Hazardous liquid incident in GLEN MILLS, DELAWARE County, PA. Reported cause: CORROSION FAILURE. Reported consequences: 0 fatalities, 0 injuries, 0.1 REFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID AT AMBIENT CONDITIONS released, $230,000 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.
Report number: 20150163.
Operator ID: 18718.
Reported incident date: 4/10/2015 15:05.
Location detail: 998+54
Cause detail: EXTERNAL CORROSION
Cause detail: ON 4/10/2015 AT APPROXIMATELY 15:05 A LANDOWNER TELEPHONICALLY REPORTED A PETROLEUM ODOR TO THE SPLP CONTROL CENTER. THE LINE WAS SHUTDOWN AND FIELD PERSONNEL WERE DISPATCHED TO THE AREA AND DETECTED A RAINBOW SHEEN ON AN INTERMITTENT DRAINAGE SWALE IN A WOODED AREA ADJACENT TO THE PIPELINE ROW. EMERGENCY RESPONSE AND INCIDENT COMMAND WAS INITIATED AND THE SOURCE OF THE ODOR WAS TRACED TO THE POINT BREEZE TO MONTELLO 12" REFINED PRODUCTS PIPELINE SYSTEM. THIS AREA OF THE PIPELINE WAS EXCAVATED AND A PLIDCO REPAIR CLAMP WAS USED TO EFFECT REPAIR AT THE FAILURE LOCATION. PERMANENT REPAIR VIA CUT OUT AND REPLACEMENT WAS PLANNED HOWEVER THE AREA OF THE FAILURE WAS LOCATED IN A WETLAND AREA THAT IS SUBJECT TO PA DEP PERMITTING. PERMIT APPROVAL PROCESS SIGNIFICANTLY DELAYED PERMANENT REPAIR. AS OF 7/10/2017 THE FAILED SECTION WAS CUT OUT AND REPLACED. THE FAILED SECTION WAS SENT TO A LABORATORY FOR FAILURE ANALYSIS. THE FAILURE ANALYSIS REPORT CONFIRMED THAT THE CAUSE OF THE FAILURE WAS EXTERNAL CORROSION. THE MOST LIKELY MECHANISM FOR THE EXTERNAL CORROSION WAS COATING FAILURE WHICH CAUSED LOCALIZED SHIELDING OF THE CP. IN 2016, DEF/MFL/SMFL/LFM AND UT CRACK ILI TOOLS WERE RUN AND SUBSEQUENT REPAIRS AND REPLACEMENT OF SECTIONS OF THIS PIPELINE WERE AFFECTED INCLUDING THE CUT OUT AND REPLACEMENT OF THIS FAILED SECTION OF PIPE. SUBSEQUENT TO THE REPAIR PROGRAM A HYDROSTATIC PRESSURE TEST WAS COMPLETED TO REQUALIFY THE MOP.
PHMSA trend classification: significant incident, not serious.
PHMSA standardized cause: CORROSION — EXTERNAL.
PHMSA indexed costs: $491,574 reported total cost, $246,606.368 in 1984 dollars, $607,315.588 in current-year dollars.
PHMSA trend flags, standardized causes, and indexed costs are analytical fields added to operator-reported incident data. They do not represent final agency causal findings.
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.