PHMSA Report 20010001
PHMSA Report 20010001
Gas transmission and gathering incident in MONTROSE, MONTROSE County, CO. Reported cause: OTHER. Reported consequences: 0 fatalities, 0 injuries, $92,000 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.
Report number: 20010001.
Operator ID: 19580.
Reported incident date: 20001120.
Cause detail: THERE WAS A FALSE EMERGENCY SHUTDOWN AT THE OLATHE COMPRESSOR STATION DUE TO FAILURE OF THE CONTROL PANEL. IN ADDITION, THE CONTROL PANEL ONLY SENT A PARTIAL ESD SIGNAL, LEAVING THE COMPRESSOR INLET VALVE OPEN, UNDETECTED, FOR ABOUT 5 HOURS. THIS ALLOWED VENTING OF PIPELINE GAS TO ATMOSPHERE. NOTICE OF SITUATION WAS RECEIVED FROM A PRIVATE PARTY AND SUBSEQUENTLY CORRECTED.
PHMSA trend classification: significant incident, not serious.
PHMSA standardized cause: ALL OTHER CAUSES — MISCELLANEOUS.
PHMSA indexed costs: $92,000 reported total cost, $62,171.414 in 1984 dollars, $153,109.058 in current-year dollars.
PHMSA trend flags, standardized causes, and indexed costs are analytical fields added to operator-reported incident data. They do not represent final agency causal findings.
This material provides agency context. It does not replace binding regulatory text, and its legal effect depends on the underlying authority and facts.