PHMSA Report 20240050
PHMSA Report 20240050
Hazardous liquid gravity and reporting-regulated-only incident in JOURDANTON, MCMULLEN County, TX. Reported cause: EQUIPMENT FAILURE. Reported consequences: 0 fatalities, 0 injuries, 0.6 CRUDE OIL released, $4,500 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.
Report number: 20240050.
Operator ID: 4461.
Reported incident date: 5/24/2024 14:16.
Cause detail: FAILURE OF EQUIPMENT BODY (EXCEPT PUMP), TANK PLATE, OR OTHER MATERIAL
Cause detail: ON 5/24/2024, AN 8IN ABOVE GROUND BALL VALVE FAILED ON THE PIPELINE SEGMENT NAMED MARY GARY/GORDON C TO MOONLIGHT PL 8IN OG (T-4 08305). FAILURE OCCURRED IN BODY SEAL OF VALVE RESULTING IN 25 GALLONS OF CRUDE OIL RELEASED. ANOTHER OPERATOR'S TECHNICIAN NOTICED RELEASED WHEN PASSING BY AND NOTIFIED EOG AT 2:16PM AND CONTROLLER SHUT-IN PIPELINE SYSTEM AT 2:25PM. EOG PIPELINE TECH ARRIVED ON-SITE AT 3:15PM TO CONFIRM AND ISOLATE. EOG'S CONTRACTOR ARRIVED SHORTLY AFTER TO ASSIST IN REPLACING VALVE. PRODUCT STAYED WITHIN PIPELINE RIGHT-OF-WAY AND WAS PROMPTLY BIO-REMEDIATED. FAILED VALVE WAS INVESTIGATED BY EOG, VALVE MANUFACTURER, AND 3RD PARTY SUBJECT MATTER EXPERT (SME). FAILURE WAS CAUSED BY A DETERIORATED O-RING IN BODY SEAL. ALL OTHER VALVE COMPONENTS WERE VERIFIED TO BE DESIGNED AND BUILT TO SPECIFICATIONS. THIS WAS NOT RELATED TO AN OVERPRESSURE EVENT ON THIS SYSTEM. O-RING HAS BEEN SENT OFF TO LABORATORY FOR FULL INVESTIGATION AS TO CAUSE OF FAILURE. LABORATORY RESULTS ARE PENDING AT THE TIME OF THIS REPORT SUBMISSION.
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.