PHMSA Report 20250212
PHMSA Report 20250212
Hazardous liquid incident in VENTURA, VENTURA COUNTY County, CA. Reported cause: NATURAL FORCE DAMAGE. Reported consequences: 0 fatalities, 0 injuries, 5.61 CRUDE OIL released, $0 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.
Report number: 20250212.
Operator ID: 32083.
Reported incident date: 8/4/2025 18:00.
Location detail: 14.03
Cause detail: TREES/VEGETATION ROOTS
Cause detail: A TREE BRANCH ALONG SPINNAKER DRIVE, OUTSIDE OF THE HARBOR STATION PROPERTY BOUNDARY, BROKE OFF AND HIT THE DCOR PIPELINE ASSET WITHIN THE STATION. THE BRANCH BROKE OFF A 1/2" FITTING (PRESSURE SENSING LINE) ON THE 6" MOSF TIE-IN LINE NEAR TO WHERE IT ENTER THE 22" VPS PIPELINE (MOP OF 285 PSIG). THE LINE WAS SHUT DOWN AT THE TIME BUT WAS UNDER APPROXIMATELY 227 PSIG STATIC HEAD. THE PRESSURE ALARM LOW (PAL) SWITCH THAT WAS SHEARED OFF BY THE TREE BRANCH WAS SET AT 185 PSIG, TRIGGERING A SCADA AND AUDIBLE ALARM AT THE VPS CONTROLLER WHO IMMEDIATELY SHUT ALL REMOTE-CONTROLLED VALVES THROUGH THE SCADA AND PERFORMED AN EMERGENCY ROW INSPECTION TO IDENTIFY IF THERE WAS A RELEASE. UPON ARRIVING AT HARBOR STATION, THE OPERATOR SUPPORTED POLICE AND FIRE, AND COMMUNICATED THE ACCIDENT TO DCOR MANAGEMENT. EMERGENCY CREWS (POLICE AND FIRE) WERE ALREADY ON SITE, HAVING BEEN NOTIFIED BY A COMMUNITY MEMBER DRIVING PAST THE LOCATION. DCOR PERSONNEL NOTIFIED CAL OES (#25 3868) AND NRC (# 1438900). BOTH REPORTS WERE MADE WITHIN 1HOUR OF IDENTIFYING THE ACCIDENT. DCOR CALLED OUT THEIR RESPONSE CONTRACTOR. BY THE FOLLOWING MORNING, CONTRACTOR HAD REMOVED 3 ROLL-OFF BOXES WITH SOILED MATERIAL, HAD BACKFILLED WITH CLEAN GRAVEL, AND CLEANED SPINNAKER DRIVE ALLOWING THE ROADWAY TO BE REOPEN. THE PAL SWITCH WAS REINSTALLED BY THE 7TH. AND THE LINE RESTARTED. NO OTHER DAMAGE WAS NOTED. DCOR PERSONNEL NOTIFIED NRC PRIOR TO THE 48-HOUR UPDATE REQUIREMENT (NRC #1439048).
PHMSA trend classification: not significant, not serious.
PHMSA standardized cause: NATURAL FORCE DAMAGE — TREES/VEGETATION ROOTS.
PHMSA indexed costs: $50,500 reported total cost, $20,506.013 in 1984 dollars, $50,500 in current-year dollars.
PHMSA trend flags, standardized causes, and indexed costs are analytical fields added to operator-reported incident data. They do not represent final agency causal findings.
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.