Gas transmission and gathering incident in ISOLA, HUMPHREYS County, MS. Reported cause: INCORRECT OPERATION. Reported consequences: 0 fatalities, 0 injuries, 3235 NATURAL GAS released, $0 reported property damage. Operator-reported incident data submitted to PHMSA, generally within 30 days. Records may be supplemented or corrected and do not represent final agency causal findings.
Report number: 20130063.
Operator ID: 19160.
Reported incident date: 6/12/2013 0:08.
Location detail: 843-1B - 0+00
Cause detail: OTHER INCORRECT OPERATION
Cause detail: TGP COMPRESSOR STATION 843; OPERATOR WAS ON SITE; EVENT OCCURRED AFTER STATION CAME ON LINE; RELIEF VALVE OPERATED PREMATURELY; RELIEF VALVE DID NOT SEAT; STATION ESD OCCURRED; INVESTIGATION AND REPAIR OF RELIEF VALVE FOUND A SMALL AMOUNT OF SLUDGE IN O-RING OF RELIEF VALVE WHICH MAY HAVE CONTRIBUTED TO THE EVENT; PRESSURE TRANSMITTERS WERE INSPECTED AND FOUND TO BE IN CALIBRATION; RELIEF VALVE WAS TESTED AND CONSISTENTLY LIFTED DURING TESTING;
PHMSA trend classification: not significant, not serious.
PHMSA standardized cause: INCORRECT OPERATION — OTHER INCORRECT OPERATION.
PHMSA indexed costs: $32,334 reported total cost, $25,646.043 in 1984 dollars, $32,639.112 in current-year dollars.