhered in areas away from the leak site. The pipeline steel’s tensile properties, Charpy properties, and chemical composition were shown to meet the API 5LX Grade X70 line pipe steel requirements in place at the time of manufacture. The average wall thickness measured was 0.284 inches, slightly greater than the specified value of 0.281 inches shown on the construction drawings. High to very high concentrations of aerobic, anaerobic, acid-producing, sulfate-reducing, and iron- related bacteria were detected on the inside surface of the pipe at the leak site. Additionally, low to moderate concentrations of all five bacteria types were detected in deposits removed from the leak location in an area with no significant corrosion. The presence of microorganisms on the pipe surfaces, combined with higher levels of bacteria present at the leak site, indicates that microbiologically induced corrosion (MIC) is likely the primary corrosion mechanism. DNVGL’s analysis determined that the leak occurred as a result of internal corrosion that propagated through the pipe wall at the 6:17 o’clock position. The internal corrosion was likely exacerbated due to the accumulation of deposits/sediments caused by non-flowing conditions. There was no indication that the failure involved a mechanical (i.e. strength-related) component. Figure 1 provides a field photograph of the failure location and a close-up view of the pipe leak location: Findings & Contributing Factors Enbridge completed a detailed incident investigation and shared their findings with PHMSA, including the following analysis of the events that delayed the detection of the release (Appendix E). These events corroborated the findings of on-site interviews of operations personnel conducted by PHMSA immediately after the release. The following is a summary of findings from the operator’s analysis of the delayed detection: Page 6 of 8#
Page 7Failure Investigation Report – Enbridge Cushing Tank Farm May 17-18, 2013 A tank movement alarm was received approximately 2.5 hours after the leak began when a tank movement limit of 310 barrels was exceeded. This was mistakenly believed to be a false alarm due to normal variations in calculated volume caused by weather effects. Tank balancing calculations conducted every 2 hours on May 17-18 also revealed unexplained losses in tank volume. These were not acted upon, however, because the utilized volume limit was not exceeded in any of the 2-hour time periods. Finally, a 1,573-barrel-loss in tank volume was recorded by the 24-hour tank balance procedure conducted the morning of May 18. This also was not acted upon, as it was mistakenly believed to be related to a previous instrumentation calibration correction. These issues allowed a significantly larger volume of crude oil to be released than otherwise would if the SCADA information had been correctly interpreted and acted upon. In their investigation findings, Enbridge also provided a summary of the events that took place on the day of the intial leak and the actions undertaken following the discovery of the leak. Their findings detailed actions Enbridge personnel should have taken in reponse to the original leak on May 17, 2013, and identified potential shortcomings in their procedures. These findings included a detailed investigation regarding why the leak went undetected for nearly 24 hours, resulting in a significantly increased volume release. Conclusions PHMSA concurs with the Enbridge investigation team determination that: 1. The primary cause of the leak was the presence of an undetected internal corrosion defect that extended through the pipe wall and produced a substantial crude oil release that went undetected for almost 24 hours; and 2. The consequences increased in severity due to misinterpretation of SCADA alarm and tank balance information, thereby delaying the discovery of the real reason for loss of product from the tank. The Enbridge investigation team identified the following items that may also have contributed to this incident: 1. Existing procedures to assess alarm conditions provide Cushing CC operations technicians with little guidance regarding how such assessments should be conducted; 2. A large number of nuisance alarms went off in the control center at the same time that the tank movement alarm was received, which may have partially obscured the importance of that alarm; 3. (b) (7)(F) Page 7 of 8#
Page 8Failure Investigation Report – Enbridge Cushing Tank Farm May 17-18, 2013 4. Cushing CC operations technicians do not have dedicated, 24-hour support staff available to help evaluate and manage alarms; 5. No documented guidance was provided to operations regarding when inhibition and/or flushing should be used as mitigation strategies; 6. Heavy vegetation in site drainage ditches and around ponds may have prevented early detection during routine drive-around site inspections; and 7. An undetected maintenance issue with an underflow pipe flume (a large corrosion hole in the pipe) allowed oil to migrate out of the upper pond, through a second drainage ditch, and into a lower pond, resulting in increased contamination and clean-up costs. As a result of the Enbridge investigation team’s key findings, the following areas received recommendations and procedural improvements aimed at the prevention of similar incidents in the future: • Procedures for locating, inspecting, and mitigating corrosion-prone facilities’ piping segments; • Terminal operating practices related to infrequently used piping; • Tank movement tracking and terminal alarm systems related to leak detection; and • Control center procedures regarding recognizing and assessing leak-related alarms. The procedures related to the prevention of internal corrosion within terminal piping were expanded to incorporate the lessons learned from this accident. Additionally, the replacement tank fill line piping was installed with an internal coating in order to minimize the likelihood of interior corrosion. Appendices A Enbridge Cushing Terminal Map B NRC Report C Operator Accident/Incident Report to PHMSA D Laboratory Analysis PP07 8181 E Operator Incident Investigation Report and Findings Page 8 of 8#
Page 9Appendix A Enbridge Cushing Terminal Map This document is on file at PHMSA#
Page 10NATIONAL RESPONSE CENTER 1-800-424-8802 *** For Public Use *** Information released to a third party shall comply with any applicable federal and/or state Freedom of Information and Privacy Laws Incident Report # 1047579 INCIDENT DESCRIPTION *Report taken at 15 : 33 on 18- MAY - 13 Incident Type: FIXED Incident Cause : EQUIPMENT FAILURE Affected Area : The incident occurred on 18-MAY-13 at 14:00 local time. Affected Medium: OTHER CONTAINMENT ON-SITE SUSPECTED RESPONSIBLE PARTY Organization: ENBRIDGE CUSHING, OK 74023 Type of Organization: PRIVATE ENTERPRISE INCIDENT LOCATION 2101 S. LINWOOD AVE . County: LINCOLN City : CUSHING State : OK Zip: 74023 WITHIN CUSHING TERMINAL SOUTH TANK FARM RELEASED MATERIAL(S) Official Material Name: OIL: CRUDE CHRIS Code: OIL Also Known As: Qty Released: 1500 BARREL(S) DESCRIPTION OF INCIDENT A TRUNK LINE GOING TO A TANK ON THE PROPERTY IS LEAKING, THE LEAK HAS MIGRATED OUTSIDE OF A BERM AND IS SETTLING INTO A CONTAINMENT POND . CAUSE IS UNKNOWN . LINE WILL BE SEALED, DUG UP AND REPLACED. INCIDENT DETAILS Package: N/A Building ID: Type of Fixed Object: TANK FARM Power Generating Facility: UNKNOWN Generating Capacity: Type of Fuel : NPDES: NPDES Compliance: UNKNOWN Fire Involved: NO INJURIES: NO FATALITIES: NO EVACUATIONS : NO Damages: NO DAMAGES Fire Extinguished: UNKNOWN Hospitalized: Empl/Crew: Who Evacuated: Empl/Crew: Passenger: Radius/Area: Passenger : Occupant : Length of Closure Direction of Closure Closure Type Description of Closure Air: N Road : N Waterway: N Major Artery : N#
Page 11Track : N Passengers Transferred : NO Environmental Impact : UNKNOWN Media Interest : NONE Community Impact due to Material: REMEDIAL ACTIONS EVACUATING LINE, DIGGING UP LINE, CLEANUP UNDERWAY, ALL MATERIAL CONTAINED ON-SITE Release Secured: YES Release Rate : Estimated Release Duration: WEATHER ADDITIONAL AGENCIES NOTIFIED Federal : State/Local: OK cc State/Local On Scene: State Agency Number : NOTIFICATIONS BY NRC COLORADO INFO ANALYSIS CENTER (FUSION CENTER) 18-MAY-13 15:39 DHS PROTECTIVE SECURITY ADVISOR (PSA DESK) 18-MAY- 13 15 : 39 DOT CRISIS MANAGEMENT CENTER (MAIN OFFICE) 18 - MAY - 13 15 : 39 U.S. EPA VI (MAIN OFFICE) 18-MAY-13 15:45 GULF STRIKE TEAM (MAIN OFFICE) 18- MAY-13 15:39 NATIONAL INFRASTRUCTURE COORD CTR (MAIN OFFICE) 18-MAY- 13 15 : 39 NOAA RPTS FOR OK (MAIN OFFICE) 18-MAY-13 15:39 NATIONAL RESPONSE CENTER HQ (AUTOMATIC REPORTS) 18-MAY- 13 15 : 39 NRC SENIOR WATCH OFFICER (MAIN OFFICE) 18 - MAY-13 15:45 OFC OF ENV SVC CHEROKEE NATIONS OK (MAIN OFFICE) 18-MAY- 13 15 : 39 SAC AND FOX NATION (EMERGENCY MANAGEMENT) 18-MAY-13 15 : 39 DEQ OKLAHOMA (MAIN OFFICE) 18-MAY-13 15 : 39 ADDITIONAL INFORMATION ALL MATERIAL EXPECTED TO STAY ON PROPERTY, WILL NOTIFY LOCAL AUTHORITIES *** END INCIDENT REPORT # 1047579 ***#
Page 12NOTICE: This report is required by 49 CFR Part 195. Failure to report can result in a civil penalty not to exceed $100,000 for each violation for each day that such violation persists except that the maximum civil penalty shall not exceed $1,000,000 as provided in 49 USC 60122. OMB NO: 2137-0047 EXPIRATION DATE: 01/31/2014 Original Report Date: 06/14/2013 U.S Department of Transportation Pipeline and Hazardous Materials Safety Administration No. 20130208 - 18846 -------------------------- (DOT Use Only) ACCIDENT REPORT - HAZARDOUS LIQUID PIPELINE SYSTEMS A federal agency may not conduct or sponsor, and a person is not required to respond to, nor shall a person be subject to a penalty for failure to comply with a collection of information subject to the requirements of the Paperwork Reduction Act unless that collection of information displays a current valid OMB Control Number. The OMB Control Number for this information collection is 2137-0047. Public reporting for this collection of information is estimated to be approximately 10 hours per response (5 hours for a small release), including the time for reviewing instructions, gathering the data needed, and completing and reviewing the collection of information. All responses to this collection of information are mandatory. Send comments regarding this burden estimate or any other aspect of this collection of information, including suggestions for reducing this burden to: Information Collection Clearance Officer, PHMSA, Office of Pipeline Safety (PHP-30) 1200 New Jersey Avenue, SE, Washington, D.C. 20590. INSTRUCTIONS Important: Please read the separate instructions for completing this form before you begin. They clarify the information requested and provide specific examples. If you do not have a copy of the instructions, you can obtain one from the PHMSA Pipeline Safety Community Web Page at http://www.phmsa.dot.gov/pipeline. PART A - KEY REPORT INFORMATION Report Type: (select all that apply) Original: Supplemental: Yes Final: Yes Last Revision Date: 12/18/2013 1. Operator's OPS-issued Operator Identification Number (OPID): 31947 2. Name of Operator ENBRIDGE PIPELINES (OZARK) L.L.C. 3. Address of Operator: 3a. Street Address 1100 LOUISIANA , SUITE 3300 3b. City HOUSTON 3c. State Texas 3d. Zip Code 77002 4. Local time (24-hr clock) and date of the Accident: 05/18/2013 14:00 5. Location of Accident: Latitude: 35.95885 Longitude: -96.75655 6. National Response Center Report Number (if applicable): 1047579 7. Local time (24-hr clock) and date of initial telephonic report to the National Response Center (if applicable): 05/18/2013 14:25 8. Commodity released: (select only one, based on predominant volume released) Crude Oil - Specify Commodity Subtype: - If "Other" Subtype, Describe: - If Biofuel/Alternative Fuel and Commodity Subtype is Ethanol Blend, then % Ethanol Blend: %: - If Biofuel/Alternative Fuel and Commodity Subtype is Biodiesel, then Biodiesel Blend (e.g. B2, B20, B100): B 9. Estimated volume of commodity released unintentionally (Barrels): 2,246.00 10. Estimated volume of intentional and/or controlled release/blowdown (Barrels): 11. Estimated volume of commodity recovered (Barrels): 2,071.00 12. Were there fatalities? No - If Yes, specify the number in each category: 12a. Operator employees 12b. Contractor employees working for the Operator 12c. Non-Operator emergency responders 12d. Workers working on the right-of-way, but NOT associated with this Operator 12e. General public 12f. Total fatalities (sum of above) 13. Were there injuries requiring inpatient hospitalization? No - If Yes, specify the number in each category: 13a. Operator employees 13b. Contractor employees working for the Operator 13c. Non-Operator emergency responders Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 1313d. Workers working on the right-of-way, but NOT associated with this Operator 13e. General public 13f. Total injuries (sum of above) 14. Was the pipeline/facility shut down due to the Accident? No - If No, Explain: The tank line was idle at the time of the leak - If Yes, complete Questions 14a and 14b: (use local time, 24-hr clock) 14a. Local time and date of shutdown: 14b. Local time pipeline/facility restarted: - Still shut down? (* Supplemental Report Required) 15. Did the commodity ignite? No 16. Did the commodity explode? No 17. Number of general public evacuated: 0 18. Time sequence (use local time, 24-hour clock): 18a. Local time Operator identified Accident: 05/18/2013 14:00 18b. Local time Operator resources arrived on site: 05/18/2013 14:30 PART B - ADDITIONAL LOCATION INFORMATION 1. Was the origin of Accident onshore? Yes If Yes, Complete Questions (2-12) If No, Complete Questions (13-15) - If Onshore: 2. State: Oklahoma 3. Zip Code: 74023 4. City Cushing 5. County or Parish Lincoln 6. Operator-designated location: Specify: 7. Pipeline/Facility name: Cushing Terminal 8. Segment name/ID: Tank 3013 Line Fill 9. Was Accident on Federal land, other than the Outer Continental Shelf (OCS)? No 10. Location of Accident: Totally contained on Operator-controlled property 11. Area of Accident (as found): Underground Specify: Under soil - If Other, Describe: Depth-of-Cover (in): 18 12. Did Accident occur in a crossing? No - If Yes, specify below: - If Bridge crossing – Cased/ Uncased: - If Railroad crossing – Cased/ Uncased/ Bored/drilled - If Road crossing – Cased/ Uncased/ Bored/drilled - If Water crossing – Cased/ Uncased - Name of body of water, if commonly known: - Approx. water depth (ft) at the point of the Accident: - Select: - If Offshore: 13. Approximate water depth (ft) at the point of the Accident: 14. Origin of Accident: - In State waters - Specify: - State: - Area: - Block/Tract #: - Nearest County/Parish: - On the Outer Continental Shelf (OCS) - Specify: - Area: - Block #: 15. Area of Accident: PART C - ADDITIONAL FACILITY INFORMATION 1. Is the pipeline or facility: Interstate 2. Part of system involved in Accident: Onshore Terminal/Tank Farm Equipment and Piping - If Onshore Breakout Tank or Storage Vessel, Including Attached Appurtenances, specify: 3. Item involved in Accident: Pipe Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 14- If Pipe, specify: 3a. Nominal diameter of pipe (in): 3b. Wall thickness (in): 3c. SMYS (Specified Minimum Yield Strength) of pipe (psi): 3d. Pipe specification: 3e. Pipe Seam , specify: - If Other, Describe: 3f. Pipe manufacturer: 3g. Year of manufacture: 3h. Pipeline coating type at point of Accident, specify: - If Other, Describe: - If Weld, including heat-affected zone, specify: - If Other, Describe: - If Valve, specify: - If Mainline, specify: - If Other, Describe: 3i. Manufactured by: 3j. Year of manufacture: - If Tank/Vessel, specify: - If Other - Describe: - If Other, describe: 4. Year item involved in Accident was installed: 5. Material involved in Accident: - If Material other than Carbon Steel, specify: 6. Type of Accident Involved: - If Mechanical Puncture – Specify Approx. size: in. (axial) by in. (circumferential) - If Leak - Select Type: - If Other, Describe: - If Rupture - Select Orientation: - If Other, Describe: Approx. size: in. (widest opening) by in. (length circumferentially or axially) - If Other – Describe: PART D - ADDITIONAL CONSEQUENCE INFORMATION 1. Wildlife impact: 1a. If Yes, specify all that apply: - Fish/aquatic - Birds - Terrestrial 2. Soil contamination: 3. Long term impact assessment performed or planned: 4. Anticipated remediation: 4a. If Yes, specify all that apply: - Surface water - Groundwater - Soil - Vegetation - Wildlife 5. Water contamination: 5a. If Yes, specify all that apply: - Ocean/Seawater - Surface - Groundwater - Drinking water: (Select one or both) - Private Well - Public Water Intake 5b. Estimated amount released in or reaching water (Barrels): 5c. Name of body of water, if commonly known: 6. At the location of this Accident, had the pipeline segment or facility been identified as one that "could affect" a High Consequence Area (HCA) as determined in the Operator's Integrity Management Program? 7. Did the released commodity reach or occur in one or more High Consequence Area (HCA)? 7a. If Yes, specify HCA type(s): (Select all that apply) - Commercially Navigable Waterway: Was this HCA identified in the "could affect" Form PHMSA F 7000.1 (Rev. 12-2012) Pipe Body 24 .281 24,000 Unknown Other Unknown Unknown 1978 Coal Tar 1979 Carbon Steel Leak Other Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 2,246.00 Unnamed tributary to Wildhorse Creek No No#
Page 15determination for this Accident site in the Operator's Integrity Management Program? - High Population Area: Was this HCA identified in the "could affect" determination for this Accident site in the Operator's Integrity Management Program? - Other Populated Area Was this HCA identified in the "could affect" determination for this Accident site in the Operator's Integrity Management Program? - Unusually Sensitive Area (USA) - Drinking Water Was this HCA identified in the "could affect" determination for this Accident site in the Operator's Integrity Management Program? - Unusually Sensitive Area (USA) - Ecological Was this HCA identified in the "could affect" determination for this Accident site in the Operator's Integrity Management Program? 8. Estimated Property Damage: 8a. Estimated cost of public and non-Operator private property damage $ 0 8b. Estimated cost of commodity lost $ 30,000 8c. Estimated cost of Operator's property damage & repairs $ 754,000 8d. Estimated cost of Operator's emergency response $ 5,600,000 8e. Estimated cost of Operator's environmental remediation $ 7,460,274 8f. Estimated other costs $ 0 Describe: 8g. Total estimated property damage (sum of above) $ 13,844,274 PART E - ADDITIONAL OPERATING INFORMATION 1. Estimated pressure at the point and time of the Accident (psig): 15.00 2. Maximum Operating Pressure (MOP) at the point and time of the Accident (psig): 250.00 3. Describe the pressure on the system or facility relating to the Accident (psig): Pressure did not exceed MOP 4. Not including pressure reductions required by PHMSA regulations (such as for repairs and pipe movement), was the system or facility relating to the Accident operating under an established pressure restriction with pressure limits below those normally allowed by the MOP? No - If Yes, Complete 4.a and 4.b below: 4a. restriction? Did the pressure exceed this established pressure 4b. State? Was this pressure restriction mandated by PHMSA or the 5. 2? Was "Onshore Pipeline, Including Valve Sites" OR "Offshore Pipeline, Including Riser and Riser Bend" selected in PART C, Question No - If Yes - (Complete 5a. – 5e. below) 5a. Type of upstream valve used to initially isolate release source: 5b. Type of downstream valve used to initially isolate release source: 5c. Length of segment isolated between valves (ft): 5d. Is the pipeline configured to accommodate internal inspection tools? - If No, Which physical features limit tool accommodation? (select all that apply) - Changes in line pipe diameter - Presence of unsuitable mainline valves - Tight or mitered pipe bends - Other passage restrictions (i.e. unbarred tee's, projecting instrumentation, etc.) - Extra thick pipe wall (applicable only for magnetic flux leakage internal inspection tools) - Other - - If Other, Describe: 5e. For this pipeline, are there operational factors which significantly complicate the execution of an internal inspection tool run? - If Yes, Which operational factors complicate execution? (select all that apply) - Excessive debris or scale, wax, or other wall buildup Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 16- Low operating pressure(s) - Low flow or absence of flow - Incompatible commodity - Other - - If Other, Describe: 5f. Function of pipeline system: 6. Was a Supervisory Control and Data Acquisition (SCADA)-based system in place on the pipeline or facility involved in the Accident? If Yes - 6a. Was it operating at the time of the Accident? 6b. Was it fully functional at the time of the Accident? 6c. Did SCADA-based information (such as alarm(s), alert(s), event(s), and/or volume calculations) assist with the detection of the Accident? 6d. Did SCADA-based information (such as alarm(s), alert(s), event(s), and/or volume calculations) assist with the confirmation of the Accident? 7. Was a CPM leak detection system in place on the pipeline or facility involved in the Accident? - If Yes: 7a. Was it operating at the time of the Accident? 7b. Was it fully functional at the time of the Accident? 7c. Did CPM leak detection system information (such as alarm(s), alert(s), event(s), and/or volume calculations) assist with the detection of the Accident? 7d. Did CPM leak detection system information (such as alarm(s), alert(s), event(s), and/or volume calculations) assist with the confirmation of the Accident? 8. How was the Accident initially identified for the Operator? - If Other, Specify: 8a. If "Controller", "Local Operating Personnel", including contractors", "Air Patrol", or "Guard Patrol by Operator or its contractor" is selected in Question 8, specify the following: 9. Was an investigation initiated into whether or not the controller(s) or control room issues were the cause of or a contributing factor to the Accident? - If No, the Operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) - If Yes, specify investigation result(s): (select all that apply) - Investigation reviewed work schedule rotations, continuous hours of service (while working for the Operator), and other factors associated with fatigue - Investigation did NOT review work schedule rotations, continuous hours of service (while working for the Operator), and other factors associated with fatigue Provide an explanation for why not: - Investigation identified no control room issues - Investigation identified no controller issues - Investigation identified incorrect controller action or controller error - Investigation identified that fatigue may have affected the controller(s) involved or impacted the involved controller(s) response - Investigation identified incorrect procedures - Investigation identified incorrect control room equipment operation - Investigation identified maintenance activities that affected control room operations, procedures, and/or controller response - Investigation identified areas other than those above: Describe: PART F - DRUG & ALCOHOL TESTING INFORMATION Form PHMSA F 7000.1 (Rev. 12-2012) =< 20% SMYS Regulated Trunkline/Transmission Yes Yes Yes Yes Yes No CPM leak detection system or SCADA-based information (such as alarm(s), alert(s), event(s), and/or volume calculations) Yes, specify investigation result(s): (select all that apply) Yes Yes Yes Yes#
Page 171. As a result of this Accident, were any Operator employees tested under the post-accident drug and alcohol testing requirements of DOT's Drug & Alcohol Testing regulations? Yes - If Yes: 1a. Specify how many were tested: 3 1b. Specify how many failed: 0 2. As a result of this Accident, were any Operator contractor employees tested under the post-accident drug and alcohol testing requirements of DOT's Drug & Alcohol Testing regulations? No - If Yes: 2a. Specify how many were tested: 2b. Specify how many failed: PART G – APPARENT CAUSE Select only one box from PART G in shaded column on left representing the APPARENT Cause of the Accident, and answer the questions on the right. Describe secondary, contributing or root causes of the Accident in the narrative (PART H). Apparent Cause: G1 - Corrosion Failure G1 - Corrosion Failure - only one sub-cause can be picked from shaded left-hand column External Corrosion: Internal Corrosion: Yes - If External Corrosion: 1. Results of visual examination: - If Other, Describe: 2. Type of corrosion: (select all that apply) - Galvanic - Atmospheric - Stray Current - Microbiological - Selective Seam - Other: - If Other, Describe: 3. The type(s) of corrosion selected in Question 2 is based on the following: (select all that apply) - Field examination - Determined by metallurgical analysis - Other: - If Other, Describe: 4. Was the failed item buried under the ground? - If Yes : 4a. Was failed item considered to be under cathodic protection at the time of the Accident? If Yes - Year protection started: 4b. Was shielding, tenting, or disbonding of coating evident at the point of the Accident? 4c. Has one or more Cathodic Protection Survey been conducted at the point of the Accident? If "Yes, CP Annual Survey" – Most recent year conducted: If "Yes, Close Interval Survey" – Most recent year conducted: If "Yes, Other CP Survey" – Most recent year conducted: - If No: 4d. Was the failed item externally coated or painted? 5. Was there observable damage to the coating or paint in the vicinity of the corrosion? - If Internal Corrosion: 6. Results of visual examination: Localized Pitting - Other: 7. Type of corrosion (select all that apply): - - Corrosive Commodity - Water drop-out/Acid - Microbiological Yes - Erosion - Other: - If Other, Describe: 8. The cause(s) of corrosion selected in Question 7 is based on the following (select all that apply): - - Field examination - Determined by metallurgical analysis Yes Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 18- Other: - If Other, Describe: 9. Location of corrosion (select all that apply): - - Low point in pipe Yes - Elbow - Other: - If Other, Describe: 10. Was the commodity treated with corrosion inhibitors or biocides? No 11. Was the interior coated or lined with protective coating? No 12. Were cleaning/dewatering pigs (or other operations) routinely utilized? Not applicable - Not mainline pipe 13. Were corrosion coupons routinely utilized? Not applicable - Not mainline pipe Complete the following if any Corrosion Failure sub-cause is selected AND the "Item Involved in Accident" (from PART C, Question 3) is Tank/Vessel. 14. List the year of the most recent inspections: 14a. API Std 653 Out-of-Service Inspection - No Out-of-Service Inspection completed 14b. API Std 653 In-Service Inspection - No In-Service Inspection completed Complete the following if any Corrosion Failure sub-cause is selected AND the "Item Involved in Accident" (from PART C, Question 3) is Pipe or Weld. 15. Has one or more internal inspection tool collected data at the point of the Accident? No 15a. If Yes, for each tool used, select type of internal inspection tool and indicate most recent year run: - - Magnetic Flux Leakage Tool Most recent year: - Ultrasonic Most recent year: - Geometry Most recent year: - Caliper Most recent year: - Crack Most recent year: - Hard Spot Most recent year: - Combination Tool Most recent year: - Transverse Field/Triaxial Most recent year: - Other Most recent year: Describe: 16. Has one or more hydrotest or other pressure test been conducted since original construction at the point of the Accident? No If Yes - Most recent year tested: Test pressure: 17. Has one or more Direct Assessment been conducted on this segment? No - If Yes, and an investigative dig was conducted at the point of the Accident:: Most recent year conducted: - If Yes, but the point of the Accident was not identified as a dig site: Most recent year conducted: 18. Has one or more non-destructive examination been conducted at the point of the Accident since January 1, 2002? No 18a. If Yes, for each examination conducted since January 1, 2002, select type of non-destructive examination and indicate most recent year the examination was conducted: - Radiography Most recent year conducted: - Guided Wave Ultrasonic Most recent year conducted: - Handheld Ultrasonic Tool Most recent year conducted: - Wet Magnetic Particle Test Most recent year conducted: - Dry Magnetic Particle Test Most recent year conducted: - Other Most recent year conducted: Describe: Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 19G2 - Natural Force Damage - only one sub-cause can be picked from shaded left-handed column Natural Force Damage – Sub-Cause: - If Earth Movement, NOT due to Heavy Rains/Floods: 1. Specify: - If Other, Describe: - If Heavy Rains/Floods: 2. Specify: - If Other, Describe: - If Lightning: 3. Specify: - If Temperature: 4. Specify: - If Other, Describe: - If High Winds: - If Other Natural Force Damage: 5. Describe: Complete the following if any Natural Force Damage sub-cause is selected. 6. Were the natural forces causing the Accident generated in conjunction with an extreme weather event? 6a. If Yes, specify: (select all that apply) - Hurricane - Tropical Storm - Tornado - Other - If Other, Describe: G3 - Excavation Damage - only one sub-cause can be picked from shaded left-hand column Excavation Damage – Sub-Cause: - If Excavation Damage by Operator (First Party): - If Excavation Damage by Operator's Contractor (Second Party): - If Excavation Damage by Third Party: - If Previous Damage due to Excavation Activity: Complete Questions 1-5 ONLY IF the "Item Involved in Accident" (from PART C, Question 3) is Pipe or Weld. 1. Has one or more internal inspection tool collected data at the point of the Accident? 1a. If Yes, for each tool used, select type of internal inspection tool and indicate most recent year run: - - Magnetic Flux Leakage Most recent year conducted: - Ultrasonic Most recent year conducted: - Geometry Most recent year conducted: - Caliper Most recent year conducted: - Crack Most recent year conducted: - Hard Spot Most recent year conducted: - Combination Tool Most recent year conducted: - Transverse Field/Triaxial Most recent year conducted: - Other Most recent year conducted: Describe: 2. Do you have reason to believe that the internal inspection was completed BEFORE the damage was sustained? 3. Has one or more hydrotest or other pressure test been conducted since original construction at the point of the Accident? - If Yes: Most recent year tested: Test pressure (psig): Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 204. Has one or more Direct Assessment been conducted on the pipeline segment? - If Yes, and an investigative dig was conducted at the point of the Accident: Most recent year conducted: - If Yes, but the point of the Accident was not identified as a dig site: Most recent year conducted: 5. Has one or more non-destructive examination been conducted at the point of the Accident since January 1, 2002? 5a. If Yes, for each examination, conducted since January 1, 2002, select type of non-destructive examination and indicate most recent year the examination was conducted: - Radiography Most recent year conducted: - Guided Wave Ultrasonic Most recent year conducted: - Handheld Ultrasonic Tool Most recent year conducted: - Wet Magnetic Particle Test Most recent year conducted: - Dry Magnetic Particle Test Most recent year conducted: - Other Most recent year conducted: Describe: Complete the following if Excavation Damage by Third Party is selected as the sub-cause. 6. Did the operator get prior notification of the excavation activity? 6a. If Yes, Notification received from: (select all that apply) - - One-Call System - Excavator - Contractor - Landowner Complete the following mandatory CGA-DIRT Program questions if any Excavation Damage sub-cause is selected. 7. Do you want PHMSA to upload the following information to CGA- DIRT (www.cga-dirt.com)? 8. Right-of-Way where event occurred: (select all that apply) - - Public - If "Public", Specify: - Private - If "Private", Specify: - Pipeline Property/Easement - Power/Transmission Line - Railroad - Dedicated Public Utility Easement - Federal Land - Data not collected - Unknown/Other 9. Type of excavator: 10. Type of excavation equipment: 11. Type of work performed: 12. Was the One-Call Center notified? 12a. If Yes, specify ticket number: 12b. If this is a State where more than a single One-Call Center exists, list the name of the One-Call Center notified: 13. Type of Locator: 14. Were facility locate marks visible in the area of excavation? 15. Were facilities marked correctly? 16. Did the damage cause an interruption in service? 16a. If Yes, specify duration of the interruption (hours) 17. Description of the CGA-DIRT Root Cause (select only the one predominant first level CGA-DIRT Root Cause and then, where available as a choice, the one predominant second level CGA-DIRT Root Cause as well): Root Cause: - If One-Call Notification Practices Not Sufficient, specify: - If Locating Practices Not Sufficient, specify: - If Excavation Practices Not Sufficient, specify: - If Other/None of the Above, explain: G4 - Other Outside Force Damage - only one sub-cause can be selected from the shaded left-hand column Other Outside Force Damage – Sub-Cause: Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 21- If Nearby Industrial, Man-made, or Other Fire/Explosion as Primary Cause of Incident: - If Damage by Car, Truck, or Other Motorized Vehicle/Equipment NOT Engaged in Excavation: 1. Vehicle/Equipment operated by: - If Damage by Boats, Barges, Drilling Rigs, or Other Maritime Equipment or Vessels Set Adrift or Which Have Otherwise Lost Their Mooring: 2. Select one or more of the following IF an extreme weather event was a factor: - Hurricane - Tropical Storm - Tornado - Heavy Rains/Flood - Other - If Other, Describe: - If Routine or Normal Fishing or Other Maritime Activity NOT Engaged in Excavation: - If Electrical Arcing from Other Equipment or Facility: - If Previous Mechanical Damage NOT Related to Excavation: Complete Questions 3-7 ONLY IF the "Item Involved in Accident" (from PART C, Question 3) is Pipe or Weld. 3. Has one or more internal inspection tool collected data at the point of the Accident? 3a. If Yes, for each tool used, select type of internal inspection tool and indicate most recent year run: - Magnetic Flux Leakage Most recent year conducted: - Ultrasonic Most recent year conducted: - Geometry Most recent year conducted: - Caliper Most recent year conducted: - Crack Most recent year conducted: - Hard Spot Most recent year conducted: - Combination Tool Most recent year conducted: - Transverse Field/Triaxial Most recent year conducted: - Other Most recent year conducted: Describe: 4. Do you have reason to believe that the internal inspection was completed BEFORE the damage was sustained? 5. Has one or more hydrotest or other pressure test been conducted since original construction at the point of the Accident? - If Yes: Most recent year tested: Test pressure (psig): 6. Has one or more Direct Assessment been conducted on the pipeline segment? - If Yes, and an investigative dig was conducted at the point of the Accident: Most recent year conducted: - If Yes, but the point of the Accident was not identified as a dig site: Most recent year conducted: 7. Has one or more non-destructive examination been conducted at the point of the Accident since January 1, 2002? 7a. If Yes, for each examination conducted since January 1, 2002, select type of non-destructive examination and indicate most recent year the examination was conducted: - Radiography Most recent year conducted: - Guided Wave Ultrasonic Most recent year conducted: - Handheld Ultrasonic Tool Most recent year conducted: - Wet Magnetic Particle Test Most recent year conducted: - Dry Magnetic Particle Test Most recent year conducted: - Other Most recent year conducted: Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 22Describe: - If Intentional Damage: 8. Specify: - If Other, Describe: - If Other Outside Force Damage: 9. Describe: G5 - Material Failure of Pipe or Weld - only one sub-cause can be selected from the shaded left-hand column Use this section to report material failures ONLY IF the "Item Involved in Accident" (from PART C, Question 3) is "Pipe" or "Weld." Material Failure of Pipe or Weld – Sub-Cause: 1. The sub-cause selected below is based on the following: (select all that apply) - Field Examination - Determined by Metallurgical Analysis - Other Analysis - If "Other Analysis", Describe: - Sub-cause is Tentative or Suspected; Still Under Investigation (Supplemental Report required) - If Construction, Installation, or Fabrication-related: 2. List contributing factors: (select all that apply) - Fatigue or Vibration-related Specify: - If Other, Describe: - Mechanical Stress: - Other - If Other, Describe: - If Original Manufacturing-related (NOT girth weld or other welds formed in the field): 2. List contributing factors: (select all that apply) - Fatigue or Vibration-related: Specify: - If Other, Describe: - Mechanical Stress: - Other - If Other, Describe: - If Environmental Cracking-related: 3. Specify: - Other - Describe: Complete the following if any Material Failure of Pipe or Weld sub-cause is selected. 4. Additional factors: (select all that apply): - Dent - Gouge - Pipe Bend - Arc Burn - Crack - Lack of Fusion - Lamination - Buckle - Wrinkle - Misalignment - Burnt Steel - Other: - If Other, Describe: 5. Has one or more internal inspection tool collected data at the point of the Accident? 5a. If Yes, for each tool used, select type of internal inspection tool and indicate most recent year run: - Magnetic Flux Leakage Most recent year run: - Ultrasonic Most recent year run: - Geometry Most recent year run: - Caliper Most recent year run: - Crack Most recent year run: - Hard Spot Most recent year run: Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 23- Combination Tool Most recent year run: - Transverse Field/Triaxial Most recent year run: - Other Most recent year run: Describe: 6. Has one or more hydrotest or other pressure test been conducted since original construction at the point of the Accident? - If Yes: Most recent year tested: Test pressure (psig): 7. Has one or more Direct Assessment been conducted on the pipeline segment? - If Yes, and an investigative dig was conducted at the point of the Accident - Most recent year conducted: - If Yes, but the point of the Accident was not identified as a dig site - Most recent year conducted: 8. Has one or more non-destructive examination(s) been conducted at the point of the Accident since January 1, 2002? 8a. If Yes, for each examination conducted since January 1, 2002, select type of non-destructive examination and indicate most recent year the examination was conducted: - - Radiography Most recent year conducted: - Guided Wave Ultrasonic Most recent year conducted: - Handheld Ultrasonic Tool Most recent year conducted: - Wet Magnetic Particle Test Most recent year conducted: - Dry Magnetic Particle Test Most recent year conducted: - Other Most recent year conducted: Describe: G6 – Equipment Failure - only one sub-cause can be selected from the shaded left-hand column Equipment Failure – Sub-Cause: - If Malfunction of Control/Relief Equipment: 1. Specify: (select all that apply) - - Control Valve - Instrumentation - SCADA - Communications - Block Valve - Check Valve - Relief Valve - Power Failure - Stopple/Control Fitting - ESD System Failure - Other - If Other – Describe: - If Pump or Pump-related Equipment: 2. Specify: - If Other – Describe: - If Threaded Connection/Coupling Failure: 3. Specify: - If Other – Describe: - If Non-threaded Connection Failure: 4. Specify: - If Other – Describe: - If Defective or Loose Tubing or Fitting: - If Failure of Equipment Body (except Pump), Tank Plate, or other Material: - If Other Equipment Failure: 5. Describe: Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 24Complete the following if any Equipment Failure sub-cause is selected. 6. Additional factors that contributed to the equipment failure: (select all that apply) - Excessive vibration - Overpressurization - No support or loss of support - Manufacturing defect - Loss of electricity - Improper installation - Mismatched items (different manufacturer for tubing and tubing fittings) - Dissimilar metals - Breakdown of soft goods due to compatibility issues with transported commodity - Valve vault or valve can contributed to the release - Alarm/status failure - Misalignment - Thermal stress - Other - If Other, Describe: G7 - Incorrect Operation - only one sub-cause can be selected from the shaded left-hand column Incorrect Operation – Sub-Cause: Damage by Operator or Operator's Contractor NOT Related to Excavation and NOT due to Motorized Vehicle/Equipment Damage No Tank, Vessel, or Sump/Separator Allowed or Caused to Overfill or Overflow No 1. Specify: - If Other, Describe: Valve Left or Placed in Wrong Position, but NOT Resulting in a Tank, Vessel, or Sump/Separator Overflow or Facility Overpressure No Pipeline or Equipment Overpressured No Equipment Not Installed Properly No Wrong Equipment Specified or Installed No Other Incorrect Operation No 2. Describe: Complete the following if any Incorrect Operation sub-cause is selected. 3. Was this Accident related to (select all that apply): - - Inadequate procedure - No procedure established - Failure to follow procedure - Other: - If Other, Describe: 4. What category type was the activity that caused the Accident? 5. Was the task(s) that led to the Accident identified as a covered task in your Operator Qualification Program? 5a. If Yes, were the individuals performing the task(s) qualified for the task(s)? G8 - Other Accident Cause - only one sub-cause can be selected from the shaded left-hand column Other Accident Cause – Sub-Cause: - If Miscellaneous: 1. Describe: - If Unknown: Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 252. Specify: PART H - NARRATIVE DESCRIPTION OF THE ACCIDENT At 2:00 PM, a tank volume change occurred and Operations personnel discovered a leak in the Cushing South Terminal on Tank 3013. The oil made its way via ditch to a small containment pond west of tank 3013. The oil overflowed from that containment into a nearby tributary to Wildhorse Creek and made its way into the large containment pond in the South Terminal. Crews constructed dams to ensure the oil remained on the South Terminal property. The suspected tank line associated with Tank 3013 was evacuated and isolated. Oil in containment ponds was recovered by vac truck and stored in Tanks 3009 & 3010. Piping was exposed and failed pipe will be assessed based on facility integrity plan, cut out and shipped to DNV for further investigation. Approximately 5,000 cubic yards of contaminated soil has been removed from release site. The soil has been moved to on site containment for testing and remediation. The recovery of 17,000 BBLs of oil/water is currently being separated. Once complete, a supplemental report will be filed with the revised volume of commodity recovered. Remediation and cleanup is still underway and is nearing completion. Crews are currently working on seeding the creek banks and conducting daily monitoring of the South containment pond ensuring the water quality out flow meets standard. Update 12/18/13 - Cleanup, remediation and analytical data collection are complete. The banks of the creek have been restored to pre-existing conditions. Monitoring of the remediation site and water quality are also complete. Re-vegetation inspection will continue in 2014 to ensure remediation efforts at the site. File Full Name PART I - PREPARER AND AUTHORIZED SIGNATURE Preparer's Name Stacy Soine Preparer's Title Compliance Analyst Preparer's Telephone Number 218-464-5754 Preparer's E-mail Address stacy.soine@enbridge.com Preparer's Facsimile Number 218-464-5992 Authorized Signature's Name David Stafford Authorized Signature Title Manager US Pipeline Compliance Authorized Signature Telephone Number 218-464-5751 Authorized Signature Email david.stafford@enbridge.com Date 12/18/2013 Form PHMSA F 7000.1 (Rev. 12-2012)#
Page 26Appendix D Laboratory Analysis PP07 8181 This document is on file at PHMSA#
Page 27Appendix E Operator Incident Investigation Report and Findings This document is on file at PHMSA#